Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-28 Cont ID  
Sent By cthroop Date 2017-03-28 Time 13:12 Rev Time 0.00
Received By cthroop Date 2017-03-28 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By cthroop Date 2017-03-03 Time 08:08 Rev Time 0.00
Received By cthroop Date 2017-03-03 Time 08:08 Sent To  
Notes
2017-03-03 08:31:28 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN WITH SETBACKS OF GENERATOR AND
 TANK.
 2. IDENTIFY LOCATION OF WINDOWS AND DOORS OF STRUCTURE
 IN PROXIMITY TO GENERATOR AND TANK.
 3. PROVIDE FOUNDATION DETAIL FOR GENERATOR SLAB.
 4. PROVIDE ATTACHMENT DETAIL OF GENERATOR TO SLAB.
 5. CANNOT VERIFY IF TANK IS ABOVE GROUND OR BELOW
 GROUND? PROVIDE CLARIFICATION.
 6. PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 7. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE SUBMITTED PLANS
 AND SUPPORTING DOCUMENTS PER FBC 107.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-02 Cont ID  
Sent By jleahy Date 2017-03-02 Time 16:08 Rev Time 0.00
Received By jleahy Date 2017-03-02 Time 16:08 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-03-28 Cont ID  
Sent By gjohnson Date 2017-03-28 Time 11:50 Rev Time 0.00
Received By gjohnson Date 2017-03-28 Time 11:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By gjohnson Date 2017-03-02 Time 16:53 Rev Time 0.00
Received By gjohnson Date 2017-03-02 Time 16:53 Sent To  
Notes
2017-03-02 16:49:181ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-29 Cont ID  
Sent By njwira Date 2017-03-29 Time 17:38 Rev Time 0.00
Received By njwira Date 2017-03-08 Time 13:42 Sent To  
Notes
2017-03-09 13:42:18RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-03 Cont ID  
Sent By cthroop Date 2017-03-03 Time 08:08 Rev Time 0.00
Received By cthroop Date 2017-02-22 Time 14:06 Sent To  
Notes
2017-02-23 14:06:24ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2017-03-29 Cont ID  
Sent By njwira Date 2017-03-29 Time 17:38 Rev Time 0.00
Received By njwira Date 2017-03-28 Time 15:59 Sent To I
Notes
2017-03-28 11:52:08CONTRACTOR SUBMITTED NEW SURVEY PAGE GPJ 3/28/17

Review Stop Z ZONING
Rev No 2 Status P Date 2017-03-21 Cont ID  
Sent By njwira Date 2017-03-21 Time 14:24 Rev Time 0.00
Received By njwira Date 2017-03-10 Time 13:57 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-01 Cont ID  
Sent By njwira Date 2017-03-01 Time 17:34 Rev Time 0.00
Received By njwira Date 2017-02-24 Time 11:38 Sent To E
Notes
2017-03-01 17:35:503/1/17- FAILED
  
 SF-7
 94-305(B)4- MECHANICAL EQUIPMENT PROJECTS MORE THAN
 4FT. INTO A REQUIRED SETBACK
  
  
 PLEASE CONTACT
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved