Plan Review Details - Permit 17020966
Plan Review Stops For Permit 17020966
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-03 Cont ID  
Sent By ccole Date 2017-03-03 Time 16:28 Rev Time 0.00
Received By ccole Date 2017-03-01 Time 11:17 Sent To  
Notes
2017-03-02 11:17:29RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-24 Cont ID  
Sent By ccole Date 2017-02-24 Time 09:31 Rev Time 0.00
Received By ccole Date 2017-02-22 Time 14:49 Sent To  
Notes
2017-02-23 14:49:45REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-03 Cont ID  
Sent By ccole Date 2017-03-03 Time 16:28 Rev Time 0.00
Received By ccole Date 2017-03-03 Time 16:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-24 Cont ID  
Sent By ccole Date 2017-02-24 Time 09:31 Rev Time 0.00
Received By ccole Date 2017-02-24 Time 09:31 Sent To  
Notes
2017-02-24 10:09:131ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020966
 2/24/17
  
 1) THE GARAGE THERMAL ENVELOPE AND MECHANCAL AND
 ELECTRICAL SYSTEMS CANNOT BE EXCLUDED FROM MEETIMNG
 COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION- 2014
 BECAUSE A NEW AC SYSTEM IS BEING INSTALLED TO CONDITION
 THE SPACE. PLEASE NOTE THERE IS NO EXEMPTION UNDER
 SECTION R101.4.8 . IF THE INTENT IS TO DEHUMIDIFY THE
 SPACE THEN PROVIDE A SYSTEM DESIGNED EXCLUISIVELY FOR
 DEHUMIDIFICATION PURPOSES.
  
 2) INDICATE HOW ACCESS WILL BE PROVIDED TO THE FIRST
 FLOOR AIRHANDLERS
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER
 TO VERIFY COMPLIANCE WITH THE NOTE "NOT TO EXCEED 200
 CFM" OF EXHAUST.
  
 4) INDICATE HOW THE KITCHEN HOOD EXHAUST SYSTEM AND O/A
 DCT WILL FUNCTION TOGETHER AND SUBMIT SPECS FOR THE
 HOOD EXHAUST SYSTEM AND MOTORIZED DAMPER-
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  