Plan Review Details - Permit 17020917
Plan Review Stops For Permit 17020917
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-08 Cont ID  
Sent By jwitmer Date 2017-08-08 Time 06:01 Rev Time 0.00
Received By jwitmer Date 2017-08-07 Time 16:56 Sent To  
Notes
2017-08-08 07:30:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020917
 ADD: 7711 S. DIXIE HWY. / BEALLS OUTLET
 CONT: TBD/ TO BE DETERMINED
 TEL: 312-522-5835
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. AUGUST 07/2017
 ACTION: BUILDING PROVISO.
  
 1A) BUILDING PROVISO. 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 1B) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 1C) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-10 Cont ID  
Sent By jwitmer Date 2017-07-10 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2017-07-10 Time 08:03 Sent To  
Notes
2017-07-10 08:09:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020917
 ADD: 7711 S. DIXIE HWY. BEALLS OUTLET
 CONT: TBD/ TO BE DETERMINED
 TEL: 312-522-5835
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY 10/2017
 ACTION: DENIED.
  
 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) SHEET LS-1 AND ALL A SHEETS ARE COPIES OF PLANS
 SIGNED AND SEALED ELECTRONICALLY AND THEN PRINTED
 OUT!!!!!!! PLEASE NOTE ALL OF THE MEP AND FIRE ALARM
 PLANS ARE ALSO PAPER FORMS OF AN ELECTRONIC
 SIGNATURE!!!!
  
 IF THE PLANS WERE ORIGINALLY SENT TO US ELECTRONICALLY
 THEN WE WOULD ACCEPT THE ELECTRONIC SIGNATURE, BUT ONCE
 THE PLANS ARE PRINTED AND SUBMITTED TO THE BUILDING
 DEPARTMENT WE HAVE LOST THE ABILITY TO ENSURE THEY
 ELECTRONIC SIGNAURE IS REAL. !!!!!
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEES SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) CORRECTED.
  
  
 3A) BUILDING PROVISO. 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 3B) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 3C) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-30 Cont ID  
Sent By jwitmer Date 2017-05-30 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2017-05-30 Time 07:15 Sent To  
Notes
2017-05-30 08:31:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020917
 ADD: 7711 S. DIXIE HWY. BEALLS OUTLET
 CONT: TBD/ TO BE DETERMINED
 TEL: 312-522-5835
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 30/2017
 ACTION: DENIED.
  
 1) SHEET LS-1 AND A SHEETS ARE COPIES OF PLANS SIGNED
 AND SEALED ELECTRONICALLY. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 2) DENIED. SHEET A-8.4 & A-8.6 BOTH SHOW THE
 INSTALLATION OF 5/8 INCH CDX WALL SHEATHING
 (CONSTRUCTION TYPE IIB). SHOW COMPLIANCE WITH 2014
 FBC-B 603.1.1FIRE RETARDANT TREATED WOOD SHALL BE
 PERMITTED IN: 1.2. NONBEARING EXTERIOR WALLS WHERE
 FIRE-RESISTANCE RATED CONSTRUCTION IS NOT REQUIRED.
  
  
 3A) BUILDING PROVISO. 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 3B) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 3C) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-28 Cont ID  
Sent By jwitmer Date 2017-02-28 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2017-02-27 Time 17:11 Sent To  
Notes
2017-02-28 11:49:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020917
 ADD: 7711 S. DIXIE HWY. BEALLS OUTLET
 CONT: TBD/ TO BE DETERMINED
 TEL: 312-522-5835
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 28/2017
 ACTION: DENIED
  
 1A) THE COVERSHEET, A1 LIST THE WIND DESIGN CRITERIA
 THE EXPOSURE B. PLEASE NOTE THIS IS TENANT LOCATION IS
 CONSIDERED A C EXPOSURE , ON THE EAST AND WEST
 EXPOSURES. THE EAST IS THE LARGE PARKING LOT AND THE
 WEST THE BACK PARKING LOT, RAILROAD RIGHT OF WAY AND
 GOLF COURSE. PLEASE ALSO GIVE THE MEAN ROOF HEIGHT FOR
 THIS TENANT SPACE.
 2014 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY,
 AND GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY
 TO ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET (30 M)
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) IN THE UPWIND DIRECTION AND A WIDTH
 GREATER THAN 150 FEET (46 M).
  
 DEFINITIONS: MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF
 EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE
 ROOF SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR
 ROOF ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES.
  
 1B) THE COVERSHEET A-1 AND SHEET LS-1 THE LIFE SAFETY
 SHEET BOTH SHOW UNDER THE HEADING LIFE SAFETY DATA SHOW
 THE EMPLOYEE LOUNGE WITH 203 SQUARE FEET / 50 SQ. FT.
 PER PERSON = 5 OCCUPANTS. A LOUNGE IS CLOSER TO A A2
 OCCUPANCY WHERE THE OCCUPANCY IS FIGURED AT 15 SQ. FT./
 OCCUPANT OR 14 OCCUPANTS.
  
 1C) PLEASE NOTE THE CHANGE IN THE OCCUPANT LOAD IN THE
 LOUNGE PUTS THE TOTAL COUNT AT 512 OCCUPANTS. THE
 OCCUPANT LOAD OF 503 INDICATES THE REQUIRED WIDTH OF
 100.6 INCHES. THE PROPOSED AMOUNT OF EGRESS WIDTH
 INDICATES 224 INCHES. THERE ARE MANY EMERGENCIES WHERE
 THERE IS NO LOSS OF POWER AND THE AUTOMATIC HORIZONTAL
 DOORS ARE STILL ACTIVE. WHEN THE ACTIVE DOOR IS
 AUTOMATICALLY ACTIVATED IT WILL BLOKE THE BREAK AWAY
 DOOR IMPEDING THE EXITING CAPACITY TO ONLY ALLOW FOR 34
 INCH. / 0.2= 170 OCC. X3= 510 OCCUPANTS. THE OCCUPANT
 LOAD COUNT ALSO INDICATES THE USE OF VESTIBULE 1 & 2,
 NOT SHOWN ON PLANS?
 ALSO REVIEW FBC-B 1005.3.2 OTHER EGRESS COMPONENTS AND
 EXCEPTION. 903.3.1.1 AND AN EMERGENCY VOICE/ ALARM
 COMMUNICATION SYSTEM IN ACCORDANCE WITH 907.5.2.2.
  
 1D) THE LIFE SAFETY SHEET SHOW THE EGRESS AISLES MARKED
 OUT WITH THE EXCEPTION TO THE REAR EXIT DOOR. FBC-B
 1017.3 AISLES IN GROUPS B AND M.
 IN GROUP B AND M OCCUPANCIES, THE MINIMUM CLEAR AISLE
 WIDTH SHALL BE DETERMINED BY SECTION 1005.1 FOR THE
 OCCUPANT LOAD SERVED, BUT SHALL NOT BE LESS THAN 36
 INCHES.
  
 2) SHEET A-2.1 SHOWS THE WIND DESIGN CRITERIA AGAIN AS
 A B EXPOSURE, SEE COMMENT ABOVE PLEASE CORRECT.
 PLEASE ALSO PROVIDE THE MEAN ROOF HEIGHT OF THE
 BUILDING, WITH THE BUILDING BEING LOCATED IN A C
 EXPOSURE, THERE WILL BE MULTIPLIERS FOR THE C EXPOSURE
 AND FOR THE HEIGHT OF THE BUILDING. A HEIGHT AND
 EXPOSURE ADJUSTMENT COEFFICIENT, * SHALL BE DETERMINED
 FROM TABLE 1609.7.2. ASCE 7-10.
  
 3) SHEET A-2.1 SHOWS A PRESSURE SCHEDULE FOR ZONES
 1,2,3,4 & 5. PLEASE NOTE FOR THE ROOF ZONES THE CHART
 STARTS AT 20 SQ. FT. FOR ROOF ZONES WE USE 10 SQ. FT.
 FOR ALL ZONES SINCE YOU ARE LOOKING AT THE FASTENERS.
 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. SHOWS RANGES
 OF SQ. FT. AREA, THE RANGE IS TO LARGE LESS THAN 20 SQ.
 FT., AND 20 SQ. FT. TO 100 SQ. FT. PLEASE SEE THE
 RANGES SET IN THE FBC-B TABLE 1609.6.2 AND ASCE 7-10
 FIGURE 30.5-1 ENCLOSED BUILDINGS. EFFECTIVE WIND AREA
 10, 20, 50, 100 SF.
  
 4) NOT USED.
  
 5) SHEET A-2.1 PLEASE UPDATE THE WIND PRESSURES, THEY
 ARE LOW FOR A C EXPOSURE AND HEIGHT MULTIPLIERS. 2014
 FBC-B TABLE 1609.7.2. HEIGHT AND EXPOSURE.
  
 6A) SUBMIT THE PRODUCT APPROVALS OR INDICATE THAT YOU
 WOULD LIKE TO MAKE THE PRODUCT APPROVALS AS A DEFERRED
 SUBMITTAL. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 6B) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 6C) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7A) SHEET A-8.2 THE FRONT ELEVATION SHOWS 2 NEW
 HORIZONTAL SLIDING DOORS. THE NEW HORIZONTAL SLIDING
 DOORS WILL NEED TO SHOW COMPLIANCE WITH 2014 FBC-B
 1008.1.4.3 HORIZONTAL SLIDING DOORS (1-8).
  
 7B) THE NEW FRONT ENTRY DOORS AS WELL AS THE NEW REAR
 EXIT WILL NEED TO SHOW COMPLIANCE WITH THE 2014 FBC- B
 SECTION : 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE SHALL NOT BE PROVIDED WITH A LATCH OR LOCK UNLESS
 IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7C) SHEET A-8.2 THE NEW FRONT ENTRY DOORS SHOW A NEW
 TRANSOM ABOVE. SHEET A-8.3 DETAIL # 3 ALSO INDICATES
 NEW HSS TUBE STEEL COLUMN AND HORIZONTAL MULLION, ALL
 FIELD WELDS OF THE TOP BOTTOM PLATES OF THE COLUMN AND
 HORIZONTAL MULLION. WHAT IS MISSING FROM DETAIL 5 SHEET
 A-8.3 DOES NOT INDICATE HOW THE TOP PLATE WILL BE
 ANCHORED TO THE STRUCTURE ABOVE. 107. 2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THIS WOULD BE PART OF THE
 COMPONENTS AND CLADDING SYSTEM 1609.6.4.4.1 COMPONENTS
 & CLADDING. FLORIDA.
  
 7D) WELDED OR BOLTED CONNECTIONS THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS.
 2014 FBC-B 2204.1 WELDING
 201404.4.2 BOLTING.
  
 8) SHEET A-8.3 DETAIL A AND DETAIL # 9 SHOWS THE NEW
 EXTERIOR WALL WITH ? INCH FIRE RESISTANT TREATED
 PLYWOOD AND 3 COAT 7/8 INCH THICK CEMENTITIOUS FINISH.
 PLEASE PROVIDE IF THIS IS A 3 COAT CEMENT PLASTER
 (STUCCO) OR IF THIS IS GOING TO BE EFIS SYSTEMS?
 ADDITIONAL COMMENTS WILL NEED TO BE ADDRESSED WHEN THE
 SYSTEM IS KNOWN. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9) DISCREPANCY IN PLANS, SHEET A-8.2 INDICATES THE
 PLANS ARE DRAWN TO 1/8 INCH SCALE, THE NEW CURVED
 ARCHITECTURAL ELEMENT FRONT CENTER OF THE BUILDING
 SCALES OUT AT 42 FEET ABOVE GRADE WHEREAS SHEET A-8.4
 DETAIL # 1 IN 3/16TH SCALE INDICATES APPROXIMATELY 30
 FEET IN ELEVATION. IT APPEARS THAT NEW EFIS TRIM WILL
 BE USED ON THE NEW ARCHITECTURAL ELEMENT. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. ALSO SEE FBC-B
 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION. ON
 BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH
 THE FOLLOWING LIMITATIONS: 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 10) SHEET A-2 INTERIOR DEMO VERSES A-2.1 & A-8.5. THE
 INTERIOR DEMO SHEET SHOWS AN ALUMINUM LADDER AND
 HANDRAIL SYSTEM BEING REMOVED. PLEASE PROVIDE WHERE
 THIS STAIRWAY WAS LEADING TO, IT APPEARS THIS IS THE
 MEANS OF EGRESS TO THE ROOF TOP ROOM WHICH RTU IS
 LOCATED? ALL OF THE MECHANICAL EQUIPMENT ON THE ROOF
 WILL NEED ACCESS SINCE IT IS LOCATED HIGHER THAN 16
 FEET FROM GRADE.
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET SUCH ACCESS
 SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS OF
 ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-07 Cont ID  
Sent By jpearson Date 2017-08-07 Time 10:40 Rev Time 0.00
Received By jpearson Date 2017-08-07 Time 10:40 Sent To  
Notes
2017-08-07 10:40:19NO CHANGES TO ELECTRICAL PLANS PREVIOUSLY APPROVED BY
 RLECKY. STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-01 Cont ID  
Sent By rlecky Date 2017-06-01 Time 11:37 Rev Time 0.00
Received By rlecky Date 2017-06-01 Time 11:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By rlecky Date 2017-03-02 Time 12:26 Rev Time 0.00
Received By rlecky Date 2017-03-02 Time 11:48 Sent To  
Notes
2017-03-02 12:27:25 
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 EXISTING ELECTRIC SERVICE. NEC 110.9, 110.10
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22, 110.24
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-08-02 Cont ID  
Sent By pleduc Date 2017-08-02 Time   Rev Time 0.00
Received By pleduc Date 2017-08-02 Time 12:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By pleduc Date 2017-06-29 Time   Rev Time 0.00
Received By pleduc Date 2017-06-28 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By pleduc Date 2017-05-24 Time   Rev Time 0.00
Received By pleduc Date 2017-05-23 Time 16:21 Sent To  
Notes
2017-05-23 17:05:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE AN INDICATION FOR A "R" SIGN
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-01 Cont ID  
Sent By pleduc Date 2017-03-01 Time   Rev Time 0.00
Received By pleduc Date 2017-03-01 Time 13:52 Sent To  
Notes
2017-03-01 15:36:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET A 1 - THERE APPEARS TO BE A DISCREPANCY IN THE
 INDICATED OCCUPANCY LOAD CALCULATIONS RELATING TO THE
 LOUNGE, THE TOTAL OCCUPANCY AND THE EXIT WIDTHS.
  
 PER THE FFPC, 5TH EDITION, CHAPTER 7, MEANS OF EGRESS,
 THE LOUNGE IS CONSIDERED AN ASSEMBLY SPACE AND SUBJECT
 TO AN OCCUPANCY CALCULATION OF 15/SQ FT.
  
 ADDITIONALLY, PLEASE REVIEW THE DOOR SCHEDULE DOOR
 WIDTHS AND PROVIDE ACCURATE EXIT OPENING WIDTHS TO
 ENSURE ADAQUATE EXIT CAPACITY. THE SLIDING DOORS MAY
 NOT PROVIDE ADAQUATE WIDTHS IF THEY DO NOT OPERATE AND
 THE EMEERGENCY FORCE OPEN IS APPLIED.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY.
  
  
  
 2)
 SHEET A 1 - THERE IS NO INDICATIONS IF THE OCCUPANCY
 WILL BE OPEN RTO THE PUBLIC DURING CONSTRUCTION
 ACTIVITY. PLEASE INDICATE INTENTIONS AND IF TO REMIN
 OPEN PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING HOW
 ALL EXITS WILL BE MAINTAINED (PHASES), FIRE ALARM, AND
 FIRE SPRINKLER SYSTEMS WILL BE FUNCTIONAL.
  
 PLEASE REVIEW AND CLARIFY WITH DETAILS.
  
  
  
 3)
 SHEET A 4 - THERE ARE NO DIMENSIONS INDICATED ON THE
 PLAN FOR THE TAPE ON THE FLOOR SHOWING ISLES.
  
 PER NFPA 101,
  
 36.2.5.4 AISLES LEADING TO EACH EXIT SHALL BE REQUIRED,
 AND THE AGGREGATE WIDTH OF SUCH AISLES SHALL BE NOT
 LESS THAN THE REQUIRED WIDTH OF THE EXIT.
  
 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN.
 (915 MM) IN CLEAR WIDTH.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
 4)
 SHEET A 4 - THERE IS NO INDICATION OF ISLE TAPE FOR
 REAR EXIT PATH LEADING TO VESTIBULE # 1.
  
 36.2.5.4 AISLES LEADING TO EACH EXIT SHALL BE REQUIRED,
 AND THE AGGREGATE WIDTH OF SUCH AISLES SHALL BE NOT
 LESS THAN THE REQUIRED WIDTH OF THE EXIT.
  
 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN.
 (915 MM) IN CLEAR WIDTH.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
  
 5)
 SHEETS A 8.2 & 8.4 - THERE IS NO INDICATION OF THE
 REQUIRED LIGHTWEIGHT ROOF SIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE AN INDICATION FOR A "R" SIGN
  
  
  
 6)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 7)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-14 Cont ID  
Sent By cpuell Date 2017-08-14 Time 09:24 Rev Time 0.00
Received By cpuell Date 2017-07-31 Time 09:37 Sent To  
Notes
2017-08-01 09:37:48C38

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-12 Cont ID  
Sent By gjohnson Date 2017-07-12 Time 16:24 Rev Time 0.00
Received By gjohnson Date 2017-06-23 Time 14:59 Sent To  
Notes
2017-06-26 14:59:41C38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-06 Cont ID  
Sent By gjohnson Date 2017-06-06 Time 15:05 Rev Time 0.00
Received By gjohnson Date 2017-05-19 Time 14:33 Sent To  
Notes
2017-05-22 14:35:42C40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By gjohnson Date 2017-03-06 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2017-02-21 Time 14:11 Sent To  
Notes
2017-02-22 14:13:09C37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-28 Cont ID  
Sent By jwitmer Date 2017-02-28 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2017-02-27 Time 17:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-08-10 Cont ID  
Sent By ccole Date 2017-08-10 Time 09:59 Rev Time 0.00
Received By ccole Date 2017-08-10 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-06 Cont ID  
Sent By ccole Date 2017-07-06 Time 09:41 Rev Time 0.00
Received By ccole Date 2017-07-06 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-30 Cont ID  
Sent By ccole Date 2017-05-30 Time 10:01 Rev Time 0.00
Received By ccole Date 2017-05-30 Time 09:19 Sent To  
Notes
2017-05-30 10:20:261ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020917
 5/30/17
  
 RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGY EFFICIENCY FORM C402-2014
 CANNOT BE USED TO SHOW COMPLAINCE FOR AN ADDITION, OR A
 NEW CONDITIONED SPACE UNLESS THE VALUES FOR THE
 REQUIRED AND INSTALLED ENVELOPE COMPONENTS AND BUILDING
 SYSTEMS ARE ENTERED IN THE EFFICIENCY COLUMNS- N/A
 CANNOT BE ENTERED IN PLACE OF THESE VALUES. PLEASE NOTE
 THAT THE PERFORMANCE COMPLIANCE OPTION USING THE
  
 ENERGYGAUGE SOFTWARE MAY BE USED TO SHOW COMPLIANCE-
 SEE SECTION C101.5.1 FBC-14 ENERGY CONSERVATION.
  
 2) DEMAND CONTROLLED VENTILATION IS REQUIRED FOR THE
 SALES AREA IN ACCORDANCE WITH SECTION C403.2.5.1.
 PLEASE REVISE THE PLAN TO SHOW COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-28 Cont ID  
Sent By ccole Date 2017-02-28 Time 16:23 Rev Time 0.00
Received By ccole Date 2017-02-28 Time 16:23 Sent To  
Notes
2017-02-28 17:06:591ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020917
 2/28/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE PREVIOUSLY UNCONDITIONED STORAGE AND RECEIVING
 AREA THAT IS NOW BEING CONDITIONED MUST BE IN
 COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION
 CODE-2014. REFER TO SECTIONS C101.4.3 AND C401.2 AND
 PROVIDE DOCUMENTATION OF COMPLIANCE. PLEASE NOTE THIS
 NEWLY CONDITIONED AREA IS CLASSIFIED AS AN ADDITION PER
 SECTION C202.
  
 3) SHEET M-1: CLARIFY THE SCOPE OF WORK FOR THE RTU'S.
 THE NOTES INDICATE BOTH EXISTING AND BEING REPLACED.
  
 4) INDICATE HOW ACCESS IS BEING PROVIDED TO THE RTU'S-
 SEE SECTION 306.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-08-11 Cont ID  
Sent By gjohnson Date 2017-08-11 Time 09:52 Rev Time 0.00
Received By gjohnson Date 2017-08-11 Time 09:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-07-12 Cont ID  
Sent By gjohnson Date 2017-07-12 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2017-07-12 Time 15:17 Sent To  
Notes
2017-07-12 16:24:011ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT.-10.1 DETAIL #4 C D SHOW THE HEIGHT OF BREAK
 ROOM SINK AT 36" IT SHALL BE 34" MAX. PER FBC ACC 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2. PLEASE SHOW CLEAR FLOOR SPACE FOR BREAKROOM SINK.
 PER FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3. PLANS SHALL BE SIGNED AND SEALED PER FAC
 61G15-23.001 SEE ALSO BUILDINGS COMMENTS
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-06 Cont ID  
Sent By gjohnson Date 2017-06-06 Time 14:59 Rev Time 0.00
Received By gjohnson Date 2017-06-06 Time 14:43 Sent To  
Notes
2017-06-06 15:05:252ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SINK IN EMPLOYEE LOUNGE SHALL COMPLY WITH FBC
 ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By gjohnson Date 2017-03-06 Time 12:52 Rev Time 0.00
Received By gjohnson Date 2017-03-06 Time 09:52 Sent To  
Notes
2017-03-06 13:14:571ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER WISER DIAGRAM. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 2. TEMPERED WATER REQUIRED AT LAV FAUCETS FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2017-08-11 Cont ID  
Sent By llouie Date 2017-08-11 Time   Rev Time 0.00
Received By llouie Date 2017-08-11 Time   Sent To I
Notes
2017-08-11 16:34:15PROVISO:
  
 1.) SEPARATE PERMIT REQUIRED FOR SIGNAGE. SIGNAGE NOT A
 PART OF THIS REVIEW.

Review Stop Z ZONING
Rev No 3 Status P Date 2017-07-03 Cont ID  
Sent By llouie Date 2017-07-03 Time   Rev Time 0.00
Received By llouie Date 2017-06-30 Time   Sent To  
Notes
2017-07-03 09:56:22PROVISO:
  
 1.) SEPARATE PERMIT REQUIRED FOR SIGNAGE.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By llouie Date 2017-05-24 Time   Rev Time 0.00
Received By llouie Date 2017-05-24 Time   Sent To  
Notes
2017-05-24 15:34:27SEPARATE PERMIT REQUIRED FOR NEW EXTERIOR SIGNAGE.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-03 Cont ID  
Sent By Llouie Date 2017-03-03 Time   Rev Time  
Received By llouie Date 2017-03-03 Time   Sent To  
Notes
2017-03-03 15:19:56SEPARATE PERMIT REQUIRED FOR NEW EXTERIOR SIGNAGE.