Plan Review Details - Permit 17020814
Plan Review Stops For Permit 17020814
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-03 Cont ID  
Sent By rmcdouga Date 2017-03-03 Time 07:00 Rev Time 0.00
Received By rmcdouga Date 2017-03-03 Time 06:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By rmcdouga Date 2017-03-14 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2017-03-14 Time 17:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By rmcdouga Date 2017-03-03 Time 07:24 Rev Time 0.00
Received By rmcdouga Date 2017-03-03 Time 06:46 Sent To  
Notes
2017-03-03 07:42:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT APPLICATION LISTS A POOL HEATER IN THE
 WORK DESCRIPTION. THE PLANS SPECIFY THAT THERE IS NO
 HEATER AND NONE IS SHOWN ON THE PLANS. PLEASE CLARIFY.
 FBC 107.2.1
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-14 Cont ID  
Sent By rmcdouga Date 2017-03-14 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2017-03-14 Time 14:18 Sent To  
Notes
2017-03-14 14:18:22RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-03 Cont ID  
Sent By rmcdouga Date 2017-03-03 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2017-02-17 Time 16:19 Sent To  
Notes
2017-02-17 16:19:58ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By rmcdouga Date 2017-03-14 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2017-03-14 Time 17:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By rmcdouga Date 2017-03-03 Time 07:09 Rev Time 0.00
Received By rmcdouga Date 2017-03-03 Time 07:09 Sent To  
Notes
2017-03-03 07:22:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THAT THE TWO SPEED HAYWARD
 SP2615X202S POOL PUMP HAS A MAXIMUM FLOW RATE OF 122
 GPM. THE WATER VELOCITY WILL EXCEED 8 FEET PER SECOND
 WITH THE 2" MAIN DRAIN SUCTION PIPE SPECIFIED ON THE
 PLANS. FBC-R4501.6.3
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-24 Cont ID  
Sent By njwira Date 2017-02-24 Time 16:38 Rev Time 0.00
Received By njwira Date 2017-02-21 Time 13:34 Sent To  
Notes
2017-02-24 16:39:462/24/17- PASSED
  
 TREE ALTERATION PERMIT REQUIRED TO MOVE A TREE
 POOL EQUIPMENT IS 12FT. FROM THE PROPERTY LINE MEETING
 SETBACK REQUIREMENTS
 13FT. REAR SETBACK MEETS 5FT. REQUIREMENT
 SIDE SETBACK IS 19.83FT. MEETING 5FT. REQUIREMENT
  
  
 PLEASE CONTACT
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved