Plan Review Details - Permit 17020797
Plan Review Stops For Permit 17020797
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-27 Time 11:17 Rev Time 0.00
Received By shill Date 2017-06-27 Time 11:17 Sent To  
Notes
2017-06-27 11:21:30#17020797 - PAVING (INCLUDING RAMPS)
 #17020806 - CONVENIENCE STORE REMODEL
 #17020803 - NEW 6K DIESEL FUEL TANK AND 4 NEW FUEL
 DISPENSING ISLANDS
 #17030189 - DUMPSTER ENCLOSURE
  
 ****PROVISOS****
  
 ITEMS REQUIRING SEPARATE PERMITS, NOT REVIEWED AT THIS
 TIME (APPLICATION, PLANS, AND FEES):
  
 CCTV
 SIGNAGE
 SITE LIGHTING (PROVIDE STRUCTURAL DETAILS, SITE PLAN
 AND CALCULATIONS FOR POLES AND FIXTURES)
 VERIFY WITH ZONING - A SEPARATE LANDSCAPING PERMIT MAY
 BE REQUIRED
 CANOPY
 RELOCATION OF VACUUM
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By shill Date 2017-05-24 Time 14:18 Rev Time 0.00
Received By shill Date 2017-05-23 Time 09:30 Sent To  
Notes
2017-05-24 14:18:57****CORRECTIONS****
  
 #17020797 - PAVING (INCLUDING RAMPS)
 #17020806 - CONVENIENCE STORE REMODEL
 #17020803 - NEW 6K DIESEL FUEL TANK AND 4 NEW FUEL
 DISPENSING ISLANDS
 #17030189 - DUMPSTER ENCLOSURE
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471.
  
 ENGINEER HAS INDICATED THAT HE WILL TO COME TO THIS
 OFFICE AND SIGN AND SEAL THE PLANS.
  
 THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS:
  
 ****PROVISOS****
  
 ITEMS REQUIRING SEPARATE PERMITS, NOT REVIEWED AT THIS
 TIME (APPLICATION, PLANS, AND FEES):
  
 CCTV
 SIGNAGE
 SITE LIGHTING (PROVIDE STRUCTURAL DETAILS, SITE PLAN
 AND CALCULATIONS FOR POLES AND FIXTURES)
 VERIFY WITH ZONING - A SEPARATE LANDSCAPING PERMIT MAY
 BE REQUIRED
 CANOPY
 RELOCATION OF VACUUM
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By shill Date 2017-03-06 Time 09:26 Rev Time 0.00
Received By shill Date 2017-03-06 Time 09:21 Sent To  
Notes
2017-03-06 09:26:10****CORRECTIONS****
 #17020797 - PAVING (INCLUDING RAMPS)
 #17020806 - CONVENIENCE STORE REMODEL (AND RELOCATION
 OF VACUUM?)
 #17020803 - NEW 6K DIESEL FUEL TANK AND 4 NEW FUEL
 DISPENSING ISLANDS
 #17030189 - CANOPY OVER FUEL DISPENSERS - SUBMIT
 APPLICATION
  
 ITEMS REQUIRING SEPARATE PERMITS, NOT REVIEWED AT THIS
 TIME (APPLICATION, PLANS, AND FEES):
 DUMPSTER ENCLOSURE
 CCTV
 SIGNAGE
 SITE LIGHTING (PROVIDE STRUCTURAL DETAILS, SITE PLAN
 AND CALCULATIONS FOR POLES AND FIXTURES)
 VERIFY WITH ZONING - A SEPARATE LANDSCAPING PERMIT MAY
 BE REQUIRED
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS PROJECT, FBC
 109. THE VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD
 AND PROFIT, EVEN IF PROVIDED BY OTHERS. IF THIS IS A
 LABOR ONLY CONTRACT, PROVIDE THE INVOICES FOR THE
 MATERIALS AS WELL AS THE CONTRACT.
  
 PROVIDE VALUE FOR EACH PERMIT (17020797, 17020806,
 17020803, 17030189). THE GRADING AND DRAINAGE VALUE
 SHOULD BE INCLUDED IN A SEPARATE ENGINEERING PERMIT, IF
 ENGINEERING DETERMINES THAT A SEPARATE ENGINEERING
 PERMIT IS REQUIRED.
  
 CONTACT THE ENGINEERING DEPARTMENT DIRECTLY TO
 DETERMINE IF A SEPARATE ENGINEERING PERMIT IS REQUIRED:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PROVIDE A PERMIT APPLICATION FOR PERMIT 17030189,
 THE CANOPY. THE PERMIT APPLICATION SHOULD BE COMPLETE
 AND ACCURATE. THE QUALIFIER'S NAME SHOULD BE INCLUDED
 ON LINE "CONTRACTOR (CERT. HOLDER). QUALIFIER'S NAME
 SHOULD BE SPELLED CORRECTLY (PHILLIP).
  
 3. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT
 SHOWING THAT FEES DUE HAVE BEEN PAID. THIS ITEM MAY BE
 ADDRESSED AFTER ALL PLAN REVIEWS ARE COMPLETE, BUT MUST
 BE ADDRESSED PRIOR TO PERMIT ISSUANCE. AN IMPACT FEE
 REVIEW STOP HAS BEEN ADDED TO 17020803.
  
 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471, FAC61G15-23.002. THE PLANS SUBMITTED
 INCLUDE A DIGITAL SIGNATURE, WHICH CAN ONLY BE UTILIZED
 FOR DIGITAL SUBMITTALS. AS THIS IS A PAPER SUBMITTAL,
 SUBMIT TWO SIGNED, SEALED DATED ORIGINALS.
  
 5. PROVIDE THE GEOTECHNICAL REPORT FOR THIS PROJECT,
 FBC 1803.5.2. THE REPORT SHOULD BE REVIEWED BY DOR
 PRIOR TO SUBMITTAL, FBC 107.
  
 6. PLANS SHOW RELOCATION OF VACUUM. THIS WORK MAY BE
 INCLUDED IN THE RENOVATION PERMIT (17020806). EITHER
 INCORPORATE ALL INFORMATION FOR THIS FOR REVIEW, OR
 THIS PERMIT WILL BE ISSUED WITH PROVISO THAT A SEPARATE
 PERMIT, APPLICATION, FEES, AND PLANS ARE REQUIRED, FBC
 107.
  
 PLANS SHOW INSTALLATION OF A CCTV SYSTEM. THIS PERMIT
 WILL BE ISSUED WITH A PROVISO THAT A SEPARATE PERMIT,
 APPLICATION, FEES, AND PLANS ARE REQUIRED, FBC 107.
  
 PLANS SHOW SITE LIGHTING. THIS PERMIT WILL BE ISSUED
 WITH A PROVISO THAT A SEPARATE PERMIT, APPLICATION,
 FEES, AND PLANS ARE REQUIRED, FBC 107.
  
 PLANS SHOW A DUMPSTER ENCLOSURE. THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT A SEPARATE PERMIT,
 APPLICATION, FEES, AND PLANS ARE REQUIRED, FBC 107.
  
 ITEMS REQUIRING A SEPARATE PERMIT HAVE NOT BEEN
 REVIEWED AT THIS TIME.
  
 7. PROVIDE PLANS FOR THE CONVENIENCE STORE RENOVATION.
 PLANS ARE TO INCLUDE WIND DESIGN CRITERIA, PRODUCT
 APPROVAL FOR THE PROPOSED NEW OPENING AND WINDOW, FBC
 107, FBC 1603.1.4.
  
 WIND DESIGN CRITERIA WAS PROVIDED ON SHEET C0.0 BUT
 LACKS COMPONENT AND CLADDING DESIGN PRESSURE
 INFORMATION.
  
 A DETAIL WAS PROVIDED ON SHEET G1.0 BUT LACKS
 SUFFICIENT INFORMATION FOR REVIEW, CONSTRUCTION, AND
 INSPECTION.
  
 REVISE PLANS TO PROVIDE THE FOLLOWING:
 STEEL LAP SPECIFICATION
 MINIMUM EMBEDMENT OF STEEL TO BEAM ABOVE
 SPECIFICATION OF HOW STEEL IS TO BE EMBEDDED INTO
 EXISTING BEAM
 PLANS SHOW STEEL INTO THE BEAM ABOVE, BUT NO STEEL
 EXTENDING FROM THE NEW COLUMNS AND SILL INTO EXISTING
 IT IS NOT CLEAR WHETHER THE COLUMNS ARE FORMED AND
 POURED OR IF THEY ARE TO BE FILLED CELLS; REVISE TO
 SPECIFY
 CONCRETE (OR GROUT) NOT SPECIFIED
 THE DETAIL IS ON A SHEET LABELED "TANK, DISPENSER, &
 PIPING SITE PLAN." PLANS SHOULD BE CLEAR AS TO SCOPE
 AND NATURE OF PROPOSED IMPROVEMENT, FBC 107.
 LOCATION OF PROPOSED NEW OPENING IS SHOWN GRAPHICALLY
 ON THE PLANS BUT NOT SPECIFIED (DISTANCE FROM CORNER).
  
 8. THE PRODUCT APPROVAL FOR THE WINDOW (AND MULLION, IF
 APPLICABLE) IS TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL, FBC 107.
  
 9. AERIALS SHOW A RECTANGULAR OBJECT IN THE LOCATION OF
 THE PROPOSED NEW WINDOW OPENING. REVISE PLAN TO CLARIFY
 WHAT IS CURRENTLY IN THIS LOCATION (WINDOW? ELECTRIC
 METER?), FBC 107.
  
 10. PROVIDE PLANS STAMPED BY FDEP, FAC62-761.
  
 11. IT IS RECOMMENDED THAT A SEPARATE SUBMITTAL FOR
 EACH PERMIT IS PROVIDED. AS SUBMITTED, NO PORTION OF
 THE WORK CAN BE ISSUED UNTIL ALL ITEMS HAVE BEEN
 ADDRESSED.
  
 12. PROVIDE PLANS FOR THE CANOPY. A PERMIT APPLICATION
 HAS BEEN SUBMITTED, BUT STRUCTURAL PLANS WERE NOT
 PROVIDED. IT IS RECOMMENDED THAT THIS BE A SEPARATE
 SUBMITTAL WHICH SHOULD INCLUDE THE SITE PLAN AND
 STRUCTURAL DETAILS, INCLUDING ELEVATIONS.
  
 13. PROVIDE SPEC SHEETS FOR THE PROPOSED FUEL
 DISPENSERS. FUEL DISPENSERS ARE TO COMPLY WITH FBC A
 228. SPEC SHEETS SHOULD SHOW COMPLIANCE. PROVIDE ENOUGH
 INFORMATION (FOR INSTANCE, CURB HEIGHT) TO SHOW
 COMPLIANCE.
  
 14. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED
 WILL HELP TO EXPEDITE YOUR PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-03-08 Cont ID  
Sent By vperez Date 2017-03-08 Time 08:54 Rev Time 0.00
Received By vperez Date 2017-03-08 Time 08:54 Sent To  
Notes
2017-03-08 08:58:56INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, AND CCTV. A NOTE
 WILL SUFFICE.
 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE
 REQUIREMENTS OF NEC TABLE 300.5 FOR MINIMUM COVER
 REQUIREMENTS FOR CONDUITS. A NOTE WILL SUFFICE
 3. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY
 REGULATORY AGENCIES.
 4. PROVIDE GENERAL ELECTRICAL DEMO NOTES APPLICABLE TO
 SCOPE AS SHOWN. FBC 107.3.5
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By mgonzale Date 2017-06-29 Time   Rev Time 1.00
Received By mgonzale Date 2017-06-29 Time   Sent To I
Notes
2017-06-29 09:17:04PASSED WITH PROVISOS:
  
 1 FOR THE PARKING STALL MAKE A NOTE TO REFER TO CITY
 STANDARD PARKING STALL STRIPING DETAIL IN SHEET C-1.2
 2 FOR THE DUMPSTER ENCLOSURE, EXTEND THE CONCRETE FROM
 14 FEET TO 20 FEET. THIS WILL ADD AN APPROACH TO
 SANITATION PICKUP AREA AS AT THE TIME OF PICKUP THE
 WEIGHT OF THE TRUCK WILL BE EXCESSIVE AND MANEUVERING
 WILL HINDER THE ASPHALT.
 3 INCLUDE CITY OF WEST PALM BEACH STANDARD DETAILS 2016
 GN-1 TO GN-1.2
 PLEASE CHANGE ANY AND ALL NOTATION(S) FROM THE TOWN OF
 CITY OF WEST PALM BEACH TO THE CITY OF WEST PALM BEACH.
 4. SOUTHWEST CORNER OF SITE IS CONCERNING THE EXISTING
 CONCRETE THERE IS AN ELEVATION OF 18.96. HOW IS THE
 WATER BEING DRAINED IN THAT LOCATION? CITY CRITERIA FOR
 DRAINAGE REVIEW ADOPTS THE FLORIDA ADMINISTRATIVE CODE
 FOR STORMWATER RETENTION AS OUTLINED IN CHAPTER 62-65.
 A TRENCH DRAIN OR A FLUME INTO LANDSCAPE BUFFER MAY BE
 REQUIRED. SITE MUST MEET THIS REQUIREMENT.
 5. INCLUDE THE TRAFFIC SIGN SIZE OR FDOT DESIGNATION
 FOR ALL PROPOSED SIGNS.
 UPDATE THE TYPICAL PARKING SPACE DETAIL AND HANDICAP
 PARKING DETAIL TO MATCH CITY OF WEST PALM BEACH
 STANDARD DETAILS.
 6. IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH, CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By shill Date 2017-05-24 Time 14:27 Rev Time 0.00
Received By shill Date 2017-05-24 Time 14:27 Sent To  
Notes
2017-05-24 14:28:09SEE PREVIOUS REVIEW
 SPOKE WITH ENGINEER OF RECORD; HE WILL SUBMIT TO
 ENGINEERING WHEN RESUBMITTING
  
 #1 SUBMIT DIRECTLY TO CITY OF WPB ENGINEERING DEPT.
 (CIVIL DRAINAGE AND CALCULATIONS). WE WILL EXPEDITE OUR
 REVIEW AT ENGINEERING.
  
 #2 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WO
 RKS/FORMS,-PERMITS-APPLICATIONS
 SUBMIT COST ESTIMATE JUST FOR DRAINAGE STRUCTURES,
 PAVING WILL BE WITH THE BUILDING DEPT,
  
 THANK YOU!
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 818-1322
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-05-15 Cont ID  
Sent By mgonzale Date 2017-05-15 Time   Rev Time 1.00
Received By mgonzale Date 2017-05-15 Time   Sent To I
Notes
2017-05-15 10:32:02#1 SUBMIT DIRECTLY TO CITY OF WPB ENGINEERING DEPT.
 (CIVIL DRAINAGE AND CALCULATIONS). WE WILL EXPEDITE OUR
 REVIEW AT ENGINEERING.
  
 #2 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WO
 RKS/FORMS,-PERMITS-APPLICATIONS
 SUBMIT COST ESTIMATE JUST FOR DRAINAGE STRUCTURES,
 PAVING WILL BE WITH THE BUILDING DEPT,
  
 THANK YOU!
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 818-1322
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-17 Cont ID  
Sent By shill Date 2017-06-29 Time 06:52 Rev Time 0.00
Received By shill Date 2017-06-22 Time 13:41 Sent To  
Notes
2017-06-26 13:42:01C36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-24 Cont ID  
Sent By shill Date 2017-05-24 Time 14:28 Rev Time 0.00
Received By shill Date 2017-05-15 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-15 Cont ID  
Sent By skennedy Date 2017-05-15 Time 10:11 Rev Time 0.00
Received By skennedy Date 2017-02-17 Time 08:00 Sent To  
Notes
2017-03-06 07:19:46C18
  
 FOUR APPLICATIONS TRAVELLING TOGETHER (17020797,
 17020806, 17020806, 17030189)
 #17020797 - PAVING
 #17020806 - CONVENIENCE STORE REMODEL (AND RELOCATION
 OF VACUUM?)
 #17020803 - FUEL TANK AND FUEL DISPENSING ISLANDS
 #17030189 - CANOPY OVER FUEL DISPENSERS

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-05-24 Cont ID  
Sent By shill Date 2017-05-24 Time 14:45 Rev Time 0.00
Received By shill Date 2017-05-24 Time 14:45 Sent To  
Notes
2017-05-24 14:45:35MU2017-7732
 RECEIPT RECEIVED VIA EMAIL
 $41,244.20
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-05-23 Cont ID  
Sent By skennedy Date 2017-05-15 Time 12:34 Rev Time 0.00
Received By shill Date 2017-05-15 Time 12:34 Sent To  
Notes
2017-05-23 09:20:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE BUILDING REVIEW
  
 TO RECAP - IMPACT FEES REQUIRED FOR ADDITIONAL FUELING
 POSITIONS (PERMIT 17020803)
 THE PLANS HAVE BEEN STAMPED BY PALM BEACH COUNTY
 (MU2017-7732) BUT THE RECEIPT WAS NOT PROVIDED
 AS ONE SET OF PLANS WERE SUBMITTED FOR ALL FOUR
 PERMITS, NONE OF THE PERMITS CAN BE ISSUED UNTIL ALL
 PERMITS ARE READY FOR ISSUANCE.
  
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By shill Date 2017-03-06 Time 07:59 Rev Time 0.00
Received By shill Date 2017-03-06 Time 07:59 Sent To  
Notes
2017-03-06 08:00:07SEE BUILDING REVIEW
 IMPACT FEES REQUIRED FOR ADDITION OF FUEL DISPENSING
 STATIONS (SEE 17020803)
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2017-05-19 Cont ID  
Sent By ccole Date 2017-05-19 Time 12:23 Rev Time 0.00
Received By ccole Date 2017-05-19 Time 12:23 Sent To  
Notes
2017-05-19 12:25:26MECHANICAL REVIEW IS UNDER PERMIT #17020803
 CCOLE- 5/19/17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-05-15 Cont ID  
Sent By skennedy Date 2017-05-15 Time 12:34 Rev Time 0.00
Received By skennedy Date 2017-05-15 Time 12:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-08 Cont ID  
Sent By ccole Date 2017-03-08 Time 15:21 Rev Time 0.00
Received By ccole Date 2017-03-08 Time 15:21 Sent To  
Notes
2017-03-08 15:48:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020797
 3/8/17
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS)
 FOR THE TANKS, DISPENSERS, AND FUEL PIPINGS. PROVIDE
 SHOP DRAWING APPROVAL STAMPS AND SIGNATURES BY THE EOR
 ON ALL PRODUCT SUBMITTALS.
  
 2) SHEET C-0.0 THE PROJECT HAS BEEN CLASSIFIED AS A
 LEVEL III ALTERATION FBC-14 EXISTING BUILDING HOWEVER
 THE ONLY ALTERATION SHOWN ON THE PLANS IS INSTALLATION
 OF A NEW EXTERIOR WINDOW. PLEASE PROVIDE A COMPLETE
 SCOPE OF WORK OUTLINE FOR THE BUILDING WITH
 CORRESPONDING DRAWINGS, DETAILS AND SPECIFICATIONS..
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-03-16 Time   Rev Time 0.00
Received By llouie Date 2017-03-10 Time 14:32 Sent To ENG
Notes
2017-03-16 12:04:093/16/16: ZONING PASSED WITH THE FOLLOWING NOTE:
  
 1.) SEPARATE PERMIT REQUIRED FOR LANDSCAPE IMPROVEMENTS
 PER ZBA 3332.
  
  
 NOTES:
  
 - REFERENCE ZBA 3332
 - SPOKE TO OFFICER KERSCHNER ON 3/16/17 - POLICE
 APPROVES SITE PLAN - ADDRESSES CPTED.
  
  
  
  
  
  
  
2017-03-13 16:35:48** FAILED ** (3/13/17)
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) FINAL ORDER FOR ZBA 3332 REQUIRES CPTED APPROVAL
 FROM THE POLICE DEPARTMENT FOR THE SITE PLAN/BUILDING
 IMPROVEMENTS.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  
  
  
  
  
  
2017-03-10 14:35:443/10/17 - WAITING ON POLICE RESPONSE FOR CPTED.
 EMAILED/LEFT VOICE MESSAGE FOR OFFICER KERSCHNER.