| Plan Review Stops For Permit 17020767 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-04-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-04-14 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-04-14 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-27 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-03-24 |
Time |
17:45 |
Sent To |
|
|
| Notes |
| 2017-03-27 15:24:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE STRUCTURAL DETAILS FOR THE INTEGRATED LADDER | | | TO THE BASEMENT MECHANICAL ROOM. FBC 107.2.1 & | | | FBC-R301.5 | | | | | | 2) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE VULKEM 350NF-R | | | WATERPROOFING. FBC-R406.2 | | | | | | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL | | | MULLIONS AND EXTERIOR DOOR TYPES. | | | | | | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THE ROOF HATCH TO THE MECHANICAL ROOM THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. FAC 61G20-3.001 | | | | | | 5) SUBMIT TWO SETS OF THE PRODUCT EVALUATIONS FOR THE | | | ICYNENE SPRAY FOAM INSULATION. FBC-R316 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-04-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-04-13 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-04-13 |
Time |
13:53 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-03-07 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-03-07 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2017-03-07 13:59:57 | 17020767 | | | | | | 1) ROOM 100 FOYER | | | A) OUTLETS PER FBC RESIDENTIAL E3901.11 | | | B) SMOKE ALARM AT BOTTOM OF THE STAIRS NFPA 72 | | | 29.5.1.1.#3 | | | | | | 2) ROOM 103 SUN ROOM | | | A) OUTLET SPACING FBC RESIDENTIAL E3901.2 | | | | | | 3) ROOM 106 KITCHEN | | | A) SMOKE/ CO2 ALARM TO CLOSE TO STOVE NFPA 72 29.8.3.4 | | | (4) | | | B) OUTLET SPACING ON COUNTER BY SINK FBC RESIDENTIAL | | | E3901.4.1 | | | | | | 4) ROOM 113 COTTAGE AND MAIN HOUSE | | | A) FRONT OUTLETS MISSING ON BOTH FBC RESIDENTIAL | | | E3901.7 | | | | | | 5) AIR HANDLER ROOM IN BASEMENT | | | A) OUTLET MISSING FOR SERVICING THE UNIT FBC | | | RESIDENTIAL E3901.12 | | | | | | 6) ROOM 203 MASTER BEDROOM | | | A) OUTLETS BY BALCONY DOORS 6' FROM OPENING PER FBC | | | RESIDENTIAL E3901.1.2.4 | | | B) OUTLET ON BALCONY PER FBC RESIDENTIAL E3901.7 | | | | | | 7) ROOM 202 BATHROOM | | | A) PENDANT FIXTURE TO CLOSE TO TUB 410.10 (D) | | | | | | 8) ALL HAYWAYS UPSTAIRS | | | A) SMOKE ALARMS REQUIRED OUTSIDE OF BEDROOMS | | | B) CARBON MONOXIDE ALARMS REQUIRED WITHIN 10' OF ALL | | | BEDROOMS | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | WEST PALM BEACH, FL | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-04-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-04-27 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-04-27 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-03-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-08 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-08 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2017-03-08 10:16:52 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | | | | | | | | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-03-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-03-01 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-03-01 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-04-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-04-27 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-04-24 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2017-04-25 14:38:04 | RESUB ROUTED TO GJOHNSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-04-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-04-14 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-04-12 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2017-04-13 11:42:05 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-27 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-16 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-05-04 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-05-04 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2017-05-04 14:18:23 | MU2017-11827, NO FEES WERE DUE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-24 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-03-24 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2017-03-24 17:46:59 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-04-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-04-27 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-04-27 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-03-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-03-23 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-03-23 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2017-03-23 18:20:10 | PLAN DENIED | | | 1) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR | | | RANGE HOOD. | | | PER SECTION M1301.3 INSTALLATION OF MATERIALS 2014 FBC | | | RESIDENTIAL CODE. | | | 2) REFER TO TO SECTION M1503.4 MAKE UP AIR REQUIRED | | | 2014 FBC RESIDENTIAL CODE | | | 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR 2014 | | | FBC RESIDENTIAL CODE | | | 4) PROVIDE SEER ON EQUIPMENT SCHEDULE ON THE PLAN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-04-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-04-27 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-04-27 |
Time |
14:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-03-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-08 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-08 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2017-03-08 10:14:42 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. WHAT EQUIPMENT WILL BE INSTALLED IN THE UNDERGROUND | | | MECHANICAL ROOM PLEASE PROVIDE SCHEDULE ON PLAN. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEN | | | TO FBC 107.3.5.3(11) | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-05 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-05 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2018-10-05 15:28:44 | METAL ROOF PRODUCT APPROVAL IN THE BUILDING PERMIT | | | SUBMITTAL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-03-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-03-01 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-03-01 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|