Plan Review Details - Permit 17020756
Plan Review Stops For Permit 17020756
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-10 Cont ID  
Sent By vperez Date 2017-03-10 Time 09:21 Rev Time 0.00
Received By vperez Date 2017-03-10 Time 09:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By vperez Date 2017-02-22 Time 10:16 Rev Time 0.00
Received By vperez Date 2017-02-22 Time 10:16 Sent To  
Notes
2017-02-22 10:23:21PLEASE NOTE THAT THE SERVICE CONDUCTORS SHOWN AT 250MCM
 IS UNDERSIZED FOR THE 281AMP LOAD BASED ON OPTIONAL
 MULTIFAMILY DWELLING CALCULATIONS. A 300 CONDUCTOR MUST
 BE INSTALLED PER NEC 310.15B16 TABLE OF AMPACITIES.
  
 SHOW CALCULATIONS BASED ON NEC 220.84 OPTINAL
 CALCULATION TO APPLY DEMAND FACTORS(45%)
  
 CLARIFY IF THERE ARE SMOKES IN THE DWELLING UNITS, IF
 SO PROVIDE A NOTE TO CLARIFY. THEY WILL BE REQUIRED IF
 NOT. FBC RES 314-315
  
 SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE.
 NEC 250.94
  
  
  
 VAL PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-10 Cont ID  
Sent By vperez Date 2017-03-10 Time 09:22 Rev Time 0.00
Received By vperez Date 2017-03-10 Time 09:22 Sent To  
Notes
2017-03-09 16:50:18RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-22 Cont ID  
Sent By vperez Date 2017-02-22 Time 10:23 Rev Time 0.00
Received By vperez Date 2017-02-22 Time 10:23 Sent To  
Notes
2017-02-17 09:20:56ROUTED TO ELECTRICAL INBOX