Plan Review Details - Permit 17020715
Plan Review Stops For Permit 17020715
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-27 Cont ID  
Sent By jwitmer Date 2017-03-27 Time 15:27 Rev Time 0.00
Received By shill Date 2017-03-27 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-30 Cont ID  
Sent By vperez Date 2017-03-30 Time 08:32 Rev Time 0.00
Received By vperez Date 2017-03-30 Time 08:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 08:49 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 08:49 Sent To  
Notes
2017-03-24 08:50:29PLEASE ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL
 APPROVAL. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-13 Cont ID  
Sent By scaldero Date 2017-03-13 Time 13:42 Rev Time 0.00
Received By scaldero Date 2017-03-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-27 Cont ID  
Sent By shill Date 2017-03-27 Time 15:28 Rev Time 0.00
Received By shill Date 2017-03-13 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-10 Cont ID  
Sent By cpuell Date 2017-03-10 Time 16:19 Rev Time 0.00
Received By cpuell Date 2017-02-17 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-20 Cont ID  
Sent By ccole Date 2017-03-20 Time 14:09 Rev Time 0.00
Received By ccole Date 2017-03-20 Time 14:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-08 Cont ID  
Sent By ccole Date 2017-03-08 Time 16:13 Rev Time 0.00
Received By ccole Date 2017-03-08 Time 16:13 Sent To  
Notes
2017-03-08 16:20:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020715
 3/8/17
  
 1) REFER TO SECTION 501.3.1 AND INDICATE THE
 TERMINATION LOCATION OF THE NEW GARAGE EXHAUST OUTLETS.
  
 2) THE AIR KING BFQ110FAN SPECIFIED ON THE PLAN IS A
 BATHROOM FAN THAT IS LIMITED TO EXHAUSTING A MAXIMUM OF
 125 SQ. FT PER MANUFACTURER'S SPECIFICATIONS. PLEASE
 PROVIDE A FAN RATED FOR USE IN A GARAGE WITH ADEQUATE
 CAPACITY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-30 Cont ID  
Sent By vperez Date 2017-03-30 Time 08:32 Rev Time 0.00
Received By vperez Date 2017-03-30 Time 08:32 Sent To  
Notes
2017-03-27 15:27:32A SHEETS OK
  
2017-03-20 15:04:32MECHANICAL DIG/SIGS VERIFIED. CCOLE

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-13 Cont ID  
Sent By llouie Date 2017-03-13 Time   Rev Time 0.00
Received By llouie Date 2017-03-13 Time   Sent To  
Notes
***NONE***