Plan Review Details - Permit 17020696
Plan Review Stops For Permit 17020696
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-05-09 Cont ID  
Sent By shill Date 2017-05-09 Time 14:12 Rev Time 0.00
Received By shill Date 2017-05-09 Time 14:12 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-04-25 Cont ID  
Sent By shill Date 2017-04-25 Time 07:46 Rev Time 0.00
Received By shill Date 2017-04-25 Time 07:41 Sent To  
Notes
2017-04-25 07:49:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 4. FBC 1609, PROVIDE WIND DESIGN CRITERIA FBC 1603.1.4.
  
 5. OK
  
 6. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED
 WILL HELP TO EXPEDITE YOUR PLAN REVIEW.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-23 Cont ID  
Sent By shill Date 2017-03-23 Time 17:41 Rev Time 0.00
Received By shill Date 2017-03-23 Time 17:35 Sent To  
Notes
2017-03-23 17:47:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. THE VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD
 AND PROFIT, EVEN IF PROVIDED BY OTHERS. IF THIS IS A
 LABOR ONLY CONTRACT, PROVIDE THE INVOICES FOR THE
 MATERIALS AS WELL AS THE CONTRACT.
  
 2-3. OK
  
 4. FBC 1609, PROVIDE A STRUCTURAL DETAIL FOR THE
 INSTALLATION, INCLUDING WIND DESIGN CRITERIA FBC
 1603.1.4.
  
 SEE MECHANICAL COMMENTS REGARDING ADDITIONAL
 INFORMATION REQUIRED FOR A COMPLETE STRUCTURAL DETAIL.
  
 I WAS NOT ABLE TO LOCATE WIND SPEED ON THE PLAN; EITHER
 ADD OR ADVISE WHERE THIS CAN BE FOUND.
  
 5. OK
  
 6. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED
 WILL HELP TO EXPEDITE YOUR PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By shill Date 2017-03-06 Time 10:19 Rev Time 0.00
Received By shill Date 2017-03-03 Time 07:34 Sent To  
Notes
2017-03-03 09:11:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. THE VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD
 AND PROFIT, EVEN IF PROVIDED BY OTHERS. IF THIS IS A
 LABOR ONLY CONTRACT, PROVIDE THE INVOICES FOR THE
 MATERIALS AS WELL AS THE CONTRACT.
  
 2. ADVANCED FBC COURSE IS REQUIRED FOR ALL ENGINEERS
 DESIGNING USING THE FLORIDA BUILDING CODE, FS 471.0195
 BY JUNE 30, 2016. EVIDENCE THAT THE COURSE HAS BEEN
 COMPLETED IS TO BE SENT TO FBPE AND THE WEBSITE
 (WWW.MYFLORIDALICENSE.COM) IS TO BE UPDATED.
  
 THIS COMMENT WILL NOT PREVENT THE PERMIT FROM BEING
 ISSUED.
  
 3. FBC 1601, REVISE PLAN TO INCLUDE WEIGHT OF EXISTING
 UNIT, PROPOSED NEW UNIT. IT IS NOT CLEAR WHETHER THE
 LOAD ONTO THE EXISTING STRUCTURE WILL BE THE SAME,
 MORE, OR LESS THAN THE EXISTING.
  
 4. FBC 1609, PROVIDE A STRUCTURAL DETAIL FOR THE
 INSTALLATION, INCLUDING WIND DESIGN CRITERIA FBC
 1603.1.4.
  
 5. AN AREA IS LABELED "EQUIPMENT ROOM". IT IS NOT CLEAR
 WHETHER THIS IS EXISTING OR PROPOSED, AND IS THIS A
 ROOM AND CONSIDERED ANOTHER STORY AND INTEGRAL TO THE
 BUILDING, OR IS THIS IS AN EQUIPMENT SHELTER, PREFAB,
 FBC 1509? NOT ENOUGH INFORMATION PROVIDED TO DETERMINE
 CODE COMPLIANCE.
  
 6. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED
 WILL HELP TO EXPEDITE YOUR PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-21 Cont ID  
Sent By vperez Date 2017-03-21 Time 09:26 Rev Time 0.00
Received By vperez Date 2017-03-21 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By vperez Date 2017-03-06 Time 10:18 Rev Time 0.00
Received By vperez Date 2017-03-06 Time 10:18 Sent To  
Notes
2017-03-06 10:18:40INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP NEW FEEDERS AND BRANCH CIRCUITS.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; MODIFICATIONS SEE VERBIAGE IN CODE.
 3. PROVIDE ACTUAL REVISED CALCULATIONS FOR THE PANEL
 BOARDS SHOWN WITH CHANGES, DP, A, B.
 4. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL
 COMMENTS RELATED TO ELECTRICAL.
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-04-26 Cont ID  
Sent By pleduc Date 2017-04-26 Time   Rev Time 0.00
Received By pleduc Date 2017-04-26 Time 11:44 Sent To  
Notes
2017-04-26 12:12:53PASSED AND RETURNED TO B19, CONTACTED RACHAEL,
 APPLICANT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-20 Cont ID  
Sent By pleduc Date 2017-03-20 Time   Rev Time 0.00
Received By pleduc Date 2017-03-20 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-24 Cont ID  
Sent By pleduc Date 2017-02-24 Time   Rev Time 0.00
Received By pleduc Date 2017-02-23 Time 12:44 Sent To  
Notes
2017-02-23 17:33:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE CONSTRUCTION AND INSPECTION OF THE WATER COOLING
 TOWER SHALL COMPLY WITH NFPA 214, STANDARD ON
 WATER-COOLING TOWERS, 2011 EDITION.
  
 THERE IS INSUFFICIENT DETAIL PROVIDED TO COMPLETE A
 REVIEW.
  
  
 2)
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER?S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
  
  
  
 3)
 4.8 SCREENING.
 4.8.1 OPEN AREAS OR SPACE BETWEEN A COMBUSTIBLE
 COLD-WATER BASIN AND THE GROUND OR ROOF OF A BUILDING
 UPON WHICH IT IS LOCATED SHALL BE EFFECTIVELY SCREENED
 TO PREVENT THE ACCUMULATION OF WASTE COMBUSTIBLE
 MATERIAL UNDER THE TOWER AND TO
 PREVENT THE USE OF SUCH AREAS OR SPACE UNDER THE TOWER
 FOR THE STORAGE OF COMBUSTIBLE MATERIAL.
 4.8.2 FIRE PROTECTION SHALL BE PERMITTED TO BE
 INSTALLED IN LIEU OF SCREENING.
  
  
 4)
 5.2.9 PROTECTION FOR FAN DRIVE MOTOR.
 5.2.9.1 A SPRINKLER OR SPRAY NOZZLE SHALL BE PROVIDED
 OVER EACH FAN DRIVE MOTOR WHERE THE MOTOR IS LOCATED SO
 THAT IT IS NOT WITHIN THE PROTECTED AREA OF THE TOWER.
  
  
 5)
 5.2.10 EXPOSURE PROTECTION.
 5.2.10.1 WHERE ANY COMBUSTIBLE EXTERIOR SURFACES OF A
 TOWER, INCLUDING THE FAN DECK AND DISTRIBUTION BASINS,
 ARE LESS THAN 100 FT (30.5 M) FROM SIGNIFICANT
 CONCENTRATIONS OF COMBUSTIBLES SUCH AS STRUCTURES OR
 PILED MATERIAL, THE COMBUSTIBLE EXPOSED SURFACES OF THE
 TOWER SHALL BE PROTECTED BY AN AUTOMATIC WATER SPRAY
 SYSTEM.
 5.2.10.2 SYSTEMS FOR EXTERIOR PROTECTION SHALL BE
 DESIGNED WITH THE SAME ATTENTION AND CARE AS INTERIOR
 SYSTEMS.
 5.2.10.2.1 PIPE SIZING SHALL BE BASED ON HYDRAULIC
 CALCULATIONS.
 5.2.10.2.2 WATER SUPPLY AND DISCHARGE RATE SHALL BE
 BASED ON A MINIMUM 0.15 GPM/FT2 (6.11 MM/MIN) FOR ALL
 PROTECTED SURFACES
  
  
 6)
 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE
 PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF NFPA 780.
  
  
 7)
 CHAPTER 6 ELECTRICAL EQUIPMENT AND WIRING
 6.1 INSTALLATION. INSTALLATION OF ALL ELECTRICAL
 EQUIPMENT AND WIRING PERTAINING TO WATER-COOLING TOWERS
 SHALL BE IN ACCORDANCE WITH NFPA 70.
 6.2* OVERCURRENT PROTECTION. ELECTRIC MOTORS THAT ARE
 DRIVING FANS SHALL BE PROVIDED WITH OVERCURRENT
 PROTECTION DEVICES AS MANDATED BY NFPA 70.
  
  
 8)
 6.3 STOP FAN. A REMOTE FAN MOTOR SWITCH SHALL BE
 PROVIDED TOSTOP THE FAN IN CASE OF FIRE.
 6.4 INTERLOCK. WHEN A FIRE PROTECTION SYSTEM IS
 INSTALLED, PROVISIONS SHALL BE MADE TO INTERLOCK THE
 FAN MOTORS WITH THE FIRE PROTECTION SYSTEM AS SET FORTH
 IN CHAPTER 5.
 6.5 VIBRATION-CONTROLLED SWITCH. A LISTED, AUTOMATIC,
 VIBRATIONCONTROLLED SWITCH SHALL BE PROVIDED TO
 AUTOMATICALLY SHUT DOWN FAN MOTORS.
  
  
 9)
 8.7 ACCESS.
 8.7.1 ACCESS TO THE TOPS OF WATER-COOLING TOWERS FOR
 FIRE FIGHTING AND MAINTENANCE SHALL BE PROVIDED BY AN
 APPROVED STAIRWAY OR LADDER.
  
 10)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 11)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PLEASE ENSURE COMPLIANCE, MAKE ANY NECESSARY CHANGES
 AND PROVIDE AN APPLICABLE NOTE OF COMPLAINCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-05-09 Cont ID  
Sent By gjohnson Date 2017-05-09 Time 13:37 Rev Time 0.00
Received By gjohnson Date 2017-05-09 Time 13:37 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By gjohnson Date 2017-03-27 Time 14:35 Rev Time 0.00
Received By gjohnson Date 2017-03-27 Time 14:35 Sent To  
Notes
2017-03-27 14:35:521ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SHT. M2A IS SHOWING A 1.5" MOTORIZED GAS VALVE THE
 THE GAS INLET FOR THE BOILER IS 2" PER MANUFACTURE THE
 VALVE S SHOULD BE THE SAME SIZE OR LARGER THAN THE
 INLET. PER WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. THE 12" VENT IS UNDERSIZED SHOULD BE 14" FOR 20'
 VENT. PER FBC FUEL GAS TABLE 504.2(1)
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2017-05-02 Time 07:48 Sent To  
Notes
2017-05-09 14:13:335/9 ON SH DESK PENDING RESPONSE FROM LL
  
  
2017-05-09 07:48:575/9 TO CC DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-09 Cont ID  
Sent By shill Date 2017-04-26 Time 14:19 Rev Time 0.00
Received By shill Date 2017-04-13 Time 17:42 Sent To  
Notes
2017-04-14 17:42:25B19
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-09 Cont ID  
Sent By shill Date 2017-03-27 Time 14:19 Rev Time 0.00
Received By shill Date 2017-03-16 Time 09:55 Sent To  
Notes
2017-03-17 09:55:52B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By vperez Date 2017-03-06 Time 10:19 Rev Time 0.00
Received By vperez Date 2017-03-06 Time 10:19 Sent To  
Notes
2017-02-16 13:41:48B05

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-05-09 Cont ID  
Sent By ccole Date 2017-05-09 Time 11:08 Rev Time 0.00
Received By ccole Date 2017-05-09 Time 10:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-04-19 Cont ID  
Sent By ccole Date 2017-04-19 Time 13:42 Rev Time 0.00
Received By ccole Date 2017-04-19 Time 11:52 Sent To  
Notes
2017-04-19 14:00:412ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020696
 4/19/17
  
 1) THE REVISED PLANS ARE STILL INDICATING THE EXISTING
 14" BOILER FLUE VENT IS STILL UNDERSIZED. PLEASE REFER
 TO TABLE 504.2 (1) FBC-14 FUEL GAS WHICH INDICATES A
 14" FLUE AT 15' HEIGHT AND 5' LATERAL CAN ADEQUATELY
 VENT UP TO 1,327 MBH BASED ON APPLIANCE INPUT RATING.
 THIS NUMBER WILL DECREASE USING A 12' FLUE LENGTH AND
 ALSO USING A 12" CONNECTOR AS INDICATED ON THE PLANS-
 SEE SECTION 504.2.8 :
  
 504.2.8 VENT AREA AND DIAMETER.
 WHERE THE VERTICAL VENT HAS A LARGER DIAMETER THAN THE
 VENT CONNECTOR, THE VERTICAL VENT DIAMETER SHALL BE
 USED TO DETERMINE THE MINIMUM VENT CAPACITY, AND THE
 CONNECTOR DIAMETER SHALL BE USED TO DETERMINE THE
 MAXIMUM VENT CAPACITY. THE FLOW AREA OF THE VERTICAL
 VENT SHALL NOT EXCEED SEVEN TIMES THE FLOW AREA OF THE
 LISTED APPLIANCE CATEGORIZED VENT AREA, FLUE COLLAR
 AREA OR DRAFT HOOD OUTLET AREA UNLESS DESIGNED IN
 ACCORDANCE WITH APPROVED ENGINEERING METHODS.
  
 2) COMMENTS #5 & 6 FROM THE PREVIOUS REVIEW STILL
 EXIST. PLEASE REVISE SHEET M-5 TO SHOW THE DETAILS AND
 DIMENSIONS THAT ARE INDICATED IN THE NARRATIVE REPONSE.
 PLEASE NOTE THAT THE 8-1/2 X 11" SUBMITTAL DOES NOT
 PROVIDE: A) ATTACHMENT DETAILS FOR THE COOLING TOWER TO
 THE STRUCTURE. B) THE CLEARANCE DISTANCE HEIGHT FROM
 THE ROOF SURFACE. C) DOES NOT BEAR THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL WHO DREW THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-21 Cont ID  
Sent By ccole Date 2017-03-21 Time 12:45 Rev Time 0.00
Received By ccole Date 2017-03-21 Time 12:39 Sent To  
Notes
2017-03-21 13:59:052ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020696
 3/21/17
  
 1) SHEET M-1: SHOW THE LOCATION OF EF-11.
  
 2) M-1: INDICATE HOW THE CURB ADAPTERS WILL BE ATTACHED
 TO THE CURBS, AND INDICATE THE LENGTH OF THE #10
 FASTENERS USED TO MOUNT THE FANS.
  
 3) M-2A: INDICATE HOW COMBUSTION AIR IS BEING PROVIDED
 FOR THE BOILER AND PROVIDE A CALCULATION- SEE SECTION
 304 FBC-14 FUEL GAS.
  
 4) M-2A & M5: REFER TO TABLE 504.2.(1): THE 12" BOILER
 FLUE IS UNDERSIZED FOR THE TOTAL 1435 MBTU INPUT.
 PLEASE INDICATE THE TOTAL LENGTH OF THE FLUE FROM THE
 BOILER VENT OUTLET TO THE TERMINATION CAP. A 12"
 DOUBLE-WALL FLUE AT 20' RUN LENGTH WITH A 0" LATERAL
 CAN ADEQUATELY VENT GAS-FIRED EQUIPMENT UP TO1350 MBTU
 INPUT CAPACITY.
  
 5) M-5: AS PREVIOUSLY REQUESTED PROVIDE STRUCTURAL
 DETAILS FOR ANCHORING THE COOLING TOWER TO THE EXISTING
 SUPPORT BASE,
  
 6) M-5: REFER TO TABLE 1509.6.5 FBC-14 BUILDING AND
 INDICATE CLEARANCE HEIGHT BELOW THE COOLING TOWER
 SUPOPORT BASE TO THE FINISHED ROOF SURFACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By ccole Date 2017-02-21 Time 09:05 Rev Time 0.00
Received By ccole Date 2017-02-21 Time 08:32 Sent To  
Notes
2017-02-21 10:12:201ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020696
 2/21/17
  
 1) PLEASE ADD THE REPLACEMENT OF THE 14 EXHAUST FANS TO
 THE WORK DESCRIPTION ON THE APPLICATION, AND ADJUST THE
 VALUE ACCORDINGLY- SECTION 109.3 WPB AMENDMENTS TO THE
 FBC.
  
 2) I AM CHALLENGING THE $250,000 JOB VALUE FOR THE
 PROPOSED PROJECT BASED ON COST VALUATION TABLES
 PUBLISHED BY MARSHALL & SWIFT VALUATION SERVICE. AS
 LISTED IN THE TABLES THE THE REPLACEMENT OF THE HEAT
 PUMPS AND DUCTWORK ALONE WOULD AMOUNT TO APPROXIMATELY
 $250,000- SEE SECTION 53 PAGE 4. PLEASE PROVIDE AN
 ITEMIZED COST BREAKDOWN THAT INCLUDES THE COOLING
 TOWER, THE PUMPS, THE BOILER, THE DUCTWORK, THE PIPING
 AND CONTROLS, THE EXHAUST FANS, AND THE COOLING TOWER
 SUPPORT STRUCTURE, STAIRS AND CATWALK.
  
 3) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF ALL THE ROOFTOP FANS AND THE COOLING
 TOWER, AND ENGINEERED DRAWINGS AND DETAILS FOR
 INSTALLATION OF THE COOLING TOWER AND SUPPORT
 STRUCTURE- SECTION 301.15.
  
 4) PROVIDE A LIST OF CODES AND STANDARDS USED IN THE
 DESIGN OF THE PROJECT.
  
 5) NEW BOILER: A) PROVIDE A COMPLETE EQUIPMENT SCHEDULE
 FOR THE BOILER INCLUDING BTUH CAPACITY. B) PROVIDE AN
 ENLARGED DRAWING SHOWING THE REQUIRED WORKING
 CLEARANCES AND LENGTH OF THE NEW 10'' FLUE. C) PROVIDE
 THE TOTAL RUN LENGTH OF THE FLUE AND EXISTING VENT FROM
 THE BOILER OUTLET TO THE TERMINATION ON THE ROOF. D)
 SHOW THE VENT TERMINATION ON SHEET M-1.
  
 6) COMMISSIONING FOR THE REPLACED COOLING TOWER AND
 HEAT PUMPS IS REQUIRED PER SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. PLEASE SUBMIT A COMMISSIONING PLAN AS
 OUTLINED IN SECTION C408.2.1.
  
 7) PROVIDE A MECHANICAL DEMOLITION PLANS FOR THE
 EQUIPMENT ROOM.
  
 8) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA HVAC CONSTRUCTION STANDARDS 2005.
  
 9) SUBMIT TWO COPIES OF A FL. PRODUCT APPROVAL AND/OR
 MIAMI-DADE NOA FOR THE GREENHECK LOUVERS.
  
 10) PLEASE CLARIFY IF THE THE REPLACED HEAT PUMPS (O/A
 UNITS) ARE PART OF THE SMOKE CONTROL SYSTEM AND ARE
 BEING USED FOR PRESSURIZATION OF CORRIDORS IN THE EVENT
 OF FIRE. PLEASE NOTE IF THEY ARE SERVING THAT FUNCTION,
 THEN SPECIAL INSPECTION OF THE SYSTEMS IS REQUIRED AS
 NOTED IN SECTION 909.3 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-05-09 Cont ID  
Sent By gjohnson Date 2017-05-09 Time 13:36 Rev Time 0.00
Received By gjohnson Date 2017-05-09 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-04-24 Cont ID  
Sent By gjohnson Date 2017-04-24 Time 09:39 Rev Time 0.00
Received By gjohnson Date 2017-04-21 Time 12:16 Sent To  
Notes
2017-04-24 09:50:311ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IN BOTH PLAN SETS THERE ARE TWO M-2A AND M-5 SHTS
 ONE SHOULD BE MARKED AS VOID OR THE BEST PRACTICE IS TO
 REMOVE THE OLD SHEET.
  
 2. PROVIDE ON THE PLAN THE BTU LOAD OF EXISTING BOILER.
 PER WPB AMEND TO FBC 107.2.1
  
 3. SHOW SIZE OF EXISTING GAS LINE. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. M-5 SHOWS RECONNECTION OF EXISTING POTABLE
 WATER SUPPLY TO TOWER SHOW TYPE OF BACK FLOW IF IT IS A
 DEVISE AND NOT AN AIR GAP IT SHALL BE CERTIFIED . FBC
 PL 608.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-03-27 Cont ID  
Sent By gjohnson Date 2017-03-27 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2017-03-27 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By gjohnson Date 2017-03-02 Time 06:43 Rev Time 0.00
Received By gjohnson Date 2017-03-02 Time 06:24 Sent To  
Notes
2017-03-02 06:59:441ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. M-2 IS THE HEATING BOILER NEW OR EXISTING. PER
 WPB AMEND TO FBC 107.2.1
  
 2. IF THE BOILER IS BEING REPLACEMENT IS IT SAME FOR
 SAME , IS THE BTU LOAD ON THE GAS THE SAME. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PLEASE PROVIDE DETAIL FOR POTABLE WATER CONNECTION.
 PER WPB AMEND TO FBC 107.2.1
  
 4. THE EXISTING BACKFLOW FOR THE POTABLE WATER
 CONNECTION SHALL BE RECERTIFIED BY A LICENSE CERTIFIED
 BACKFLOW PREVENTION TESTER. PER CITY OF WPB CROSS
 CONNECTION CONTROL MANUAL. PROVIDE NOTE ON PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 A NARRATIVE LISTING THE ORIGINAL REVIEW COMMENT NUMBER
 WITH A DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING
 THE SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE
 FOUND WILL HELP EXPEDITE THE REVIEW.
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY.

Review Stop Z ZONING
Rev No 3 Status P Date 2017-05-09 Cont ID  
Sent By llouie Date 2017-05-09 Time   Rev Time 0.00
Received By llouie Date 2017-05-09 Time   Sent To  
Notes
2017-05-09 15:37:27* HEIGHT OF THE BUILDING WITH NEW COOLING TOWER IS 126
 FT.

Review Stop Z ZONING
Rev No 2 Status F Date 2017-04-20 Cont ID  
Sent By llouie Date 2017-04-20 Time   Rev Time 0.00
Received By llouie Date 2017-04-19 Time   Sent To  
Notes
2017-04-20 12:08:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE HEIGHT OF THE COOLING TOWER SEEMS TO BE 17 FT.
 (AT ITS HIGHEST POINT). PLEASE VERIFY THE HEIGHT BY
 PROVIDING DIMENSIONS TO THE TALLEST POINT OF THE
 COOLING TOWER.
  
 2.) WHAT IS THE HEIGHT OF THE OTHER EXISTING EQUIPMENT
 TO BE REPLACED?
  
 3.) PROVIDE ARCHITECTURAL ELEVATIONS SHOWING THE
 DIMENSIONED HEIGHT OF THE RESIDENTIAL BUILDING.
 ILLUSTRATIONS SHOWING THE EXISTING BUILDING AND
 BUILDING WITH THE PROPOSED NEW ROOFTOP EQUIPMENT SHALL
 BE PROVIDED TO DETERMINE ANY HEIGHT DIFFERENCES, AND
 CONFORMANCE WITH THE HEIGHT REQUIREMENT OF THE CURRIE
 MIXED USE DISTRICT (CMUD) TRANSITIONAL SUB-DISTRICT.
  
 NOTES:
  
 * PROPERTY IS ZONED CMUD (TRANSITION SUB-DISTRICT):
 HEIGHT LIMITATION IS TEN (10) STORIES/135 FT.
  
 * ROOFTOP EQUIPMENT SHALL BE REPLACED AT THE SAME
 HEIGHT AS THE EXISTING EQUIPMENT OR COMPLY WITH THE
 HEIGHT REGULATIONS OF THE CMUD TRANSITIONAL
 SUB-DISTRICT.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-27 Cont ID  
Sent By njwira Date 2017-02-27 Time 17:05 Rev Time 0.00
Received By njwira Date 2017-02-27 Time 17:05 Sent To  
Notes
***NONE***