Plan Review Details - Permit 17020633
Plan Review Stops For Permit 17020633
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2017-06-19 Time 11:23 Sent To  
Notes
2017-06-19 13:42:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020633
 ADD: 8993 OKEECHOBEE BLVD. SUITE # 110
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: 561-358-4140
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JUNE 19/ 2017
 ACTION: DENIED
  
 1) 2ND REQUEST. THE DESIGNER OF RECORD HAS CHANGED THE
 OCCUPANCY CLASSIFICATION TO BUSINESS INDICATING THE
 TENANT SPACE WOULD BE USED FOR TRAINING AND SKILL
 DEVELOPMENT NOT WITHIN A SCHOOL OR ACADEMIC PROGRAM.
 FOR THE BUILDING OFFICIAL TO ACCEPT THIS USAGE THE
 DESIGNER OF RECORD WILL NEED TO PROVIDE A FURNITURE
 PLAN OF HOW MANY STUDENTS WILL ATTEND CLASSES AT ANY
 GIVEN TIME AND 2ND A RATIO BETWEEN INSTRUCTORS/ TUTORS
 AND THEIR STUDENTS. TO VERIFY IF THE PROPOSED SETTING
 WILL NOT BE AS CLASSROOM TRAINING GIVEN TO LARGER
 GROUPS IN A TRADITIONAL EDUCATIONAL PROGRAM OR IF THIS
 IS MORE ON THE LINES OF TUTORS WORKING WITH ONE
 INDIVIDUAL. THE PLANS WILL NEED TO REFLECT THIS. 2014
 FBC-B 304.1 & 2012 IBC-B COMMENTARY, TRAINING AND SKILL
 DEVELOPMENT NOT WITHIN A SCHOOL OR ACADEMIC PROGRAM
  
 1ST ROUND OF COMMENTS. SHEET 1 INDICATES THE ALTERATION
 LEVEL AS A LEVEL II. THE OCCUPANCY TYPE IS LISTED AS
 EDUCATIONAL, THIS IS A CHANGE IN USE AND A CHANGE IN
 OCCUPANCY. PLEASE REVIEW THE REQUIREMENTS FOR A CHANGE
 OF OCCUPANCY IN THE 2014 FBC-EXISTING BUILDING CODE
 SECTION 1001.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 2A) 2ND REQUEST. PLEASE PROVIDE THE AGE GROUP OF THOSE
 WHO WILL BE GETTING INSTRUCTIONS. 2014 FBC-B 305.1
 EDUCATIONAL GROUP E VERSES GROUP B/ BUSINESS.
  
 1ST ROUND OF COMMENTS. SHEET 1 INDICATES THIS IS AN
 EDUCATIONAL OCCUPANCY PLEASE PROVIDE THE AGE GROUP OF
 THE STUDENTS. FBC-B SECTION 305.1 EDUCATIONAL.
  
 2B) SHEET 1 THE OCCUPANT LOAD IS RED LINED, NOONE CAN
 WRITE ON THE ENGINEERED PLANS PLEASE UPDATE PLANS TO
 THE CORRECT OCCUPANT LOAD.
 2014 FBC-B TABLE 1004. 1.2.
  
 THE REST OF THE REVIEW CANNOT OCCUR UNTIL THE ANSWERS
 TO COMMENTS 1 & 2 OCCUR.
  
  
  
 3) SHEET 1 INDICATES THE SQUARE FOOTAGE OF THE TENANT
 SPACE AS 1400 SQ. FT. AND THE NET AS 815 SQ. FT. THE
 INTERIOR TENANT AREA OF LEASABLE SPACE IS 19.5 X 68.5
 SQ. FT.= 1336 SQ. FT. THE NET SQUARE FEET REMOVAL OF
 THE RESTROOM AND WALLS IS APPROXIMATELY 1250 SQ. FT. /
 20 SQ. FT. PER OCCUPANT = 63 OCCUPANTS. THE FBC-B TABLE
 1004.1.2 FOR EDUCATIONAL IS 20 SQ. FT. / OCCUPANT/ NET,
 PLEASE PROVIDE HOW YOUR NET SQ. FOOTAGE OF 815 SQ. FT.
 WAS DERIVED?
  
 4) SHEET 1 INDICATES THE TENANT SEPARATION WALLS ARE TO
 BE ONE HOUR FIRE RATED WALLS. THESE SAME WALLS ARE
 OCCUPANCY SEPARATION WALLS WITH THE PLANS INDICATING
 BUSINESS OCCUPANCIES ON BOTH SIDES. FOR AN
 NON-SPRINKLERED BUILDING WITH EITHER BUSINESS OF
 MERCANTILE OCCUPANCIES THE EDUCATIONAL OCCUPANCY
 REQUIRES A 2 HOUR FIRE RATING. FBC-B TABLE 508.4.
  
 5) 2014 FBC-B SECTION 468 SCHOOLS:
 5A) 468.3.5.1 STANDARDS. EDUCATIONAL AND ANCILLARY
 FACILITIES SHALL BE PROVIDED WITH TOILETS, HANDWASHING
 FACILITIES, AND DRINKING FOUNTAINS FOR ALL OCCUPANTS,
 IN RATIOS AND ACCESSIBLE AS REQUIRED BY THE FLORIDA
 BUILDING CODE, FLORIDA LAW, AND FEDERAL REQUIREMENTS.
  
 5B) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF
 TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 5C) 468.3.5.4 SHIELDING DEVICE. THE ENTRY TO EACH GROUP
 TOILET ROOM SHALL BE PROVIDED WITH A DOOR, PARTITION,
 OR OTHER SHIELDING DEVICE TO BLOCK FROM VIEW THE
 OCCUPANTS IN THE TOILET ROOM. IF A DOOR IS PROVIDED, IT
 SHALL HAVE A CLOSER AND SHALL SWING OUT IN THE
 DIRECTION OF EGRESS.
  
 5D) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE
 IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM)
 ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN
 WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A
 HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR.
 TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS.
  
 5E) 468.3.7.1 ILLUMINATION LEVEL IN
 CLASSROOMS/INSTRUCTIONAL SPACES. ILLUMINATION AT THE
 NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION
 SPACE SHALL BE A MINIMUM OF 40 FOOTCANDLES (400 LUX).
  
 5F) 468.3.7.4 ILLUMINATION FAILURE OF GENERAL AND MEANS
 OF EGRESS LUMINARIES.
 ILLUMINATION SYSTEMS SHALL BE DESIGNED AND MAINTAINED
 SO THAT THE FAILURE OF ANY SINGLE LIGHTING UNIT, SUCH
 AS AN ELECTRIC LUMINARY, DOES NOT LEAVE ANY OCCUPIED
 SPACE OR MEANS OF EGRESS IN THE DARK. (SEE SECTION1006
 FOR ADDITIONAL MEANS OF EGRESS REQUIREMENTS.)
  
 6) 2014 EXISTING BUILDING CODE SECTION 1012.1.4
 ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 1012.8. 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT
 UNDERGO A CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION
 SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY. PLEASE SHOW COMPLIANCE
 WITH: 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 7) THE HALLWAY BY THE STORAGE ROOM IS NOT DIMENSIONED
 BUT SCALES 54 INCHES, THE DOOR TO THE STORAGE ROOM IS
 AN OUTSWING DOOR, (3-0 FOOT) ONLY LEAVING 18 INCHES
 CLEAR. WITH AN OCCUPANT LOAD 50 OR GREATER THE MINIMUM
 REQUIRED CORRIDOR WIDTH IS 44 INCHES (FBC-B TABLE
 1018.2) ? OF THAT WIDTH WOULD BE 22 INCHES. PLEASE SEE
 SECTION 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL
 NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES
 (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By jwitmer Date 2017-02-23 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2017-02-22 Time 17:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-15 Cont ID  
Sent By jleahy Date 2017-06-15 Time 17:40 Rev Time 0.00
Received By jleahy Date 2017-06-15 Time 17:40 Sent To  
Notes
2017-06-15 17:40:57SEE COMMENTS FROM 3/5/17 REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By jleahy Date 2017-03-06 Time 14:28 Rev Time 0.00
Received By jleahy Date 2017-03-06 Time 14:28 Sent To  
Notes
2017-03-06 14:33:33THE FOLLOWING ITEMS NEED TO BE CORRECTED:
  
 FBC EC 2014
 C 405.2.2.2 OCCUPANCY SENSORS REQUIRED
 C 405.5.2 INTERIOR POWER ALLOWANCES PER TABLE 405.5.2
 (1)
  
 NEC 2011
 110.24(A)(B) AVAILABLE FAULT CURRENT FOR SERVICE
 REQUIRED
 215.5 DIAGRAM OF SERVICE TO BAY/UNIT.
 408.4 PANEL SCHEDULE.
  
 JAKE LEAHY
 CITY OF WEST PALM BEACH
 ELECTRICAL PLANS EXAMINER

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-15 Cont ID  
Sent By wjolin Date 2017-06-15 Time 16:47 Rev Time 0.00
Received By wjolin Date 2017-06-15 Time 16:24 Sent To  
Notes
2017-06-15 16:47:448993 OKEECHOBEE BOULEVARD #110
 PERMIT #17020633
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE OCCUPANT LOAD FACTOR FOR A BUSINESS OCCUPANCY IS
 100 SQ.FT. PER PERSON, NOT 20 SQ.FT. PER PERSON; THIS
 WILL REDUCE THE CALCULATED OCCUPANT LOAD FROM 63
 PERSONS TO 13 PERSONS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By wjolin Date 2017-02-21 Time 11:13 Rev Time 0.00
Received By wjolin Date 2017-02-21 Time 10:54 Sent To  
Notes
2017-02-21 11:12:038993 OKEECHOBEE BOULEVARD #110
 PERMIT #17020633
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A PERMIT FOR A CHANGE OF OCCUPANCY IS NEEDED IN LIEU OF
 A COMMERCIAL INTERIOR PERMIT.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXITS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 NFPA 101 TABLE 6.1.14.4.1(B) REQUIRES THE EDUCATIONAL
 OCCUPANCY TO BE SEPARATED FROM THE ADJACENT BUSINESS
 OCCUPANCIES WITH A 2-HOUR FIRE BARRIER.
  
 WHAT FIRE PROTECTION FEATURES (FIRE ALARM, FIRE
 SPRINKLER, ETC.) ARE PROTECTING THE EDUCATIONAL
 OCCUPANCY?
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 13:42 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 10:19 Sent To  
Notes
2017-06-09 10:19:39B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By jleahy Date 2017-03-06 Time 14:40 Rev Time 0.00
Received By jleahy Date 2017-02-14 Time 15:37 Sent To  
Notes
2017-02-16 15:37:20B03

Review Stop Z ZONING
Rev No 1 Status N Date 2017-05-02 Cont ID  
Sent By shill Date 2017-05-02 Time 15:20 Rev Time 0.00
Received By shill Date 2017-05-02 Time 15:20 Sent To  
Notes
2017-05-02 15:20:54NOT REQUIRED PER AV
  