Plan Review Details - Permit 17020623
Plan Review Stops For Permit 17020623
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-27 Cont ID  
Sent By jwitmer Date 2017-06-27 Time 06:42 Rev Time 0.00
Received By jwitmer Date 2017-06-27 Time 06:01 Sent To  
Notes
2017-06-27 06:30:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020623 CHANGE OF OCCUPANCY!!!
 ADD: 218 CLEMATIS ST.
 CONT: MCL CONSTRUCTION INC.
 TEL: 561-368-2434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JUNE 27/ 2017
 ACTION: BUILDING PROVISO
  
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 CODE105.3.1.2(2) FIRE SPRINKLER DOCUMENTS FOR ANY NEW
 BUILDING OR ADDITION WHICH INCLUDES A FIRE SPRINKLER
 SYSTEM WHICH CONTAINS 50 OR MORE SPRINKLER HEADS. A
 CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED
 UNDER SECTION 633.521, FLORIDA STATUTES, MAY DESIGN A
 FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, NOT
 WITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. 61-41,003 ADMINISTRATION AND
 DEPARTMENT RESPONSIBILITIES. (4) TESTING & EVALUATION
 OF PRODUCTS. FL. S. 553.842 PRODUCT EVALUATION AND
 APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 ROOF TOP VENTILATORS & FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 3) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-01 Cont ID  
Sent By jwitmer Date 2017-06-01 Time 16:34 Rev Time 0.00
Received By jwitmer Date 2017-06-01 Time 11:29 Sent To  
Notes
2017-06-01 16:34:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020623 CHANGE OF OCCUPANCY!!!
 ADD: 218 CLEMATIS ST.
 CONT: MCL CONSTRUCTION INC.
 TEL: 561-368-2434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 01/ 2017
 ACTION: DENIED
  
 1A-B) COMPLIED.
  
 1C) NEW COMMENT WHICH DEALS WITH THE AREA INCREASE
 TAKEN FOR FIRE SPRINKLERS, NO PLANS WERE SUBMITTED FOR
 FIRE SPRINKLERS. W. P. B. ADMINISTRATIVE
 CODE105.3.1.2(2) FIRE SPRINKLER DOCUMENTS FOR ANY NEW
 BUILDING OR ADDITION WHICH INCLUDES A FIRE SPRINKLER
 SYSTEM WHICH CONTAINS 50 OR MORE SPRINKLER HEADS. A
 CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED
 UNDER SECTION 633.521, FLORIDA STATUTES, MAY DESIGN A
 FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, NOT
 WITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 2) 2ND REQUEST. PLEASE NOTE THE ENERGY FORMS STATE
 RIGHT BY THE SIGNATURE, THIS SIGNATURE IS AN ELECTRONIC
 SIGNATURE. THE SUBMITTED ENERGY CALS. AND HVAC CALS.
 ARE PRINTED BUT HAVE A DIGITAL SIGNATURE, BY JOHN
 LANGFORD P. E. PLEASE SHOW COMPLIANCE WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEES SIGNATURE SHALL NOT BE USED ON ELECTRONICALLY
 SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET A0.3 SHOWS 127 INTERIOR SEATS, 26 EXTERIOR
 SEATS AND WHAT MAY APPEAR TO BE 30 FEET OF STANDING AT
 THE BAR, UNDETERMINABLE AMOUNT OF FOOTAGE AND USE?
  
 3A-C) COMPLIED
  
 3D) PLEASE NOTE THE FIRE PLAN REVIEWERS NOTES ON THE
 FIRE PIT. THE PLANS SHOW IN THE CENTER OF THE PLAN A
 INDOOR FIRE PIT, PLEASE PROVIDE THE TYPE OF FUEL,
 AMOUNT OF FUEL AND THE AMOUNT OF BTU?S WILL BE USED PER
 HOUR. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 4-6) COMPLIED.
  
 7A) SEMI-COMPLIED. IT IS TRUE THE FRONT ENTRY DOOR DOES
 NOT REQUIRE PANIC HARDWARE BUT THE HARDWARE DOES NEED
 TO COMPLY WITH : 2014 FBC-B SECTION 1008.1.9.3(2)
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
  
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
  
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
  
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 7B) THE REAR EXIT DOOR NOT LABELED ON SHEET A0.5 AND
 NOT INCLUDED IN THE DOOR SCHEDULE SHEET A7.1 DOES
 INDICATE A DOOR 108 TO BE VERIFIED PANIC HARDWARE IS
 REQUIRED. PLEASE IDENTIFY THE DOOR ON SHEET A0.5.
  
 8) COMPLIED.
  
 8A) NEW COMMENT DEALS WITH A0.5 THE AWNING OVER THE
 PUBLIC SIDEWALK AND HOW CLOSE THE CURB IS TO THE
 AWNING. THE CURB IS NOT SHOWN IN THE DEPICTED PLAN.
 COMPLIANCE WITH 2014 FBC-B SECTION 3202.3.1 CANNOT BE
 DETERMINED.
 3202.3.1 AWNINGS, CANOPIES, MARQUEES AND SIGNS.
 AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE
 CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS
 SPECIFIED IN CHAPTER 16. AWNINGS, CANOPIES, MARQUEES
 AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE
 ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE
 THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM
 THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT
 AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED
 NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE.
  
  
 9) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. 61-41,003
 ADMINISTRATION AND DEPARTMENT RESPONSIBILITIES. (4)
 TESTING & EVALUATION OF PRODUCTS. FL. S. 553.842
 PRODUCT EVALUATION AND APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 ROOF TOP VENTILATORS & FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 11) SEMI-COMPLIED. THE ROOF TOP EXHAUST FAN DOES HAVE A
 DETAIL FOR ANCHORING OF THE FAN TO THE CURB AND CURB TO
 THE ROOF FRAMING. THE MECHANICAL REVIEWER REQUEST
 DETAILS AS WELL FOR THE NEW ROOF TOP CONDENSERS TO THE
 EXISTING STANDS.
 ROOF TOP A/C STANDS WILL NEED TO SUPPLY THE FOLLOWING
 INFORMATION, CALCULATE THE AREA OF THE ROOF TOP
 COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND
 COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN
 THE TABLES , ANCHORS AND UPLIFT VERSES MOMENT. 2014
 FBC-B 1604.4 ANALYSIS.
  
 12) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By jwitmer Date 2017-03-17 Time 13:47 Rev Time 0.00
Received By jwitmer Date 2017-03-14 Time 08:07 Sent To  
Notes
2017-03-17 13:47:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020623 CHANGE OF OCCUPANCY!!!
 ADD: 218 CLEMATIS ST.
 CONT: MCL CONSTRUCTION INC.
 TEL: 561-368-2434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 17/ 2017
 ACTION: DENIED
  
 1A) THE COVERSHEET LIST THE FLOOR RATING AS A1.0 HOUR
 FIRE RATING PER TABLE 601 OF THE 2014 FBC-B. THE
 COVERSHEET DOES NOT LIST ANY CRITERIA FOR HORIZONTAL
 ASSEMBLIES OR OCCUPANCY SEPARATION FOR HORIZONTAL
 ASSEMBLIES SEPARATING THE A2 ASSEMBLY USE AND THE
 BUSINESS OCCUPANCY ON THE 2ND FLOOR. PLEASE REVIEW
 TABLE 707.310 OF THE FBC-B THE REQUIREMENT FOR 2 HOUR
 FIRE SEPARATION BETWEEN THE HORIZONTAL ASSEMBLIES
 BETWEEN FIRE AREAS. THIS IS A MIXED USE BUILDING PLEASE
 PROVIDE THE TOTAL SQ. FT. FOR EACH OCCUPANCY PER FLOOR
 AND 508.4.2 ALLOWABLE BUILDING AREA. IN EACH STORY, THE
 BUILDING AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS
 OF THE ACTUAL BUILDING AREA OF EACH SEPARATED OCCUPANCY
 DIVIDED BY THE ALLOWABLE BUILDING AREA OF EACH
 SEPARATED OCCUPANCY SHALL NOT EXCEED 1.
  
 1B) IN THE EXISTING BUILDING CODE SECTION 1012.5.1 FIRE
 WALL ALTERNATIVE FOR HORIZONTAL ASSEMBLIES THERE ARE
 (3) REQUIREMENTS IF ALL (3) REQUIREMENTS ARE MET THAN
 THE HORIZONTAL ASSEMBLIES CAN BE REDUCED TO (1) HOUR.
 PLEASE NOTE THIS TENANT SPACE IS ONLY (1) TENANT SPACE
 OF THE BUILDING ADDRESSED 230 CLEMATIS WITH 18,317
 SQUARE FEET ON THE 1ST FLOOR AND 14,344 ON THE SECOND
 FLOOR.
  
 2) THE SUBMITTED ENERGY CALS. AND HVAC CALS. ARE
 PRINTED BUT HAVE A DIGITAL SIGNATURE, BY JOHN LANGFORD
 P. E. PLEASE SHOW COMPLIANCE WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET A0.3 SHOWS 127 INTERIOR SEATS, 26 EXTERIOR
 SEATS AND WHAT MAY APPEAR TO BE 30 FEET OF STANDING AT
 THE BAR, UNDETERMINABLE AMOUNT OF FOOTAGE AND USE?
  
 3A) PLANS SHOW 8 ACCESSIBLE SEATING AREAS. THE UNKNOWN
 IS THE USAGE OF THE 30 FEET OF BAR APPEARS TO BE
 STANDING ROOM? COMPLIANCE WITH FBC-ACCESS. CODE 226.1.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
  
 3B) SEMI-COMPLIED. THE UNKNOWN IS THE USAGE OF THE 30
 FEET OF BAR APPEARS TO BE STANDING ROOM?
 PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE
 226.2 DISPERSION. DINING SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY.
  
 3C) PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS.
 CODE 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3.
 3C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3D) THE PLANS SHOW IN THE CENTER OF THE PLAN A INDOOR
 FIRE PIT, PLEASE PROVIDE THE TYPE OF FUEL, AMOUNT OF
 FUEL AND THE AMOUNT OF BTU?S WILL BE USED PER HOUR.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 4)SHEET A0.6 THE DETAIL MOUNTING HEIGHTS SHOWS SIGNAGE
 LOCATED CENTER LINED AT 60 INCHES. PLEASE SHOW
 COMPLIANCE WITH ACCESS. CODE 703.4.1 HEIGHT ABOVE
 FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS
 SHALL BE LOCATED 48 INCHES (1220 MM) MINIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES
 (1525 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE HIGHEST
 TACTILE CHARACTER.
  
 5) SHEET A0.6 THE RESTROOM DETAILS FOR THE WATER CLOSET
 GRAB BARS SHOWS THE DIMENSION TAKEN FROM THE FLOOR TO
 CENTERLINE OF THE GRAB BAR, BE AWARE THE 2014 ACCESS.
 CODE CHANGED THE DIMENSION TO THE TOP OF THE GRASPING
 SURFACE, SEE ACCESS. CODE 609.4.
  
 6) DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. PLEASE REVIEW SHEET A0.7 AND
 M2.1. SHEET A0.7 INDICATES A (1) HOUR FIRE RATING
 WHEREAS THE M2.1 SHOWS A (2) HR. FIRE RATING. SHAFTS
 LESS THAN 4 STORIES ONLY REQUIRE A 1 HOUR FIRE RATING,
 FBC-B 713.4.
  
 7) SEE SHEETS A0.5 FLOOR PLAN ENTRY DOOR 101 AND SHEET
 A8.3 DETAILS 5&6. SHEET A0.5 SHOWS A SINGLE ENTRY DOOR
 AND SIDE LIGHT. SHEET A8.3 SHOWS 2 DETAILS OF THE ENTRY
 DOOR, THE SIDE LIGHT DOESN?T APPEAR IN ANY DETAILS. THE
 OTHER ISSUE IS IN DETAIL 5 IT IS A SINGLE PAIN OF GLASS
 WITH PANIC HARDWARE, IN DETAIL # 6 THERE ARE (2) PANES
 OF GLASS AND NO PANIC HARDWARE. 107.2.1.3 DISCREPANCY
 IN PLANS AND FBC-B 1008.1.10 PANIC AND FIRE EXIT
 HARDWARE.
  
 8) SHEET A8.5 DETAIL # 11 SHOWS A PATIO GATE AND DETAIL
 # 5 A GUARDRAIL. SHEETS A0.3 AND A0.5 BOTH SHOW THE
 OUTDOOR PATIO BUT PLEASE NOTE THIS AREA IS THE PUBLIC
 RIGHT OF WAY. FBC-B 3202.1.3 AREAWAYS.
 AREAWAYS SHALL BE PROTECTED BY GRATES, GUARDS OR OTHER
 APPROVED MEANS.
  
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
 3202.2.1 STEPS.
 3202.2.2 ARCHITECTURAL FEATURES.
 3202.2.3 AWNINGS.
  
 9) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. 61-41,003
 ADMINISTRATION AND DEPARTMENT RESPONSIBILITIES. (4)
 TESTING & EVALUATION OF PRODUCTS. FL. S. 553.842
 PRODUCT EVALUATION AND APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 ROOF TOP VENTILATORS & FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) SHEET M103 SHOWS ROOF TOP FANS BUT THE DETAILS DO
 NOT PROVIDE ANCHORAGE OF THE CURB TO THE ROOF FRAMING
 NOR THE ROOFTOP FAN TO THE UNIT.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-12 Cont ID  
Sent By jleahy Date 2017-06-12 Time 08:29 Rev Time 0.00
Received By jleahy Date 2017-06-12 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-10 Cont ID  
Sent By jleahy Date 2017-03-10 Time 10:08 Rev Time 0.00
Received By jleahy Date 2017-03-09 Time 16:52 Sent To  
Notes
2017-03-10 10:50:30PAGE E101
 A) LOAD CACLUATION PER ARTICLE 220 REQUIRED.
 B) FAULT CURRENT CALCULATION REQUIRED PER 110.24
 C) LABELING FOR FAULT CURRENT REQUIRED PER 100.24
 D) NEED THE GROUNDING DETAIL SHOWN ON DRAWING FOR THE
 SERVICE.
 E) RISER DIAGRAM FEEDER 200 TOO SMALL FOR 400A
 F) RISER DIAGRAM FEEDER 300 NOT SHOWN ON DRAWINGS
 G) TIME CLOCK SUBMIT CUT SHEET
  
 PAGE E201
 A) CIRCUITS AT THE BAR B19,21,23, A48,18,22 REQUIRE
 GFCI PROTECTION 210.8(B)(5)
 B) KITCHEN OUTLETS A29,34,53,58,59, B31,33,35,37
 REQUIRE GFCI PROTECTION 210.8(B)(2)
  
 PAGE E202
 A) ROOF NEEDS AN OUTLET WITHIN 25' OF THE EQUIPMENT AND
 GFCI PROTECTED 210.63, 210.8(B)(3)
  
 PAGE E301
 A) SUBMIT INTERIOR LIGHTING POWER ALLOWANCES PER FBC EC
 C405.5.2
 B) LIGHTING IN BAR AREA NOT CLEAR ON DRAWINGSS LINES
 ALL OVER THE AREA NOT CONNECTED TO ANYTHING.
 C) LIGHT FIXTURE TYPES TO BE LABLELED ON ALL FIXTURES
 ON DRAWING FOR REVIEW.
 D) ALL CIRCUITS ARE SHOWN AS TIME CLOCK NEED CIRCUIT
 NUMBERS ON PLANS FOR LIGHTING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-28 Cont ID  
Sent By wjolin Date 2017-06-28 Time 12:30 Rev Time 0.00
Received By wjolin Date 2017-06-28 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-05-31 Cont ID  
Sent By wjolin Date 2017-05-31 Time 10:31 Rev Time 0.00
Received By wjolin Date 2017-05-24 Time 15:18 Sent To  
Notes
2017-05-24 12:15:28218 CLEMATIS STREET
 PERMIT #17020623
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PRODUCT DATA FOR THE FIRE PIT INDICATES IT IS ONLY
 TO BE INSTALLED OUTDOORS. ADDITIONALLY THIS OFFICE DOES
 NOT SUPPORT THE USE OF INTERIOR OPEN FLLAME DEVICES.
  
 SHEET E301: NO EMERGENCY LIGHTING PROVIDED.
  
 NFPA 96 SECTION 14.1.5 WHERE A SOLID FUEL COOKING
 APPLIANCE ALLOWS EFFLUENT TO ESCAPE FROM THE APPLIANCE
 OPENING, THIS OPENING SHALL BE COVERED BY A HOOD AND AN
 EXHAUST SYSTEM THAT MEETS THE REQUIREMENTS OF SECTIONS
 14.3, 14.4, AND 14.6.14.7.1 SOLID FUEL COOKING
 APPLIANCES THAT PRODUCE GREASELADEN VAPORS SHALL BE
 PROTECTED BY LISTED FIRE-EXTINGUISHING EQUIPMENT. NO
 TYPE I EXHAUST HOOD WITH SUPPRESSION SYSTEM PROVIDED
 FOR WOOD FIRED PIZZA OVENS.
  
 SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH
 NFPA 96. APPLIANCES WITH FIREBOXES OVER 5 FT3 THE WATER
 SOURCE SHALL BE A FIXED PIPE WATER SYSTEM WITH A HOSE
 OF ADEQUATE LENGTH TO REACH THE COMBUSTION AND COOKING
 CHAMBERS OF THE APPLIANCE. ALL OVEN ASH SHALL BE
 REMOVED FROM THE ASH COMPARTMENT AT LEAST ONCE PER DAY.
 THE ASH SHALL BE SPRAYED ADEQUATELY WITH WATER BEFORE
 REMOVAL TO EXTINGUISH ANY HOT ASH OR CINDERS AND TO
 CONTROL THE DUST WHEN THE ASH IS MOVED. SECTION
 14.9.3.8.1 A HEAVY METAL CONTAINER OR CART (MINIMUM 16
 GAUGE) WITH A COVER SHALL BE PROVIDED FOR THE REMOVAL
 OF ASH. THE ASH REMOVAL CONTAINER OR CART SHALL NOT
 EXCEED A MAXIMUM OF 20 GAL CAPACITY, SHALL BE ASSIGNED
 FOR THIS ONE PURPOSE, SHALL BE ABLE TO BE HANDLED
 EASILY BY ANY EMPLOYEE ASSIGNED THE TASK, AND SHALL
 PASS EASILY THROUGH ANY PASSAGEWAY TO THE OUTSIDE OF
 THE BUILDING. THE CONTAINER OR CART SHALL ALWAYS BE
 COVERED WHEN IT IS BEING MOVED THROUGH THE PREMISES.
  
 NO FIRE ALARM OR FIRE SPRINKLER SCOPE OF WORK PROVIDED.
  
 EXISTING EXIT DOORS: FOR ASSEMBLY OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-01 Cont ID  
Sent By wjolin Date 2017-03-01 Time 12:25 Rev Time 0.00
Received By wjolin Date 2017-02-21 Time 11:30 Sent To  
Notes
2017-03-01 11:25:59218 CLEMATIS STREET
 PERMIT #17020623
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 INSUFFICIENT EXIT SIGNS PROVIDED TO IDENTIFY PRIMARY
 AND SECONDARY EXITS. NO EMERGENCY LIGHTING PROVIDED.
  
 PROVIDE MORE INFORMATION AND DETAILS FOR THE FIREPIT.
 SUBMIT PRODUCT DATA AND UL LISTING (OR EQUAL).
  
 PROVIDE UL LISTING (OR EQUAL) DATA FOR THE PIZZA OVENS.
 SUBMIT PRODUCT DATA FOR WOOD FIRED PIZZA OVENS
 INDICATING IF A SUPPRESSION SYSTEM IS REQUIRED FOR THIS
 APPLIANCE.
  
 INDICATE THE LOCATION AND QUANTITY OF WOOD FUEL TO BE
 STORED FOR THE PIZZA OVENS.
  
 SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH
 NFPA 96. FOR EXAMPLE: PER SECTION 14.9.2.1. FUEL
 STORAGE SHALL NOT EXCEED A ONE-DAY SUPPLY WHERE STORAGE
 IS LOCATED IN THE SAME ROOM AS THE SOLID FUELED
 APPLIANCE, OR IN THE SAME ROOMS AS THE FUEL-LOADING OR
 CLEAN-OUT DOORS. SECTION14.9.3.7.3 APPLIANCES WITH
 FIREBOXES OVER 5 FT3 THE WATER SOURCE SHALL BE A FIXED
 PIPE WATER SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO
 REACH THE COMBUSTION AND COOKING CHAMBERS OF THE
 APPLIANCE. ALL OVEN ASH SHALL BE REMOVED FROM THE ASH
 COMPARTMENT AT LEAST ONCE PER DAY. THE ASH SHALL BE
 SPRAYED ADEQUATELY WITH WATER BEFORE REMOVAL TO
 EXTINGUISH ANY HOT ASH OR CINDERS AND TO CONTROL THE
 DUST WHEN THE ASH IS MOVED. SECTION 14.9.3.8.1 A HEAVY
 METAL CONTAINER OR CART (MINIMUM 16 GAUGE) WITH A COVER
 SHALL BE PROVIDED FOR THE REMOVAL OF ASH. THE ASH
 REMOVAL CONTAINER OR CART SHALL NOT EXCEED A MAXIMUM OF
 20 GAL CAPACITY, SHALL BE ASSIGNED FOR THIS ONE
 PURPOSE, SHALL BE ABLE TO BE HANDLED EASILY BY ANY
 EMPLOYEE ASSIGNED THE TASK, AND SHALL PASS EASILY
 THROUGH ANY PASSAGEWAY TO THE OUTSIDE OF THE BUILDING.
 THE CONTAINER OR CART SHALL ALWAYS BE COVERED WHEN IT
 IS BEING MOVED THROUGH THE PREMISES.
  
 MEP PLANS ARE SIGNED; HOWEVER, THE SEAL IS A COPY OF
 THE SEAL.
  
 NO FIRE ALARM OR FIRE SPRINKLER SCOPE OF WORK PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop G GAS REVIEW
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-09 Time   Rev Time 0.00
Received By gjohnson Date 2017-06-09 Time 15:00 Sent To  
Notes
2017-06-09 15:02:196/9/17 THE GAS HAS BEEN REMOVED FROM PLANS/GPJ

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By gjohnson Date 2017-03-17 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2017-03-17 Time 09:16 Sent To  
Notes
2017-03-17 09:22:30GAS COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC FUEL GAS 404.8.2 CONDUIT
 WITH BOTH ENDS TERMINATING INDOORS.
 WHERE THE CONDUIT ORIGINATES AND TERMINATES WITHIN THE
 SAME BUILDING, THE CONDUIT SHALL ORIGINATE AND
 TERMINATE IN AN ACCESSIBLE PORTION OF THE BUILDING AND
 SHALL NOT BE SEALED. THE CONDUIT SHALL EXTEND NOT LESS
 THAN 2 INCHES (51 MM) BEYOND THE POINT WHERE THE PIPE
 EMERGES FROM THE FLOOR.
  
 2, SHOW ROUTING FROM METER TO STEP DOWN REGULATOR NOT
 SHOWN ON SITE PLAN. PER WPB AMEND TO FBC 107,2,1
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 1ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-29 Cont ID  
Sent By lmarchan Date 2017-06-29 Time 16:41 Rev Time 0.00
Received By lmarchan Date 2017-06-16 Time 13:23 Sent To  
Notes
2017-06-20 13:23:57C01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-15 Cont ID  
Sent By cpuell Date 2017-06-15 Time 07:54 Rev Time 0.00
Received By cpuell Date 2017-05-17 Time 14:37 Sent To  
Notes
2017-05-18 14:37:41C01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-03-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-02-14 Time 10:46 Sent To  
Notes
2017-02-15 10:47:02C01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2017-07-03 Time 15:54 Sent To  
Notes
2017-07-06 10:07:17PALM BEACH COUNTY IMPACT FEE OFFICE
 MU-2017-018590-0000
 RECEIPT NUMBER: 2017-0705-47
 FEES: $244.64
2017-07-03 15:54:41GIVEN TO JWITMER

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-06-27 Cont ID  
Sent By jwitmer Date 2017-06-27 Time 06:42 Rev Time 0.00
Received By jwitmer Date 2017-06-27 Time 06:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-06-01 Cont ID  
Sent By jwitmer Date 2017-06-01 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2017-06-01 Time 11:29 Sent To  
Notes
2017-06-01 16:34:56IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By jwitmer Date 2017-03-17 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2017-03-14 Time 08:07 Sent To  
Notes
2017-03-17 10:54:29IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By ccole Date 2017-06-29 Time 09:33 Rev Time 0.00
Received By ccole Date 2017-06-28 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-31 Cont ID  
Sent By ccole Date 2017-05-31 Time 13:48 Rev Time 0.00
Received By ccole Date 2017-05-31 Time 10:40 Sent To  
Notes
2017-05-31 14:41:382ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020623
 5/31/17
  
 RESULTS: DENIED.
  
 1) THE TWO GREASE EXHAUST DUCTS FOR THE PIZZA OVENS
 MUST BE RUN SEPARATELY BECAUSE THEY ARE SERVING
 SOLID-FUEL FIRED APPLIANCES- PLEASE SEE SECTION 506.3.5
 ITEM #4 AND SEPARATE THE DUCTS.
  
 2) ADVISORY: PLEASE REVIEW PAGE #3 OF THE SUBMITTED
 INSTALLATION INSTRUCTIONS FOR THE PIZZA OVENS AND
 SPECIFY ON THE PLANS WHICH OF THE THREE EXHAUST SYSTEMS
 WILL BE INSTALLED.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 VENTLESS RANGE AND DISHWASHER HOODS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLANS.
  
 4) THE CAPTIVE-AIRE KITCHEN EXHAUST PLANS (SHEETS M102
 & M103) ARE NO LONGER APPLICABLE TO THE PROJECT. PLEASE
 EITHER REMOVE THE SHEETS FROM THE PLAN SETS, OR REVISE
 THEM TO SHOW THE NEW VENTLESS HOODS PLANS, DETAILS, AND
 EQUIPMENT SCHEDULES.
  
 5) M101: THE AIR BALANCE DIAGRAM NEEDS TO BE REVISED TO
 MATCH THE REVISED PLANS AND SYSTEMS. PLEASE NOTE THE
 FOLLOWING: A) EF02 IS INDICATED TO HAVE A CAPACITY OF
 1475 CFMS IN THE AIR BALANCE DIGRARM, BUT ONLY 470 CFMS
 IN THE FAN SCHEDULE. B) EF04 AND SF03 ARE STILL SHOWING
 IN THE DIAGRAM HOWEVER THEY HAVE BEEN REMOVED FROM THE
 PLANS.
  
 6) M101: PLEASE PLACE A NOTE TO INDICATE THE LOCATIONS
 OF THE AHU ACCESS PANELS AND PROVIDE DIMENSIONS-
 SECTION 306.1
  
 7) THE WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 ROOFTOP EQUIPMENT IS INCOMPLETE: A) PROVIDE DETAILS FOR
 ANCHORING THE NEW CONDENSERS TO THE EXISTING STANDS. B)
 PROVIDE DETAILS FOR INSTALLATION OF THE GREASE DUCT
 SUPPORTS. C) SUBMIT THE NOA FOR THE NEW ROOF STAND WITH
 SHOP DRAWING APPORVAL STAMP BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By ccole Date 2017-02-23 Time 11:42 Rev Time 0.00
Received By ccole Date 2017-02-23 Time 11:42 Sent To  
Notes
2017-02-23 13:01:051ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020623
 2/23/17
  
 1) THE CITY OF WEST PALM BEACH BUILDING DIVISION
 REQUIRES SEPARATE PERMITS FOR KITCHEN EXHAUST HOODS,
 FIRE SUPPRESSION SYSTEMS, FIRE SPRINKLERS, AND WALK-IN
 COOLERS AND FREEZERS- PLACE A NOTE ON THE PLANS
 ACCORDINGLY. PLEASE NOTE THAT NO DETAILS OR
 SPECIFICATIONS FOR THE DISHWASHER HOOD HAVE BEEN
 PROVIDED.
  
 2) SHEET M201: THE MAKEUP AIR DUCT FOR THE KITCHEN
 HOODS IS PROHIBITED FROM BEING IN THE SAME RATED SHAFT
 ENCLOSURE WITH THE GREASE EXHAUST DUCT- SECTION
 506.3.11. OPTIONS- REMOVE THE MAKEUP AIR DUCT, OR
 INDICATE THE GREASE DUCT IS TO BE WRAPPED WITH APPROVED
 LISTED AND LABELED DUCT WRAP PER SECTION 506.3.11.2.
  
 3) ADVISORIES- KITCHEN AND EXHAUST HOODS:
  
 A) AN 18" CLEARANCE TO COMBUSTIBLES IS REQUIRED FOR THE
 GREASE EXHAUST DUCTS- SEE SECTIONS 506.3.6, 506.3.11,
 506.3.11.1, & 506.3.11.2. IF A DUCT WRAP IS TO BE
 INSTALLED, MANUFACTURER'S SPECIFICATIONS SHALL BE
 SUBMITTED PER SECTION 506.3.11.2, AND THE GREASE DUCT
 PENETRATIONS INTO AND OUT OF THE RATED SHAFTS SHALL BE
 PROTECTED WITH A THROUGH-PENETRATION FIRE-STOP SYSTEM
 CLASSIFIED IN ACCORDANCE WITH ASTM E 814 OR UL 1497.
 PLEASE NOTE THAT THERE IS NO REQUIREMENT FOR THE FIRE
 DAMPERS TO BE INSTALLED IN THE GREASE DUCTS AT THE
 SHAFT PENETRATIONS.
  
 B) PLEASE NOTE THAT THE TEMPERATURE DIFFERENTIAL
 BETWEEN MAKE-UP AIR FOR THE KITCHEN EXHAUST AND THE AIR
 IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F
 PER SECTION 508.1.1. MEETING THIS COMPLIANCE MAY
 REQUIRE PRE-COOLING OF THE MAKE-UP AIR USING AN AC UNIT
  
 C) THE NOA'S FOR THE ROOFTOP FANS MUST BE SUBMITTED
 WITH SHOP DRAWING APPROVAL STAMPS AND SIGNATURES BY THE
 ENGIEER OF RECORD. THE EOR MUST ALSO CIRCLE, HIGHLIGHT,
 OR OTHERWISE MARK ALL APPLICABLE INSTALLATION NOTES,
 DETAILS, DESIGN PRESSURES, AND ANCHORING METHODS ON THE
 DOCUMENTS.
  
 4) SHEETS M201 & A0.7: THE PLANS ARE CONFLICTING
 CONCERNING THE HOURLY FIRE-RATINGS OF THE SHAFTS.
  
 5) SHEET M201: INDICATE THE REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS FOR THE O/A INTAKE LOCATIONS AS REQUIRED
 BY SECTION 401.4.
  
 6) M201: SHOW THE TERMINATION LOCATION OF THE
 DISHWASHER HOOD EXHAUST DUCT.
  
 7) M201: REFER TO SECTION 304 FLORIDA FUEL GAS CODE AND
 PROVIDE COMBUSTION AIR CALCULATIONS FOR THE PIZZA
 OVENS, THE KITCHEN COOKING APPLIANCES, AND THE GAS
 WATER HEATER.
  
 8) PROVIDE AN EQUIPMENT SCHEDULE FOR THE GAS WATER
 HEATER AND MODIFY THE DETAIL ON M101 TO INDICATE THE
 TYPE AND SIZE OF GAS VENT AND TOTAL RUN FROM THE WH TO
 THE TERMINATION CAP.
  
 9) M201: INDICATE HOW ACCESS FOR MAINTENANCE AND
 REPLACEMENT OF THE AIR HANDLERS IN THE SOFFIT WILL BE
 PROVIDED- SEE SECTION 306.1.
  
 10) M201: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE
 AHU'S- SECTION 307.
  
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PIZZA
 OVENS AND THEIR ASSOCIATED EXHAUST HOODS AND VENTS. SEE
 COMMENT #2B ABOVE- FIRE DAMPERS MAY NOT BE REQUIRED FOR
 THE EXHAUST DUCT PENETRATING THE SHAFT ENCLOSURE.
  
 12) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION
 OF ALL THE ROOF TOP MECHANICAL EQUIPMENT PER SECTION
 301.15. PLEASE PROVIDE COMPLETE DETAILS FOR ANCHORING
 THE UNITS TO THE ROOF STRUCTURE.
  
 13) PLEASE REVIEW CHAPTER 10 OF THE FBC-14 EXISTING
 BUILDING CODE- THE PROPOSED PROJECT IS A CHANGE OF
 OCCUPANCY AND SHOULD BE NOTED AS SUCH UNDER THE
 BUILDING CODE DATA ON SHEET A0.1.
  
 14) PLEASE REVIEW SECTION C101.4.4 AND SECTION C401.2
 FBC-14 ENERGY CONSERVATION AND PROVIDE DOCUMENTATION OF
 ENERGY CONSERVATION COMPLIANCE. THE SUBMITTED ENERGY
 FORM C402-2014 IS FOR RENOVATED BUILDINGS, AND CANNOT
 BE USED FOR BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 15:00 Rev Time 0.00
Received By gjohnson Date 2017-06-09 Time 15:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By gjohnson Date 2017-03-17 Time 08:34 Rev Time 0.00
Received By gjohnson Date 2017-03-17 Time 08:33 Sent To  
Notes
2017-03-17 09:12:431ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. DOOR ON ACCESSIBLE TOILET STALLS SHALLL NOT SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE
 REQUIRED TURNING SPACE. PER FBC ACC 603.2.3
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW. PER FBC ACC 604.7
  
 4. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602.
 PER FBC ACC 602.1
  
 5. ALL FIXTURE FLOWING THROUGH GREASE INTERCEPTOR SHALL
 BE INCLUDED ON THE SIZING CALCULATION THE FIXTURES THAT
 ARE MISSING FROM CALCULATIONS ARE # 4 MOP SINK, #6.1
 SINK, #6.2 SINK, #7 PRE RINSE SINK, #8 DISHWASHER , #12
 SINK , #32.A TROUGH DRAIN. PER FBC PL 1003.3.1
  
 6. FIXTURES IN THE BAR AREA SHALL NOT BE ON THE GREASE
 SYSTEM. PER FBC PL 1003.2
  
 7. THE THREE COMP SINK SHALL BE INDIRECTLY WASTED. PER
 FBC PL 802.1
  
 8. SHT. P101 DETAIL B5 THE FIRST NOTE REQUIRING
 TEMPERED WATER IS WRONG THE TEMPERATURE FOR TEMPERED
 WATER SHAL BE BETWEEN 85?F (29?C) AND 110?F (43?C). PER
 FBC PL 202
  
 9. SHOW TEMPERATURE LIMITING DEVICE ON WATER RISER
 DIAGRAM TO SHOW COMPLIANCE WITH FBC PL 416.5
  
 10. SHOW COMPLIANCE WITH FBC PL 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By   Date 2017-06-29 Time   Rev Time 0.00
Received By kmartin Date 2017-06-29 Time 15:34 Sent To I
Notes
2017-06-29 15:35:02BASED ON WASTE PRODUCTION CALCULATIONS, THE BUILDING
 OWNER WILL BE CONTACTED FOR NECESSARY IMPROVEMENTS TO
 THE WASTE RECEPTACLE AREA.

Review Stop Z ZONING
Rev No 2 Status F Date 2017-06-14 Cont ID  
Sent By   Date 2017-06-14 Time   Rev Time 0.00
Received By kmartin Date 2017-06-14 Time 15:10 Sent To  
Notes
2017-06-14 15:17:35PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
  
 1. THIS PERMIT DOES NOT INCLUDE THE AREA IDENTIFIED AS
 -OUTDOOR PATIO 100- ON SHEET A 0.5. A SEPARATE PROCESS,
 SIDEWALK CAFE IS REQUIRED. BE ADVISED THAT OUTDOOR
 FURNITURE SHALL NOT BE FIXED PERMANENTLY. ALL OUTDOOR
 FURNITURE SHALL BE STORED AFTER OPERATION HOURS.
  
 2. DUMPSTER SHALL BE PROPERLY SCREENED AND LANDSCAPED
 MEETING THE REQUIREMENTS OF SECTION 94-315.
  
 FOR MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN,
 URBAN DESIGN PLANNER, AT [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-09 Cont ID  
Sent By   Date 2017-03-09 Time   Rev Time 0.00
Received By kmartin Date 2017-03-08 Time 16:51 Sent To  
Notes
2017-03-09 16:07:381. THIS PERMIT DOES NOT INCLUDE THE AREA IDENTIFIED AS
 -OUTDOOR PATIO 100- ON SHEET A 0.5. A SEPARATE PROCESS,
 SIDEWALK CAFE IS REQUIRED. BE ADVISED THAT OUTDOOR
 FURNITURE SHALL NOT BE FIXED PERMANENTLY. ALL OUTDOOR
 FURNITURE SHALL BE STORED AFTER OPERATION HOURS.
  
 2. SHOW DUMPSTER ON THE SITE PLAN, ENSURE THAT IT IS
 PROPERLY SCREENED AND LANDSCAPED MEETING THE
 REQUIREMENTS OF SECTION 94-444.
  
 FOR MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN,
 URBAN DESIGN PLANNER, AT [email protected].