Plan Review Details - Permit 17020618
Plan Review Stops For Permit 17020618
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-22 Cont ID  
Sent By rmcdouga Date 2017-03-22 Time 12:54 Rev Time 0.00
Received By rmcdouga Date 2017-03-22 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-07 Cont ID  
Sent By rmcdouga Date 2017-03-07 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2017-03-07 Time 17:05 Sent To  
Notes
2017-03-07 18:23:14PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GAF MODIFIED ROOF SYSTEM SPECIFIED HAS A MAXIMUM
 DESIGN PRESSURE THAT IS NOT ADEQUATE FOR THE PERIMETER
 AND CORNER ROOF AREAS. SUBMIT TWO SETS OF SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 NUMBER 7 OF NOA NO. 14-1030.02. FBC 103.2.1
 THE CALCULATIONS THAT WERE SUBMITTED ARE INCORRECT.
 THIS PROJECT IS A TWO STORY ADDITION, THE MEAN ROOF
 HEIGHT IS AROUND 20 FEET. THE HEIGHT ON THE
 CALCULATIONS IS SPECIFIED AS 8 FEET. THE PARAPET WALL
 IS 1' 9" HIGH, NOT 4', THEREFORE, THE UPLIFT PRESSURES
 IN THE CORNERS ARE NOT THE SAME AS THE PERIMETER
 PRESSURES. THE BASE SHEET FASTENING FOR THE CORNERS IS
 SPECIFIED AS 24 STAGGERED ROWS. PLEASE SUBMIT CORRECTED
 CALCULATIONS AND REVIEW THEM CAREFULLY FOR ERRORS.
  
 2) THE REVISION FEES OF $305.50 WILL NEED TO BE PAID
 BEFORE ANY MORE PLAN REVIEWS ARE DONE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By rmcdouga Date 2017-02-21 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2017-02-21 Time 15:01 Sent To  
Notes
2017-02-21 17:33:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - THE PRODUCT APPROVALS ARE REQUIRED TO
 BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 2) THE GAF MODIFIED ROOF SYSTEM SPECIFIED HAS A MAXIMUM
 DESIGN PRESSURE THAT IS NOT ADEQUATE FOR THE PERIMETER
 AND CORNER ROOF AREAS. SUBMIT TWO SETS OF SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 NUMBER 7 OF NOA NO. 14-1030.02. FBC 103.2.1
  
 3) FOUR OF THE PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE CHANGES OR WERE NOT PREVIOUSLY SUBMITTED AND ARE
 CONSIDERED REVISIONS. THE BORAL TILESEAL UNDERLAYMENT
 NOA NO. 12-0417.06 AND THE PGT FD-101 FRENCH DOORS NOA
 NO. 16-0629.17 ARE NEW. THE EAGLE ROOFING CAPISTRANO
 CONCRETE TILE NOA NO. 15-0223.20 AND THE PGT
 PW-701/720/820 FIXED WINDOWS NOA NO. 16-0629.14 ARE
 CHANGES. THE REVISION FEE IS $100.00 PLUS $50.00 PER
 PRODUCT APPROVAL. THE TOTAL IS $305.50.
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-03-21 Cont ID  
Sent By destabro Date 2017-03-21 Time 08:38 Rev Time 0.00
Received By destabro Date 2017-03-21 Time 08:38 Sent To B
Notes
2017-03-20 15:03:40ROUTED TO DESIREE ESTABROOK

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-02-17 Cont ID  
Sent By destabro Date 2017-02-17 Time 13:44 Rev Time 0.00
Received By destabro Date 2017-02-17 Time 13:44 Sent To B
Notes
2017-02-15 14:37:23ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-22 Cont ID  
Sent By rmcdouga Date 2017-03-22 Time 12:54 Rev Time 0.00
Received By rmcdouga Date 2017-03-15 Time 13:15 Sent To  
Notes
2017-03-16 13:16:03RESUB ROUTED TO DESTABRO VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-21 Cont ID  
Sent By rmcdouga Date 2017-02-21 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2017-02-14 Time 09:40 Sent To  
Notes
2017-02-15 09:40:36SUBMITTAL ROUTED TO HISTORIC VIA ZONING INBOX