Plan Review Details - Permit 17020494
Plan Review Stops For Permit 17020494
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By skennedy Date 2017-03-13 Time 15:22 Rev Time 0.00
Received By skennedy Date 2017-03-13 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By skennedy Date 2017-02-22 Time 09:35 Rev Time 0.00
Received By skennedy Date 2017-02-22 Time 09:35 Sent To  
Notes
2017-02-22 11:05:351ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING ALTERATION LEVEL
 II
  
 1) PLEASE INDICATE THE CODE IN EFFECT AND THE SCOPE OF
 WORK UPON THE PLAN AS FOLLOWS:
 FBC 2014 5TH ED. RESIDENTIAL
 FBC 2014 EXISTING BUILDING ALTERATION LEVEL II
  
 2) THE DESIGNER IS REQUIRED TO SIGN THE PLAN PER
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 3) THE PRINT QUALITY OF THE PLAN IS TOO LIGHT, PLEASE
 REPRINT DARKER TO DEMONSTRATE THE ALTERATIONS PER FBC
 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 4) A DOOR AND GARAGE DOOR PRODUCT APPROVALS ARE
 PROVIDED. PLEASE INDICATE THE LOCATION OF THE DOOR TO
 BE REPLACED ACTUALLY ON THE PLAN AND NOTE UPON THE PLAN
 THE GARAGE DOOR REPLACEMENT.
  
 *NOTE THERE IS A SCOPE OF WORK PROVIDED INDICATING
 RELATED INFORMATION HOWEVER; THE ACTUAL PLAN SHOULD
 HAVE RELATIVE NOTATIONS AS IS DONE ON THE PLAN FOR
 WINDOW REPLACEMENTS. THERE ARE OTHER ITEMS IN THE SCOPE
 THAT SHOULD BE ADDED TO THE PLAN SUCH AS THE ADDING OF
 BEAMS, YOU MAY WISH TO CONSIDER ADDING THE SCOPE OF
 WORK NOTES IN GENERAL TO THE PLAN
  
 PLEASE ALSO NOTE THAT THE SCOPE OF WORK PROVIDED
 INDICATES OTHER WORK NOT SHOWN ON THE PLAN THAT EACH
 REQUIRE SEPARATE PERMITS AND PLAN SUBMITTALS IN THIS
 JURISDICTION AS FOLLOWS:
 A) POOL & POOL DECK MODIFICATIONS
 B) POOL BARRIER AND FENCE
 C) DRIVEWAY
 ADDITIONALLY NOTE THESE SEPARATE PERMIT SUBMITTALS WILL
 BE ASSESSED FEES BASED UPON THE VALUE OF EACH,
 ACCORDINGLY, YOU MAY WISH TO REDUCE THE VALUE CLAIMED
 ON THIS SUBMITTAL BY THE CORRESPONDING VALUE OF EACH TO
 BE SUBMITTED IN THE FUTURE.
 5) PLEASE PROVIDE TYPICAL WALL SECTION DETAILS FOR NEW
 WALLS PARTICULARLY THE NEW SHOWER WALLS AND ANY SHOWER
 PAN DETAILS.
 6) PLEASE INDICATE THAT REPLACEMENT BEDROOM WINDOWS
 WILL MEET THE REQUIREMENTS OF FBC EXISTING
 SECTION 704 MEANS OF EGRESS
  
 704.1 GENERAL.
 MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 701.1 AND
 THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE.
  
 EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL
 DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5-PERCENT
 REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED.
  
 7) PLEASE PROVIDE NOTES TO DEMONSTRATE IN NEW BEDROOM
 NUMBER 4 THE EXISTING WINDOW WILL MEET THE REQUIREMENTS
 OF SECTION FBC-R310 EMERGENCY ESCAPE AND RESCUE
 OPENINGS
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By skennedy Date 2017-03-13 Time 15:23 Rev Time 0.00
Received By skennedy Date 2017-03-13 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By skennedy Date 2017-02-22 Time 09:35 Rev Time 0.00
Received By skennedy Date 2017-02-22 Time 09:35 Sent To  
Notes
2017-02-22 11:50:271ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 1) PLEASE SEE BUILDING PLAN REVIEW FOR QUALITY OF PLAN
 AND NEEDED NOTES.
  
 2) PLEASE PROVIDE NOTES TO DEMONSTARTE COMPLIANCE WITHT
 HE FOILLOWING FOR ALTERED ARES.
  
 FBCRE3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 SHOW THE BELOW AS EXISTING, PROPOSED OR NOTE TO BE
 EVALUATED.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 NOTE THAT A REVISED PANEL SCHEDULE WILL BE PROVIDED AS
 NEED OR INCLUDE IN RE-SUBMITTAL.
  
  
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-13 Cont ID  
Sent By skennedy Date 2017-03-13 Time 15:23 Rev Time 0.00
Received By skennedy Date 2017-03-13 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-22 Cont ID  
Sent By skennedy Date 2017-02-22 Time 09:36 Rev Time 0.00
Received By skennedy Date 2017-02-10 Time 08:51 Sent To  
Notes
2017-02-13 08:52:22SKENNEDY'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By skennedy Date 2017-03-13 Time 15:23 Rev Time 0.00
Received By skennedy Date 2017-03-13 Time 15:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By skennedy Date 2017-02-22 Time 09:35 Rev Time 0.00
Received By skennedy Date 2017-02-22 Time 09:35 Sent To  
Notes
2017-02-22 11:06:301ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 PLEASE PROVIDE A HVAC DUCT PLAN TO SHOW REQUIRED
 MODIFICATION TO DUCTS IN ACCORDANCE WITH:
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 , BALANCED AIR IN NEW
 BEDROOM 4 PERM FBC-R 1602.4, & BATH EXHAUST PER FBC-R
 M15.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By skennedy Date 2017-03-13 Time 15:23 Rev Time 0.00
Received By skennedy Date 2017-03-13 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By skennedy Date 2017-02-22 Time 09:36 Rev Time 0.00
Received By skennedy Date 2017-02-22 Time 09:36 Sent To  
Notes
2017-02-22 11:40:391ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 1) PLEASE PROVIDE A PLUMBING RISER DIAGRAM FOR THE NEW
 BATHROOM & KITCHEN AREAS AND NOTES TO INDICATE THE
 CAPING OFF OF OTHER SUPPLY AND WASTE LINES.
 2) PLEASE SEE THE BUILDING PLAN REVIEW AS TO QUALITY OF
 PLAN AND NEEDED SHOWER DETAILS.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  