Plan Review Details - Permit 17020446
Plan Review Stops For Permit 17020446
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-17 Cont ID  
Sent By jwitmer Date 2017-02-17 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2017-02-17 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 15:05 Rev Time 0.00
Received By jwitmer Date 2017-02-15 Time 13:45 Sent To  
Notes
2017-02-15 15:09:28BUILDING PLAN REVIEW
 W. P. B. REVISION: 17020446
 W. P. B. PERMIT: 16070025
 ADD: 2450 METRO CENTRE BLVD.
 CONT: MEDICAL CONSULTANTS PLUS
 TEL: 954-444-3325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 15/ 2017
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEET IS NOT SIGNED NOR SEALED BY
 A FLORIDA REGISTERED ARCHITECT. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS. PLANS ARE TO BE
 SIGNED WITH A FULL SIGNATURE FROM THE ARCHITECT OF
 RECORD PER 481.221 WITH A MINIMUM OF FIRST AND LAST
 NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 2) THE STRUCTURAL SHEET S1 & S2 ARE NOT SIGNED NOR
 SEALED BY A FLORIDA ENGINEER. FL ADMIN CODE
 61G15-23.002 ENGINEERS EFFECTIVE DATE 05/06/2009.
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 3) THE MRI SHEETS FROM GE HEALTHCARE HAVE NOT BEEN
 REVIEWED BY THE DESIGNER OF RECORD AND SHOP DRAWING
 STAMP OF APPROVAL APPLIED. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) SHEET A.1 HAS THE EQUIPMENT ROOM IN A DIFFERENT
 LOCATION THAN THE PROPOSED DRAWINGS BY G. E. HEALTHCARE
 IS A REVISION REQUIRED? 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5A) THIS BUILDING SITE HAS BEEN TAKEN OUT OF AN A FLOOD
 ZONE BY LETTER OF MAP REVISION. PLEASE NOTE THE
 PROPOSED CHILLER PAD ON THE EXTERIOR OF THE BUILDING
 MUST HAVE THE TOP OF THE EQUIPMENT PAD ABOVE THE HEIGHT
 OF 16.00 FT. NGVD. TO BE IN COMPLIANCE WITH FEMA
 REGULATIONS. PLEASE IDENTIFY ON PLANS. FBC-B 1603.1.7
 FLOOD DESIGN DATA.
  
 5B) THE GE HEALTHCARE PLANS DO NOT INDICATE HOW THE
 CHILLER IS TO BE MOUNTED TO THE SLAB, NOR HOW THE
 CHILLER WILL BE ANCHORED TO PREVENT THE UNIT FROM
 OVERTURNING, DUE TO HIGH WINDS. 2014 FBC-M- 301.15 WIND
 RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 6) SHEET A1 OF THE GE HEALTHCARE PLANS NOTE #65
 INDICATES A REMOVAL OF A PORTION OF WALL 9?-0? X 9?-0?
 WHEREAS THE ISSUED SET OF PLANS DOES NOT PROVIDE ANY
 SUCH NOTE NOR OF WHAT MATERIALS THE WALL IS TO BE
 REBUILT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-14 Cont ID  
Sent By vperez Date 2017-02-14 Time 13:25 Rev Time 0.00
Received By vperez Date 2017-02-14 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-15 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 15:09 Rev Time 0.00
Received By jwitmer Date 2017-02-09 Time 14:06 Sent To  
Notes
2017-02-13 14:06:51VPEREZ'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-02-17 Cont ID  
Sent By ccole Date 2017-02-15 Time 07:10 Rev Time 0.00
Received By ccole Date 2017-02-14 Time 15:58 Sent To  
Notes
***NONE***