Plan Review Details - Permit 17020392
Plan Review Stops For Permit 17020392
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-02 Cont ID  
Sent By rmcdouga Date 2017-03-02 Time 15:31 Rev Time 0.00
Received By rmcdouga Date 2017-03-02 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-27 Cont ID  
Sent By rmcdouga Date 2017-02-27 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2017-02-24 Time 18:48 Sent To  
Notes
2017-02-27 10:27:11PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FINAL BASE SHEET FASTENER SPACING FOR ROOF ZONES
 2 AND 3 IS INCORRECT. THE SPACING FOR ZONE 2 SHOULD BE
 8" OC IN THE LAP AND 8" OC IN 3 ROWS IN THE FIELD. THE
 SPACING FOR ZONE 3 SHOULD BE 5" OC IN THE LAP AND 5" OC
 IN 3 ROWS IN THE FIELD. IT APPEARS THAT THE FRACTIONS
 WERE ROUNDED UP RATHER THAN DOWN AS REQUIRED BY RAS
 117. ALSO, PLEASE SUBMIT THE ACTUAL RAS 117 ENHANCED
 FASTENING CALCULATIONS WITH YOUR DOCUMENTS. GENERAL
 LIMITATION NUMBER 7 ON PAGE 16 OF NOA NO. 13-1022.15
 REQUIRES ROOFING APPLICATION STANDARD 117 CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT OR
 REGISTERED ROOF CONSULTANT. SEE FBC 107.2.1.3
 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 AND THE BASIS OF CALCULATIONS. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE
 BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR
 ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE AS STATE LAW REQUIRES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-13 Cont ID  
Sent By rmcdouga Date 2017-02-13 Time 18:22 Rev Time 0.00
Received By rmcdouga Date 2017-02-13 Time 17:17 Sent To  
Notes
2017-02-13 17:35:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESIGNER OF RECORD'S REVIEW STAMPS ARE REQUIRED
 ON THE PRODUCT APPROVALS, NOT THE ENHANCED FASTENING
 CALCULATIONS. FBC 107.3.4
  
 2) THE RAS 117 ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FS 471 &
 FAC 61G15 - 23.002
  
 3) THE ROOF ZONE WIND PRESSURE CALCULATIONS FOR THE 10
 FT. MEAN ROOF HEIGHT IS NOT APPLICABLE TO BUILDING "A".
 THESE 3 STORY TOWNHOUSES DO NOT HAVE THE DETACHED
 GARAGE. PLEASE REMOVE THEM FROM THIS SUBMITTAL. FBC
 107.2.1
  
 4) THE ROOF ZONE WIND PRESSURE CALCULATION DOCUMENTS
 THAT WERE SUBMITTED, SPECIFY A 160 MPH BASIC WIND
 SPEED, A 30 FT MEAN ROOF HEIGHT AND EXPOSURE CATEGORY
 D. ON SHEET S15 OF THE APPROVED PLANS A 170 MPH BASIC
 WIND SPEED, A 33.33 FT MEAN ROOF HEIGHT AND EXPOSURE
 CATEGORY C ARE SPECIFIED. PLEASE CORRECT THE ROOF ZONE
 WIND PRESSURE CALCULATION DATA TO CORRESPOND WITH THE
 APPROVED PLANS. FBC 107.2.1 & FBC-R301.2.1
  
 5) THE FINAL BASE SHEET FASTENER SPACING FOR ROOF ZONES
 2 AND 3 IS INCORRECT. THE SPACING SHOULD BE 8" OC IN
 THE LAP AND 3 FIELD ROWS FOR ZONE 2 AND 5" OC IN THE
 LAP AND 3 FIELD ROWS FOR ZONE 3. IT APPEARS THAT THE
 FRACTIONS WERE ROUNDED UP RATHER THAN DOWN AS REQUIRED
 BY RAS 117. ALSO, PLEASE SHOW THE ACTUAL RAS 117
 CALCULATIONS ON YOUR DOCUMENTS. FBC 107.2.1.4
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-02 Cont ID  
Sent By rmcdouga Date 2017-03-02 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2017-03-01 Time 09:48 Sent To  
Notes
2017-03-02 09:48:33RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-27 Cont ID  
Sent By rmcdouga Date 2017-02-27 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2017-02-22 Time 14:37 Sent To  
Notes
2017-02-23 14:37:56RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-13 Cont ID  
Sent By rmcdouga Date 2017-02-13 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2017-02-09 Time 11:56 Sent To  
Notes