| 2017-02-13 17:35:05 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE DESIGNER OF RECORD'S REVIEW STAMPS ARE REQUIRED |
| | ON THE PRODUCT APPROVALS, NOT THE ENHANCED FASTENING |
| | CALCULATIONS. FBC 107.3.4 |
| | |
| | 2) THE RAS 117 ARE REQUIRED TO HAVE THE FLORIDA |
| | ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE, |
| | COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FS 471 & |
| | FAC 61G15 - 23.002 |
| | |
| | 3) THE ROOF ZONE WIND PRESSURE CALCULATIONS FOR THE 10 |
| | FT. MEAN ROOF HEIGHT IS NOT APPLICABLE TO BUILDING "A". |
| | THESE 3 STORY TOWNHOUSES DO NOT HAVE THE DETACHED |
| | GARAGE. PLEASE REMOVE THEM FROM THIS SUBMITTAL. FBC |
| | 107.2.1 |
| | |
| | 4) THE ROOF ZONE WIND PRESSURE CALCULATION DOCUMENTS |
| | THAT WERE SUBMITTED, SPECIFY A 160 MPH BASIC WIND |
| | SPEED, A 30 FT MEAN ROOF HEIGHT AND EXPOSURE CATEGORY |
| | D. ON SHEET S15 OF THE APPROVED PLANS A 170 MPH BASIC |
| | WIND SPEED, A 33.33 FT MEAN ROOF HEIGHT AND EXPOSURE |
| | CATEGORY C ARE SPECIFIED. PLEASE CORRECT THE ROOF ZONE |
| | WIND PRESSURE CALCULATION DATA TO CORRESPOND WITH THE |
| | APPROVED PLANS. FBC 107.2.1 & FBC-R301.2.1 |
| | |
| | 5) THE FINAL BASE SHEET FASTENER SPACING FOR ROOF ZONES |
| | 2 AND 3 IS INCORRECT. THE SPACING SHOULD BE 8" OC IN |
| | THE LAP AND 3 FIELD ROWS FOR ZONE 2 AND 5" OC IN THE |
| | LAP AND 3 FIELD ROWS FOR ZONE 3. IT APPEARS THAT THE |
| | FRACTIONS WERE ROUNDED UP RATHER THAN DOWN AS REQUIRED |
| | BY RAS 117. ALSO, PLEASE SHOW THE ACTUAL RAS 117 |
| | CALCULATIONS ON YOUR DOCUMENTS. FBC 107.2.1.4 |
| | |