Plan Review Details - Permit 17020349
Plan Review Stops For Permit 17020349
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-15 Cont ID  
Sent By rmcdouga Date 2017-03-15 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2017-03-15 Time 07:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By rmcdouga Date 2017-02-21 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-02-21 Time 07:22 Sent To  
Notes
2017-02-21 13:54:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON PAGE 1 OF THE ENGINEER'S DRAWINGS THE QMPV
 E-MOUNT AND TILE DETAILS ARE TOO SMALL TO BE LEGIBLE.
 SUBMIT DRAWINGS THAT ARE LEGIBLE. FBC 107.2.1.4
  
 2) THE SIGNED AND SEALED PLANS HAVE BEEN CHANGED USING
 WHITEOUT. THIS IS NOT ALLOWED, AS THERE IS NO WAY TO
 DETERMINE IF THE CHANGES WERE MADE BY THE ENGINEER. FS
 471

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By vperez Date 2017-03-13 Time 10:12 Rev Time 0.00
Received By vperez Date 2017-03-13 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By vperez Date 2017-02-14 Time 11:35 Rev Time 0.00
Received By vperez Date 2017-02-14 Time 11:35 Sent To B
Notes
2017-02-14 11:44:12INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1- PLEASE NOTE THAT ALTHOUGH 16 MODULES ARE BEING
 SELECTED, THE LR-16-0124A INDICATED 20 MODULES.
 CLARIFYFBC 107.3.5
 2- THE MARK UPS AND SELECTION OF SYSTEM TO BE INSTALLED
 DOES NOT MEET THE CLARITY REQUIRED FOR RECORDS
 MANAGMENT. SUBMIT ONLY THE APPLICABLE INFORMATION FOR
 THIS PROJECT. FBC 107.2.1.4
 3- COMMENTS MAY FOLLOW UPON RESUBMITTAL.
 VAL PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-15 Cont ID  
Sent By rmcdouga Date 2017-03-15 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2017-03-10 Time 14:19 Sent To  
Notes
2017-03-10 14:20:23VPEREZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-21 Cont ID  
Sent By rmcdouga Date 2017-02-21 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2017-02-08 Time 13:21 Sent To  
Notes
2017-02-09 13:21:58ROUTED TO ELECTRICAL INBOX