Plan Review Details - Permit 17020341
Plan Review Stops For Permit 17020341
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-21 Cont ID  
Sent By jwitmer Date 2017-03-21 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2017-03-21 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-16 Cont ID  
Sent By jwitmer Date 2017-02-16 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2017-02-16 Time 07:16 Sent To  
Notes
2017-02-16 08:12:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020341
 ADD: 4601 N. CONGRESS AVE. SUITE # 107
 CONT: DOWN SOUTH BUILDERS LLC
 TEL: 561-701-1602
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 16/ 2017
 ACTION: DENIED
  
 1) SHEET A-3.0:
 1A) THE ENTRY DOOR (114A) INTO THE SICK ROOM IS MISSING
 THE MANEUVERING CLEARANCE OF 18 INCHES LATCH SIDE OF
 THE DOOR PULL SIDE OF THE DOOR. SEE 2014
 FBC-ACCESSIBILITY CODE 404.2.4 & TABLE 404.2.4.1
 MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS.
  
 1B) THE ENTRY DOORS (117 A & B) INTO THE MANAGERS? ROOM
 IS MISSING THE MANEUVERING CLEARANCE OF 18 INCHES LATCH
 SIDE OF THE DOOR PULL SIDE OF THE DOOR. SEE 2014
 FBC-ACCESSIBILITY CODE 404.2.4 & TABLE 404.2.4.1
 MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS.
  
 1C) THE REFERRAL ROOM (104) ALSO ROOM IS MISSING THE
 MANEUVERING CLEARANCE OF 18 INCHES LATCH SIDE OF THE
 DOOR PULL SIDE OF THE DOOR. SEE 2014 FBC-ACCESSIBILITY
 CODE 404.2.4 & TABLE 404.2.4.1 MANEUVERING CLEARANCE AT
 MANUAL SWINGING DOORS.
  
 1D) THE REFERRAL ROOM HAS AN OFFSET WALL THE LARGER
 DIMENSION THAT IS GIVEN IS 7 FOOT 3 INCHES. THE OFFSET
 IN THE WALL IS NOT GIVEN NOR THE DIMENSION OF THE
 SHORTER LENGTH WALL IN THE OPPOSITE WALL. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-7.0 DETAIL # 4 DOOR SIGNAGE. THE DETAIL
 INDICATES THE HEIGHT OF THE PICTOGRAM BUT NEGLECTS TO
 PROVIDE THE MAXIMUM HEIGHT OR POSITION FOR BRAILLE. SEE
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. TACTILE
 CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES (1220
 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE LOWEST TACTILE
 CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-01 Cont ID  
Sent By jleahy Date 2017-03-01 Time 16:07 Rev Time 0.00
Received By jleahy Date 2017-03-01 Time 16:04 Sent To  
Notes
2017-03-01 16:18:16LIGHTING POWER ALLOWANCE CALCULATION SHALL BE SUBMITTED
 TO THIS OFFICE PRIOR TO THE CEILING ROUGH. FBC EC
 405.2(1,2)
 SEE PAGE E0.1
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 CITY OF WEST PALM BEACH

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-21 Cont ID  
Sent By wjolin Date 2017-02-21 Time 11:29 Rev Time 0.00
Received By wjolin Date 2017-02-21 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-03-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-03-14 Time 13:45 Sent To  
Notes
2017-03-15 13:46:05RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-08 Cont ID  
Sent By gjohnson Date 2017-03-08 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-02-08 Time 14:11 Sent To  
Notes
2017-02-09 14:11:13B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-16 Cont ID  
Sent By jwitmer Date 2017-02-16 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2017-02-16 Time 07:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-16 Cont ID  
Sent By ccole Date 2017-03-16 Time 16:15 Rev Time 0.00
Received By ccole Date 2017-03-16 Time 16:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-10 Cont ID  
Sent By ccole Date 2017-02-10 Time 10:37 Rev Time 0.00
Received By ccole Date 2017-02-10 Time 10:37 Sent To  
Notes
2017-02-10 11:52:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020341
 2/10/17
  
 1) SHEET M2.1: PROVIDE THE FLEX DUCT SIZES ON THE PLAN
 OR RELOCATE THE FLEX SCHEDULE FROM SHEET M6.1.
  
 2) M2.1, KEY NOTE #2: PLEASE RELOCATE THE TWO ZONE
 DAMPERS IN THE EXAM AND ADULT RECEPTION ROOMS INTO THE
 ADJACENT TENANT SPACES THEY WILL BE SERVING IN ORDER TO
 PROVIDE ACCESS FOR SERVICE AND REPLACEMENT- SECTION
 306.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-03-08 Cont ID  
Sent By gjohnson Date 2017-03-08 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-03-08 Time 12:45 Sent To  
Notes
***NONE***