| 2017-02-09 11:28:02 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) & CITY |
| | AMENDMENTS TO THE 2015 FBC |
| | |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | PROJECT NAME: KEY WEST FISH & CHICKEN |
| | JOB ADDRESS: 1258 PALM BEACH LAKES BLVD. |
| | DESCRIPTION: CHANGE OUT OF FPE PANEL |
| | MASTER PERMIT: 17020335 |
| | |
| | |
| | PLANS FOR THE ABOVE MENTIONED PERMIT WERE REVIEWED FOR |
| | COMPLIANCE WITH THE CODES HEREIN DESCRIBED. FOLLOWING |
| | YOU WILL SEE NOTES ADDRESSING THE REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | YOUR RESUBMITTAL. |
| | |
| | 1. THIS RISER DIAGRAM AS PROVIDED IS CONFUSING. |
| | REFLECTED SERVICE INDICATES 4-300KCMLS CONDUCTORS AND |
| | THE FEEDER FOR PANEL ?A? INDICATES 4-3/0 & 1 #6 GEC, |
| | YET YOU SAY THE SERVICE IS 1 PHASE. CORRECT RISER |
| | ACCORDINGLY |
| | 2. PER NEC 230.7 SERVICE CONDUCTORS CAN?T SHARE RACEWAY |
| | WITH FEEDER CONDUCTORS. |
| | 3. PER NEC 110.16 ARC-FAULT HAZARD WARNING LABELS SHALL |
| | BE REQUIRED. |
| | 4. YOU SHALL PROVIDE LOAD CALCS FOR EACH PANEL AND |
| | SERVICE DISCONNECT TO ASCERTAIN PROPER CONDUCTOR |
| | SIZING. CONDUCTORS TO PANEL ?A? ARE ONLY GOOD FOR 160 |
| | AMP. SERVICE CONDUCTORS ARE ONLY GOOD FOR 228 AMP. |
| | 5. PER NEC 110.14(A) TERMINAL FOR MORE THAN ONE |
| | CONDUCTOR SHALL BE SO IDENTIFIED. ACCORDING TO THE |
| | SUBMITTED RISER DIAGRAM, DISCONNECT ?A? LOAD SIDE |
| | TERMINALS APPEAR TO HAVE MULTIPLE CONDUCTORS. |
| | 6. PER NEC 250.66 THE GROUNDING ELECTRODE CONDUCTOR FOR |
| | THIS SERVICE SHALL BE A MINIMUM OF #4 COPPER. THE |
| | PROVIDED RISER DIAGRAM INDICATES #10. CORRECT |
| | ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |