| 2017-02-08 17:34:10 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17020286 |
| | W. P. B. PERMIT: 16081292 |
| | ADD: 201 NARCISSUS ST. SUITE # 905/906 |
| | CONT: PHILIP E. JOHNSON, INC. |
| | TEL: 561-366-1034 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 08/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED SALES BROCHURE FOR SAM 90 IS JUST THAT |
| | A SALES BROCHURE. PLEASE NOTE THE CITY REQUIRES THE |
| | ACTUAL TEST. THE TECHNICAL DATA IN THE BROCHURE STATES |
| | THE IIC VALE OF 70 AND STC VALUE OF 67, THEY DO NOT |
| | STATE THE SLAB THICKNESS AND THE TEST WAS PREFORMED |
| | WITH A DROP CEILING FULL OF INSULATION. |
| | IF YOU ARE LOOKING FOR THE USE OF THIS PRODUCT THE CITY |
| | DOES HAVE INTERTEK TEST REPORTS, TESTED ON A 5 INCH |
| | CONCRETE SLAB, NO DROP CEILING WITH A STC OF 54 AND IIC |
| | OF 51 FOR SUPER SAM-125 UNDERLAYMENT BUT NO TEST RESULT |
| | FOR FLAME SPREAD AND SMOKE DEVELOPMENT. |
| | SEE THE ACTUAL REQUIREMENTS BELOW. |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |