Plan Review Details - Permit 17020277
Plan Review Stops For Permit 17020277
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-05 Cont ID  
Sent By jwitmer Date 2017-05-05 Time 17:01 Rev Time 0.00
Received By jwitmer Date 2017-05-05 Time 16:01 Sent To  
Notes
2017-05-05 16:45:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020277
 ADD: 3223 COMMERCE PL.
 CONT: TBD / ARCH. KUOPPALA, ROBERT
 TEL: 561-385-7106
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 NOTICE: NFIP REVIEW STOP (NATIONAL FLOOD INSURANCE
 PROGRAM) BUILDING IS A POST FIRM BUILT IN 1990, NOT A
 SUBSTANTIAL IMPROVEMENT, SEE ATTACHED SHEET RECORDS
 BACK 6 YEARS. J. WITMER PX 02/10/2017.
  
 2ND REVIEW
 DATE: FRI. MAY05/ 2017
 ACTION: BUILDING PROVISO
  
 1A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
  
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, CURBS
  
 1B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-10 Cont ID  
Sent By jwitmer Date 2017-02-10 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2017-02-10 Time 07:10 Sent To  
Notes
2017-02-10 13:31:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020277
 ADD: 3223 COMMERCE PL.
 CONT: TBD / ARCH. KUOPPALA, ROBERT
 TEL: 561-385-7106
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE: NFIP REVIEW STOP (NATIONAL FLOOD INSURANCE
 PROGRAM) BUILDING IS A POST FIRM BUILT IN 1990, NOT A
 SUBSTANTIAL IMPROVEMENT, SEE ATTACHED SHEET RECORDS
 BACK 6 YEARS. J. WITMER PX 02/10/2017.
 1ST REVIEW
 DATE: FRI. FEB. 10/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS (MICHAEL BASSFORD
 P. E.)
 EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 2) SHEET D-1 & LS1 INDICATES THIS IS A LEVEL II
 ALTERATION. PLEASE NOTE THE LAST KNOWN USE IS A
 BUSINESS OCCUPANCY. SHEET D-1 ALSO LIST IN NOTE 2 THE
 USE IS TO BE A CHURCH OR AN A-3 OCCUPANCY.
  
 SEE THE 2014 FBC-B 303.4. THE 2014 EXIST. BUILD. CODE
 SECTION 1001.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 3) THE LIFE SAFETY SHEET INDICATES THE OCCUPANT LOAD OF
 THE SANCTUARY AT 641 OCCUPANTS, AND A OVERALL OCCUPANT
 LOAD OF 974 OCCUPANTS FOR THE BUILDING. WITH ASSEMBLY
 OCCUPANT LOADS OF 300 OR MORE THE BUILDING RISK
 CATEGORY INCREASES. THE 2014 FBC-B SECTION 1007.2 SNOW
 AND WIND LOADS. BUILDINGS AND STRUCTURES SUBJECT TO A
 CHANGE OF OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF
 OCCUPANCY RESULTS IN HIGHER WIND OR SNOW RISK
 CATEGORIES BASED ON THE FLORIDA BUILDING CODE, BUILDING
 TABLE 1604.5. RISK CATEGORY III BUILDINGS- BUILDINGS
 AND OTHER STRUCTURES WHOSE PRIMARY OCCUPANCY IS PUBLIC
 ASSEMBLY WITH AN OCCUPANT LOAD GREATER THAN 300.
 PLEASE REVIEW THE WIND SPEED CHART FOR CATEGORY III
 BUILDINGS AND OTHER STRUCTURES, THE WIND ZONE IS 180
 MPH (3 SECOND GUST) VULT. BUILDINGS SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND OR SNOW LOAD
 PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4) SHEET A-3 PROVIDES COMPONENTS AND CLADDING BUT DOES
 NOT PROVIDE THE DESIGN WIND CRITERIA, AND WITH THE
 BUILDING RISK FACTOR INCREASING, THE WIND SPEED TO 180
 VULT SO WILL THE PRESSURES INCREASE. PLEASE ALSO
 PROVIDE THE MEAN ROOF HEIGHT FOR THE STRUCTURE.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, CURBS
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By jleahy Date 2017-05-11 Time 13:06 Rev Time 0.00
Received By jleahy Date 2017-05-11 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By vperez Date 2017-02-17 Time 10:05 Rev Time 0.00
Received By vperez Date 2017-02-17 Time 10:05 Sent To  
Notes
2017-02-17 10:06:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS. A NOTE
 WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS
 MODIFICATIONS; SEE VERBIAGE IN CODE.
 4. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15
 AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW
 COMPLIANCE ACCORDINGLY.
 5. SHOW ACTUAL CALCULATION AND COMPLIANCE WITH FBC
 ENERGY CONSERVATION LIGHTING DENSITIES PER CODE
 SECTION. C405
 6. LABEL ALL KITCHEN AREA RECEPTACLES WITHIN 6FT OF
 SINKS TO BE GFCI PROTECTED NEC 210.8B
 7. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL
 COMMENTS RELATED TO ELECTRICAL.
 8. DESIGNER OF RECORD TO SIGN AND SEAL ELECTRICAL
 DRAWINGS SUBMITTED FOR REVIEW.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-26 Cont ID  
Sent By pleduc Date 2017-04-26 Time   Rev Time 0.00
Received By pleduc Date 2017-04-26 Time 11:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By pleduc Date 2017-02-23 Time   Rev Time 0.00
Received By pleduc Date 2017-02-23 Time 12:43 Sent To  
Notes
2017-02-23 13:43:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE PROPOSED OCCUPANCY USE IS A CHANGE OF OCCUPANCY
 AND APPEARS TO BE ASSEMBLY. HOWEVER, THERE ARE SEVERAL
 OCCUPANCIES IN THIS PROJECT, ASSEMBLY, BUSINESS,
 EDUCATION,
  
 PER NFPA 101
  
 12.1.2* CLASSIFICATION OF OCCUPANCY. SEE 6.1.2.
 12.1.3 MULTIPLE OCCUPANCIES.
 12.1.3.1 GENERAL. MULTIPLE OCCUPANCIES SHALL BE IN
 ACCORDANCE WITH 6.1.14.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE
 RESISTANCE?RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
  
 PLEASE PROVIDE THE SPECIFIC OCCPANY AND ENSURE ALL THE
 REQUIRMENTS OF THEAT OCCUPANCY ARE ADDRESSED.
  
  
  
 2) SHEET A 4 - THERE ARE INDICATIONS OF WARMING OVENS
 IN THE KITCHEN.
  
 PER NFPA 101
  
 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 FOR VERIFICATION PURPOSES, PLEASE PROVIDE THE
 MANUFACTURES SPECIFICATION SHEETS FOR EACH OF THE
 WARMING OVENS.
  
  
  
  
 3) SHEET A 3 - THE DOOR SCHEDULE INDCATES EXIT DEVICE
 KEY ENTRY
  
 PER NFPA 101
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 12.2.2.2.6. 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH
 7.2.1.5.5 SHALL BE PERMITTED TO BE USED ON A SINGLE
 DOOR OR A SINGLE PAIR OF DOORS IF BOTH OF THE FOLLOWING
 CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY OCCUPANCY HAS AN OCCUPANT LOAD NOT
 GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 PLEASE PROVIDE FOR THE NOTED REQUIREMENTS ON ALL
 APPLICABLE EXIT DOORS.
  
  
  
 4) SHEET FP 1 - THE DESIGN OF THE FIRE SPRINKLER SYSTEM
 DOES NOT MEET THE REQUIRMENTS OF THE CODE
  
 FLORIDA BUILDING CODE
  
 105.3.1.2 NO PERMIT MAY BE ISSUED FOR ANY BUILDING
 CONSTRUCTION, ERECTION, ALTERATION, MODIFICATION,
 REPAIR, OR ADDITION UNLESS THE APPLICANT FOR SUCH
 PERMIT PROVIDES TO THE ENFORCING AGENCY WHICH ISSUES
 THE PERMIT ANY OF THE FOLLOWING DOCUMENTS WHICH APPLY
 TO THE CONSTRUCTION FOR WHICH THE PERMIT IS TO BE
 ISSUED AND WHICH SHALL BE PREPARED BY OR UNDER THE
 DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471,
 FLORIDA STATUTES:
  
 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR
 ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH
 CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS
 AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN
 A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS,
 NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 FAC
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION EITHER IN
 PLAN DRAWINGS OR NARRATIVE FORM SIGNED AND SEALED BY A
 QUALIFIED EOR.
  
  
  
  
 5) SHEET A 3 - THERE IS EXITING THROUGH A CLASSROOM B
 AT DOOR 27 THROUGH OFFICE 2, DOOR 53. THERE ARE
 LOCKSETS INDICATED FOR THESE DOORS.
  
 PER NFPA 101
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, 19, 22, OR
 23.
  
 THIS IS NOT ALLOWED WITHIN CHAPTER 12 NEW ASSEMBLY
 OCCUPANCIES.
  
 PLEASE PROVIDE DOOR KNOBS/HANDLES COMPLYING WITH THIS
 CODE.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-19 Time 14:31 Sent To  
Notes
2017-05-22 14:31:18RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-19 Cont ID  
Sent By lmarchan Date 2017-05-19 Time 08:10 Rev Time 0.00
Received By lmarchan Date 2017-04-21 Time 15:09 Sent To  
Notes
2017-04-24 15:09:08C15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-21 Cont ID  
Sent By lmarchan Date 2017-03-21 Time 09:44 Rev Time 0.00
Received By lmarchan Date 2017-02-07 Time 13:50 Sent To  
Notes
2017-02-08 13:50:20C15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-05-05 Cont ID  
Sent By jwitmer Date 2017-05-05 Time 16:34 Rev Time 0.00
Received By jwitmer Date 2017-05-05 Time 16:31 Sent To  
Notes
2017-05-05 16:34:44PALM BEACH COUNTY IMPACT FEE OFFICE
 CHANGE OF OCCUPANCY: A3/ CHURCH
 DATE: 04/ 21/17
 MU2017-10918
 FEES: $ 00.00 NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-02-10 Cont ID  
Sent By jwitmer Date 2017-02-10 Time 13:32 Rev Time 0.00
Received By jwitmer Date 2017-02-10 Time 07:11 Sent To  
Notes
2017-02-10 13:32:07BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-23 Cont ID  
Sent By ccole Date 2017-05-23 Time 11:51 Rev Time 0.00
Received By ccole Date 2017-05-22 Time 16:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-04-27 Cont ID  
Sent By ccole Date 2017-04-27 Time 11:01 Rev Time 0.00
Received By ccole Date 2017-04-27 Time 11:01 Sent To  
Notes
2017-04-27 13:47:342ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020277
 4/27/17
  
 1) M-4: THE O/A CALCULATIONS FOR THE FELLOWSHIP AREA-
 AHU'S- 8A & 8B INDICATE DEMAND CONTROLLED VENTILATION
 IS REQUIRED- SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) M-4: THE O/A CALCULATIONS FOR THE CHOIR/PLATFORM ARE
 NOT IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES AN
 O/A RATE BASED ON 70 PERSONS PER 1000 SF.
  
 3) PROVIDE MAKE-UP AIR FOR EF-1 IN THE WARMING KITCHEN-
 SECTION 508.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By ccole Date 2017-02-09 Time 14:33 Rev Time 0.00
Received By ccole Date 2017-02-09 Time 10:56 Sent To  
Notes
2017-02-09 14:34:001ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17020277
 2/9/17
  
 1) THE PROPOSED PROJECT SHALL BE CLASSIFIED AS A CHANGE
 OF OCCUPANCY PER SECTION 506 FBC-14 EXISTING BUILDING.
 PLEASE CORRECT THE APPLICATION AND THE LEVEL 2
 ALTERATION CLASSIFICATION SHOWN ON SHEET LS-1. THE CITY
 OF WEST PALM BEACH BUSINESS LICENSING RECORDS SHOW NO
 LICENSURE FOR THE CHURCH, AND THE PALM BEACH COUNTY
 PROPERTY APPRAISER?S REPORT IDENTIFIES THE USE AS
 OFFICE
  
 2) REFER TO SECTION C101.4.4 AND C401.2 FBC-14 ENERGY
 CONSERVATION CODE, AND SUBMIT DOCUMENTATION OF
 COMPLIANCE.
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS- SECTION C403.2.1
  
 4) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL
 LIGHTING SYSTEMS IS REQUIRED PER SECTION C408.1 AND
 C408.2. PLEASE PROVIDE A PLAN IN ACCORDANCE WITH
 SECTION C408.2.1 AND REVIEW ALL COMPLIANCES AS
 INDICATED IN THE SUB-SECTIONS OF C408.2. PLEASE NOTE
 THAT PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION,
 THE REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING WHICH
 INCLUDES A FINAL REPORT.
  
 5) REFER TO SECTIONS 809.1 & 809.2 AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3 FBC-14 EXISTING BUILDING CODE. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF O/A AIR FOR OCCUPANTS. A) PLEASE NOTE THAT DEMAND
 CONTROLLED VENTILATION MAY BE REQUIRED PER SECTION
 C403.2.5.1.
  
 6) SHEET M-1: PROVIDE A KEYNOTE TO IDENTIFY THE 14X14
 EXHAUST DUCT FROM ERV-1.
  
 7) M-1: THE PLAN INDICATES 450 CFMS OF AIR BEING
 RETURNED FROM HALL A, HOWEVER THERE APPEARS TO BE NO
 AIR SUPPLIED TO HALL A- PLEASE CLARIFY.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DOUBLE
 WALL AND CONVECTION OVENS.
  
 9) IN ORDER TO EXPEDITE THE SECOND REVIEW, PROVIDE A
 RESPONSE NARRATIVE FOR THE DESIGN PROFESSIONAL OF
 RECORD ADDRESSING EACH COMMENT. DUE TO THE LACK OF
 INFORMATION THE MECHANICAL REVIEW IS STOPPED AT THIS
 TIME. PLEASE NOTE ADDITIONAL COMMENTS MAY OCCUR UPON
 REVIEW OF THE CALCULATIONS AND THE RESUBMITTED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2017-02-10 Cont ID  
Sent By jwitmer Date 2017-02-10 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2017-02-10 Time 07:15 Sent To  
Notes
2017-02-10 09:11:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020277
 ADD: 3223 COMMERCE PL.
 CONT: TBD / ARCH. KUOPPALA, ROBERT
 TEL: 561-385-7106
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 10/ 2017
 ACTION: APPROVED.
  
 NOTE: NFIP REVIEW STOP (NATIONAL FLOOD INSURANCE
 PROGRAM) BUILDING IS A POST FIRM BUILT IN 1990, NOT A
 SUBSTANTIAL IMPROVEMENT, SEE ATTACHED SHEET RECORDS
 BACK 6 YEARS. W. P. B. MUNI CODE ORD. NO. 4658-16
 SECTION 94-546 (3) 5 YEAR PERIOD.
 FIRM PANEL 145 OF 245
 COMMUNITY PANEL NUMBER120192-0145 B- ANNEXED INTO THE
 CITY OF W. P. B.
 MAP REVISED: OCT. 15, 1982.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-04 Cont ID  
Sent By gjohnson Date 2017-05-04 Time 13:18 Rev Time 0.00
Received By gjohnson Date 2017-05-04 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By gjohnson Date 2017-02-17 Time 13:50 Rev Time 0.00
Received By gjohnson Date 2017-02-17 Time 12:11 Sent To  
Notes
2017-02-17 14:02:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. A GREASE INTERCEPTOR WILL BE REQUIRED FOR THE 3 COMP
 SINK, S1 AND THE DISHWASHERS. PER FBC PL 1003.1 +
 1003.3.1
  
 2. THE GARBAGE DISPOSALS SHALL COMPLY WITH FBC PL
 1003.3.2 FOOD WASTE GRINDERS.
 WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER.
  
 3. THE REVENT ON S1 IS NOT ALLOWED IT SHALL COMPLY WITH
 FBC PL 904.3 VENT TERMINATION.
 VENT STACKS OR STACK VENTS SHALL TERMINATE OUTDOORS TO
 THE OPEN AIR OR TO A STACK-TYPE AIR ADMITTANCE VALVE IN
 ACCORDANCE WITH SECTION 918.
  
 4. THE DISHWASHER CAN NOT CONNECT SEPARATELY TO
 DRAINAGE SYSTEM THEY SHALL COMPLY WITH. FBC PL 802.1.6
 DOMESTIC DISHWASHING MACHINES.
 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2, OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. THE WASTE LINE OF A
 DOMESTIC DISHWASHING MACHINE DISCHARGING INTO A KITCHEN
 SINK TAILPIECE OR FOOD WASTE GRINDER SHALL CONNECT TO A
 DECK-MOUNTED AIR GAP OR THE WASTE LINE SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER.
  
 802.1.7 COMMERCIAL DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
  
 5. A BACK FLOW DEVISE IS REQUIRED ON THE WATER SUPPLY
 FOR THE ICE MAKER. PER FBC PL 608.3
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-05-15 Time   Rev Time 0.00
Received By pgreilic Date 2017-05-15 Time 15:18 Sent To  
Notes
2017-05-15 15:26:21PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-02 Cont ID  
Sent By pgrehic Date 2017-03-02 Time   Rev Time 0.00
Received By pgreilic Date 2017-03-02 Time 15:26 Sent To  
Notes
2017-03-02 11:02:38PAUL GREILICH, SENIOR PLANNER
 [email protected]
 561-822-1443