Plan Review Details - Permit 17020177
Plan Review Stops For Permit 17020177
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-04-11 Cont ID  
Sent By mgonzale Date 2017-04-11 Time   Rev Time 1.00
Received By mgonzale Date 2017-04-11 Time   Sent To I
Notes
2017-04-11 13:26:27PROVISO: USE LEAD FREE DCDA'S
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 M GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-03-22 Cont ID  
Sent By ccole Date 2017-03-22 Time   Rev Time 1.00
Received By mgonzale Date 2017-03-22 Time   Sent To ENG
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By pleduc Date 2017-03-27 Time   Rev Time 0.00
Received By pleduc Date 2017-03-23 Time 14:16 Sent To M
Notes
2017-03-27 10:24:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ANY TEMPORAY FIRE PUMP AND/OR FIRE EQUIPMENT SYSTEM
 FOR PHASING PURPOSES SHALL BE SUBMITTED AND TESTED
 UNDER SEPARATE PERMIT SUBMITTAL.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By pleduc Date 2017-02-22 Time   Rev Time 0.00
Received By pleduc Date 2017-02-22 Time 12:14 Sent To M
Notes
2017-02-22 12:43:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) GENERAL COMMENT: HOW WILL THE WATER SUPPLY BE
 CONTROLLED DURING THE PHASING PLAN AND TCO AREAS? I.E.
 THE PARKING STRUCTURE WANTS TO BE TCO FOR FLOORS 1-6,
 HOW WILL THE WATER SUPPLY BE INSURED/CONTROLLED TO
 REMAIN ACTIVE, AS WELL AS, BEING AVAILABLE FOR FD USE
 ON ALL OTHER ARES DURING CONSTRUCTION? HOIW WILL FDC'S
 BE ASSIGNED, ETC.
  
 PLEASE PROVIDE A SPECIFIC DETAILED PLAN IN NARRATIVE
 AND/OR DRAWING FORM.
  
  
  
 2) SHEET FP 1.1 AND ALL OTHER RELATED PLAN SHEETS - THE
 SPRINKLER COUNT LEGEND INDICATES A FEW INCORRECT
 REFERENCES. A FEW DESCRIPTIONS DO NOT APPEAR TO MATCH
 THE PICTURE DIAGRAM.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) FP SHEETS & FP 17 - PRV'S ARE INDICATED; HOWEVER,
 THE SIZE AND/OR THE AMOUNT OF PRESSURE IS NOT.
  
 PLEASE PROVIDE THE SIZE AND/OR AMOUNT OF THE PRV FOR
 EACH AREA AND EACH FLOOR.
  
  
  
  
 4) FP SHEETS - SOME OF THE RESEDENTIAL UNITS APPEAR TO
 HAVE SOFFITS AND OR OTHER POTENTIAL OBSTRUCTION, I.E.
 CEILING FANS, LIGHT FIXTURES, ETC. WEHN SIDEWALL
 SPRINKLERS ARE INDICATED. RESIDENTIAL SIDEWALL
 SPRINKLERS ARE DESIGNED FOR FLAT CEILINGS.
  
 PLEASE PROVIDE A NOTE ENSURING COMPLIANCE WITH THE
 OBSTRUCTION REQUIRMENTS.
  
  
  
 5) FP SHEETS 13-24 -WITHIN THE SOUTH/CENTER UNITS IT
 APPEARS THAT A SIDEWALL SPRINKLER IS INDICATED IN A
 SMALL RECTANGLAR AREA NEXT TO CORRIDOR. IT DOES NOT
 APPEAR THAT A SIDEWALL SPRINKLER WILL WORK IN THIS
 AREA.
  
 PLEASE CONFIRM WHAT THIS AREA IS AND THAT A SIDEWALL
 SPRINKLER MEETS THE PROTECTION REQUIREMENTS.
  
  
  
  
 6) SHEET FP 13 - CONTAINED WITHIN THE AREA 1 LEVEL 24
 CALCULATION BOX 4 HEADS ARE INDICATED; HOWEVER, ONLY 2
 HEADS APPEAR TO BE CONTAINED WITHIN THE FLOOR AREA
 STRIPING.
  
 PLEASE REVIEW AND PROVIDE CLARITY, EXPLANATION OR
 CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-14 Cont ID  
Sent By hmoser Date 2017-04-14 Time 14:58 Rev Time 0.00
Received By hmoser Date 2017-04-11 Time 15:59 Sent To  
Notes
2017-04-12 15:59:51RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-12 Cont ID  
Sent By lmarchan Date 2017-04-12 Time 15:58 Rev Time 0.00
Received By lmarchan Date 2017-03-22 Time 12:50 Sent To  
Notes
2017-03-23 12:50:17RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By lmarchan Date 2017-03-23 Time 12:49 Rev Time 0.00
Received By lmarchan Date 2017-02-06 Time 14:09 Sent To  
Notes
2017-02-07 14:09:34ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-04-14 Cont ID  
Sent By hmoser Date 2017-04-14 Time 14:57 Rev Time 0.00
Received By hmoser Date 2017-04-14 Time 14:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-04-05 Cont ID  
Sent By hmoser Date 2017-04-05 Time 14:54 Rev Time 0.00
Received By hmoser Date 2017-04-05 Time 14:31 Sent To ENG
Notes
2017-04-05 14:54:46PLAN DENIED
 1) CAN'T FIND PRODUCT DATA SHEET FOR BACKFLOW
 PREVENTER, AS REQUESTED FROM LAST REVIEW.
 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION
 DRAWIMGS, SPECIFICATIONS, AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 PLAN REVIEW BY HAROLD MOSER.
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-24 Cont ID  
Sent By ccole Date 2017-02-24 Time 11:39 Rev Time 0.00
Received By ccole Date 2017-02-24 Time 11:38 Sent To ENG
Notes
2017-02-24 11:41:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020177
 2/24/17
  
 1) COMPLY WITH FIRE REVIEWER'S COMMENTS.
  
 2) PLEASE PROVIDE A PRODUCT DATA SHEET FOR THE BACKFLOW
 PREVENTER, AND ADD IO TO THE SUBMITTAL PACKAGE. IT MAY
 BE HELPFUL TO PROVIDE AN INDEX FOR THE SUBMITTAL
 PACKAGE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  