| 2017-02-22 12:43:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) GENERAL COMMENT: HOW WILL THE WATER SUPPLY BE |
| | CONTROLLED DURING THE PHASING PLAN AND TCO AREAS? I.E. |
| | THE PARKING STRUCTURE WANTS TO BE TCO FOR FLOORS 1-6, |
| | HOW WILL THE WATER SUPPLY BE INSURED/CONTROLLED TO |
| | REMAIN ACTIVE, AS WELL AS, BEING AVAILABLE FOR FD USE |
| | ON ALL OTHER ARES DURING CONSTRUCTION? HOIW WILL FDC'S |
| | BE ASSIGNED, ETC. |
| | |
| | PLEASE PROVIDE A SPECIFIC DETAILED PLAN IN NARRATIVE |
| | AND/OR DRAWING FORM. |
| | |
| | |
| | |
| | 2) SHEET FP 1.1 AND ALL OTHER RELATED PLAN SHEETS - THE |
| | SPRINKLER COUNT LEGEND INDICATES A FEW INCORRECT |
| | REFERENCES. A FEW DESCRIPTIONS DO NOT APPEAR TO MATCH |
| | THE PICTURE DIAGRAM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) FP SHEETS & FP 17 - PRV'S ARE INDICATED; HOWEVER, |
| | THE SIZE AND/OR THE AMOUNT OF PRESSURE IS NOT. |
| | |
| | PLEASE PROVIDE THE SIZE AND/OR AMOUNT OF THE PRV FOR |
| | EACH AREA AND EACH FLOOR. |
| | |
| | |
| | |
| | |
| | 4) FP SHEETS - SOME OF THE RESEDENTIAL UNITS APPEAR TO |
| | HAVE SOFFITS AND OR OTHER POTENTIAL OBSTRUCTION, I.E. |
| | CEILING FANS, LIGHT FIXTURES, ETC. WEHN SIDEWALL |
| | SPRINKLERS ARE INDICATED. RESIDENTIAL SIDEWALL |
| | SPRINKLERS ARE DESIGNED FOR FLAT CEILINGS. |
| | |
| | PLEASE PROVIDE A NOTE ENSURING COMPLIANCE WITH THE |
| | OBSTRUCTION REQUIRMENTS. |
| | |
| | |
| | |
| | 5) FP SHEETS 13-24 -WITHIN THE SOUTH/CENTER UNITS IT |
| | APPEARS THAT A SIDEWALL SPRINKLER IS INDICATED IN A |
| | SMALL RECTANGLAR AREA NEXT TO CORRIDOR. IT DOES NOT |
| | APPEAR THAT A SIDEWALL SPRINKLER WILL WORK IN THIS |
| | AREA. |
| | |
| | PLEASE CONFIRM WHAT THIS AREA IS AND THAT A SIDEWALL |
| | SPRINKLER MEETS THE PROTECTION REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 6) SHEET FP 13 - CONTAINED WITHIN THE AREA 1 LEVEL 24 |
| | CALCULATION BOX 4 HEADS ARE INDICATED; HOWEVER, ONLY 2 |
| | HEADS APPEAR TO BE CONTAINED WITHIN THE FLOOR AREA |
| | STRIPING. |
| | |
| | PLEASE REVIEW AND PROVIDE CLARITY, EXPLANATION OR |
| | CORRECT. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |