| 2017-03-13 15:40:40 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE |
| | REQUIRED DURING CONSTRUCTION. |
| | |
| | 1- ACCORDING TO THE FLOOD INSURANCE RATE MAP (FIRM) |
| | COMMUNITY-PANEL NUMBER 120229 0020 B EFFECTIVE MARCH 1, |
| | 1979 THE PROPOSED ADDITION WILL PLACE THE HOUSE IN |
| | FLOOD ZONE A5. THE ADDITION AND THE EXISTING HOUSE NEED |
| | TO COMPLY WITH THE REQUIREMENTS OF SEC. 1103.5 |
| | FBC-EXISTING BUILDING, 5TH EDITION (2014). SHOW |
| | COMPLIANCE WITH SEC. R322 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). COORDINATE WITH ITEM #2 BELOW. NOTE: ANY SPACE |
| | BELOW THE 7'-6" FINISH FLOOR ELEVATION NEEDS TO COMPLY |
| | WITH THE FLOOD RESISTANT CONSTRUCTION OF SEC. R322 |
| | FBC-RESIDENTIAL, INCLUDING FLOOD VENTS. |
| | |
| | 2- PROVIDE SURVEY (2 COPIES) SHOWING THE EXISTING HOUSE |
| | FINISH FLOOR ELEVATION AND THE PROPOSED ADDITION |
| | FINISHED FLOOR ELEVATION AS REQUIRED BY SEC. |
| | 107.3.5.3(8) CITY AMENDMENTS. |
| | |
| | 3- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY |
| | SEC. R401.4 FBC-RESIDENTIAL. |
| | |
| | 4- SPECIFY SIZE OF NEW ATTIC ACCESS SHOWN IN THE NEW |
| | MATER BEDROOM AREA. SEC. R807 FBC-RESIDENTIAL. |
| | |
| | 5- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10' OF EACH |
| | BEDROOM, INCLUDING THE EXISTING BEDROOMS AS REQUIRED BY |
| | SEC. R315 FBC-RESIDENTIAL. |
| | |
| | 6- CLARIFY WHY SUBMITING FLORIDA PRODUCT APPROVAL |
| | FL17176-R0 FOR SLIDING GLASS DOORS?. THERE ARE NO |
| | SLIDING GLASS DOORS SHOWN ON PLANS. IN ADDITION, THIS |
| | FLORIDA PRODUCT APPROVAL IS FOR THE 2010 FBC CODE |
| | VERSION. CURRENT CODE VERSION IS THE 2014 FBC. CLARIFY |
| | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 7- ARCHITECT OF RECORD TO SPECIFY ROOF TILE FASTENING |
| | AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SIZE AN NUMBER OF |
| | SCREWS. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL |
| | IS REQUIRED. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF |
| | RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| | ADHESIVES. |
| | |
| | B) MULLIONS AS SHOWN ON PLANS FOR DOORS AND WINDOWS. |
| | NOTE: SPECIFY MULLION SIZE AND FASTENERS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | C) FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | FRAMING PLANS, WALL DETAILS AND TRUSS ANCHOR SCHEDULE. |
| | . PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING |
| | THE SPECIFIED CONNECTOR OR ARCHITECT TO LIST ALL THE |
| | FLORIDA PRODUCT APPROVAL NUMBERS NEXT TO EACH SPECIFIED |
| | CONNECTOR. NOTE: FLORIDA PRODUCT APPROVAL FL474 |
| | SPECIFIED ON THE TRUSS ANCHOR SCHEDULE NEEDS TO BE |
| | UPDATED. NEED THE CURRENT 2014 FBC APPROVAL. |
| | |
| | 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. NOTE: PLEASE PLACE REVIEW STAMP ON THE |
| | FRONT PAGE OF THE PRODUCT APPROVALS NOT ON THE BACK. |
| | THIS IS FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS |
| | RETENTION PURPOSES. |
| | |
| | 10- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE FOAM |
| | INSULATION SPECIFIED ON PLANS SHOWING COMPLIANCE WITH |
| | SEC. R316 FBC-RESIDENTIAL. |
| | |
| | 11- ENERGY CALCULATIONS SUBMITTED. NOTE: THIS IS A |
| | CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE |
| | NOT REQUIRED, BUT IF CONTRACTOR WANTS TO SUBMITT THEM, |
| | THEN REVISE AS REQUIRED: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION |
| | SHOWN ON PAGE 3 OF 4 TO MATCH PLANS SUBMITTED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| | WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE |
| | THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |