Plan Review Details - Permit 17020064
Plan Review Stops For Permit 17020064
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-28 Cont ID  
Sent By tklarge Date 2017-02-28 Time 09:22 Rev Time 0.00
Received By tklarge Date 2017-02-21 Time 16:41 Sent To  
Notes
2017-02-21 16:41:20RESUB ROUTED TO PLUMBING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 06:33 Rev Time 0.00
Received By tklarge Date 2017-02-02 Time 14:55 Sent To  
Notes
2017-02-02 14:55:21PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By tklarge Date 2017-02-28 Time 09:22 Rev Time 0.00
Received By tklarge Date 2017-02-28 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 06:33 Rev Time 0.00
Received By tklarge Date 2017-02-06 Time 06:14 Sent To  
Notes
2017-02-06 06:33:431) THE PLUMBING DRAWING IS DONE IN PENCIL WHICH IS
 UNACCEPTABLE. SUBMIT A SANITARY AND WATER RISER FOR THE
 PLUMBING WORK TO BE DONE. WPB AMEND. TO FBC
 SEC.107.3.5.3.
 2) SHOW ALL PIPE SIZES ON THE REQUIRED WATER AND
 SANITARRY RISERS.WPB AMEND. TO FBC SEC.107.2.1.
 3) SHOW THE FIXTURE CLEARANCES OF EACH PLUMBING FIXTURE
 ON THE PLAN. 2014 FBC-RES. SEC. P2705.
 4) SHOW THE SHOWER DIMENSIONS ON THE PLAN. COMPLY WITH
 2014 FBC SEC.P2708.
 5) PROVIDE DETAILS AS TO HOW HOT WATER IS BEING
 SUPPLIED TO THIS ADDITION.
 6) THIS SUBMITTAL SHALL BE SUBMITTED AS A COMPLETE
 PACKAGE INCLUDING ELECTRICA PLANS AND APPLICATION,
 MECHANICAL ( IF APPLICABLE) AND BUILDING PLANS AND
 APPLICATION.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  