Plan Review Details - Permit 17011234
Plan Review Stops For Permit 17011234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-10 Cont ID  
Sent By jwitmer Date 2017-02-10 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2017-02-10 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-03 Cont ID  
Sent By jwitmer Date 2017-02-03 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2017-02-03 Time 11:53 Sent To  
Notes
2017-02-03 14:07:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011234
 ADD: 2508 N AUSTRALIAN AVE. SUITE # ?????
 CONT: JERRET CONSTRUCTION VERSES WINDOW MASTERS OF S.
 FLORIDA
 TEL: 954-520-8095
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 03/2017
 ACTION: DENIED
  
 1) THE QUALIFIER JERROLD GROSS IS REGISTERED UNDER
 WINDOW MASTERS OF S. FLORIDA IN THE CITY OF WEST PALM
 BEACH. YOU WILL NEED TO REGISTER THE COMPANY JERRET
 CONSTRUCTION CO. INC. AS WELL. A HOLD WILL BE PUT ON
 THIS PERMIT NO TO ISSUE UNTIL A NEW REGISTRATION
 OCCURS.
  
 2) THE PLANS DO NOT INDICATE IF THIS IS A SINGLE TENANT
 OR MULTIPLE TENANTS. THE PLANS ONLY SHOW WHERE WORK IS
 OCCURRING IN THE WEST ? OF THE BUILDING. SHEET AB.1
 DOES SHOW WORK IN THE SHARED CORRIDOR IF THIS IS
 MULTIPLE TENANTS WITHIN THE BUILDING .
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 WITH THE TOTAL SQ. FT. OF THE BUILDING BEING 5,000 SQ.
 FT. THE OCCUPANT LOAD WOULD BE 50 FOR THE TOTAL
 BUILDING, EVEN IF THERE IS ONLY ONE TENANT.
 IN THE 2014 FBC-B TABLE 1018.1 WILL REQUIRE A 1 HOUR
 FIRE RATED CORRIDOR (BUILDING NOT FIRE SPRINKLERED)
 WHEN THE OCCUPANT LOAD IS MORE THAN 30 WITH OPENING
 PROTECTIVES PER FBC-B TABLE 716.5 DOORS ARE REQUIRED TO
 BE 20 MINUTE.
  
 3) SHEET LS.1 THE FORMULA FOR EXITING OUT BOTH EXIT A
 &B 34?/0.2= 170 OCCUPANTS NOT 167. 2014 FBC-B 1005.3.2.
  
 4) THE LIFE SAFETY PLAN NOR SHEET A1 SHOW COMPLIANCE
 WITH 2014 FBC-B 906.1 PORTABLE FIRE EXTINGUISHERS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-14 Cont ID  
Sent By vperez Date 2017-02-14 Time 10:56 Rev Time 0.00
Received By vperez Date 2017-02-14 Time 10:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 09:37 Rev Time 0.00
Received By albarran Date 2017-02-06 Time 08:35 Sent To I
Notes
2017-02-06 09:37:56ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 2508 N. AUSTRALIAN AVE.
 DESCRIPTION: INTERIOR BUILDING OF OFFICES
 MASTER PERMIT: 17011234
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE
 TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING
 TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION.
 PPROVIDE A FIXTURE SCHEDULES TO INDICATE COMPLIANCE.
 2. FBC EC405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS
 SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT
 PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE
 INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30
 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL
 EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50
 PERCENT POWER.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-02 Cont ID  
Sent By pleduc Date 2017-02-02 Time   Rev Time 0.00
Received By pleduc Date 2017-02-02 Time 12:07 Sent To  
Notes
2017-02-02 14:17:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FIRE ALARM SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE FIRE ALARM, EXCEEDS 4 HOURS,
 A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2017-02-17 Cont ID  
Sent By skennedy Date 2017-02-17 Time 14:49 Rev Time 0.00
Received By skennedy Date 2017-02-08 Time 16:23 Sent To  
Notes
2017-02-08 16:23:31B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 10:01 Rev Time 0.00
Received By albarran Date 2017-01-31 Time 10:32 Sent To I
Notes
2017-02-06 10:06:582/6/17 SPOKE TO DONNY OVER THE PHONE TO LET HIM KNOW
 THAT ALL REVIEWS WERE COMPLETE AND PLANS ARE READY FOR
 CORRECTIONS. FILE SENT TO SMALL DENIED "J". MA
  
2017-02-01 10:32:17B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-03 Cont ID  
Sent By jwitmer Date 2017-02-03 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2017-02-03 Time 11:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-02-17 Cont ID  
Sent By ccole Date 2017-02-17 Time 09:18 Rev Time 0.00
Received By ccole Date 2017-02-17 Time 09:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-09 Cont ID  
Sent By ccole Date 2017-02-09 Time 09:52 Rev Time 0.00
Received By ccole Date 2017-02-09 Time 09:52 Sent To  
Notes
2017-02-09 10:20:552ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17011234
 2/9/17
  
 1) DUCT SMOKE DETECTORS, FIRE DAMPERS, AND A FIRE RATED
 CEILING ARE CALLED OUT IN THE DESIGN TABLE ON SHEET
 M.2. PLEASE SHOW THEIR LOCATIONS WITH SYMBOLS ON SHEET
 M.1 OR REVISE THE TABLE TO MATCH THE PLANS.
  
 2) THE 4X12 RETURN DUCTS RETURNING 200 CFMS OF AIR ARE
 UNDERSIZED BASED ON A FRICTION RATE OF 0.094. PLEASE
 INCREASE THE SIZE OF THE DUCTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-03 Cont ID  
Sent By ccole Date 2017-02-03 Time 07:56 Rev Time 0.00
Received By ccole Date 2017-02-03 Time 07:47 Sent To  
Notes
2017-02-03 08:06:411ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17011234
 2/3/17
  
 1) SHEET M.1: SOME OF THE PRINT ON THE PLANS NEEDS TO
 BE BOLDER FOR REVIEW AND FOR SCANNING TO PUBLIC
 RECORDS- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
 PLEASE PROVIDE BOLDER PRINT FOR THE DUCT SIZES,
 DIFFUSER AND GRILL SIZES, AND CFM CAPACITIES.
  
 2) M.1: PROVIDE THE SUPPLY DUCT SIZES AT OFFICES 104 &
 107.
  
 3) INDICATE THE TYPE OF DUCT INSULATION TO BE INSTALLED
 AND R-VALUE.
  
 4) THE PROJECT HAS BEEN CLASSIFIED AS A LEVEL 2
 ALTERATION. REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 5) SHOW THE O/A DUCTS SUPPLYING THE TWO AHU'S AND
 INDICATE COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION- AUTOMATIC DAMPERS FOR O/A
 SHUTDOWN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  