Plan Review Details - Permit 17011176
| Plan Review Stops For Permit 17011176 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2017-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-06-08 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-06-08 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2017-06-08 11:43:24 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) | | | ADD: 1620 N. CONGRESS AVE. | | | CONT: BRICKELL GROUP | | | TEL: 305-370-3988 | | | TEL: 561-373-3902 / KARI | | | E-MAIL: [email protected] | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 5THREVIEW | | | DATE: FWED. JUNE 07/ 2017 | | | ACTION: BUILDING PROVISO | | | | | | 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL | | | SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS | | | SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR | | | RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION | | | SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN | | | COMPLIANCE WITH THE SHORING DOCUMENTS BY THE | | | CONTRACTOR. | | | | | | 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE | | | CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE | | | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING | | | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT | | | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF | | | JOB, NO INSPECTION ACTIVITY. | | | | | | 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD | | | BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD | | | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED | | | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED | | | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT: | | | ART IN PUBLIC PLACES. | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH | | | APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH | | | WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR | | | SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER. | | | FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS | | | SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN | | | CHAPTER 16 OF THIS CODE. | | | | | | 6) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2017-06-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-06-05 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-06-02 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2017-06-02 13:45:34 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) | | | ADD: 1620 N. CONGRESS AVE. | | | CONT: BRICKELL GROUP | | | TEL: 305-370-3988 | | | TEL: 561-373-3902 / KARI | | | E-MAIL: [email protected] | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 4THREVIEW | | | DATE: FRI. JUNE 02/ 2017 | | | ACTION: BUILDING PROVISO | | | | | | 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL | | | SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS | | | SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR | | | RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION | | | SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN | | | COMPLIANCE WITH THE SHORING DOCUMENTS BY THE | | | CONTRACTOR. | | | | | | 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE | | | CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE | | | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING | | | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT | | | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF | | | JOB, NO INSPECTION ACTIVITY. | | | | | | 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD | | | BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD | | | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED | | | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED | | | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT: | | | ART IN PUBLIC PLACES. | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH | | | APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH | | | WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR | | | SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER. | | | FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS | | | SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN | | | CHAPTER 16 OF THIS CODE. | | | | | | 6) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-05-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-05-31 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-05-31 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2017-05-31 09:00:38 | | | | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) | | | ADD: 1620 N. CONGRESS AVE. | | | CONT: BRICKELL GROUP | | | TEL: 305-370-3988 | | | TEL: 561-373-3902 / KARI | | | E-MAIL: [email protected] | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 3RD REVIEW | | | DATE: TUES. MAY 30, 2017 | | | ACTION: DENIED | | | | | | 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL | | | SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS | | | SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR | | | RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION | | | SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN | | | COMPLIANCE WITH THE SHORING DOCUMENTS BY THE | | | CONTRACTOR. | | | | | | 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE | | | CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE | | | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING | | | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT | | | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF | | | JOB, NO INSPECTION ACTIVITY. | | | | | | 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD | | | BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD | | | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED | | | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED | | | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT: | | | ART IN PUBLIC PLACES. | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5-7) COMPLIED. | | | | | | 8) 3RD REQUEST. PLEASE PROVIDE AN ITEMIZED LIST OF COST | | | AND OVERHEAD INCLUDING THE DESIGN TEAM FEES FOR THESE | | | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE | | | CALCULATED VALUE OF THE PERMIT. THE STATED VALUE FOR | | | THE BUILDING PERMIT($5,000,000.00) AND THE FOUNDATION | | | PERMIT ($750,000.00) & VIBRO-PLACEMENT PERMIT | | | $85,000.00 TOTALS TO $5,835,000.00 DOLLARS. THE | | | CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES | | | IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING. | | | PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE | | | ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE | | | BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE | | | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE | | | CALCULATED VALUE OF THE PERMIT. | | | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT | | | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS | | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST | | | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC | | | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME OR MASTER PERMIT. | | | | | | 9) SEMI-COMPLIED. 3RD REQUEST. THIS REVIEW THERE WERE | | | ONLY 2 SETS OF FP01 & FP11 DRAWINGS. A3RD SET OF FIRE | | | PROTECTION PLANS ARE STILL REQUIRED, FOR A THRESHOLD | | | BUILDING. | | | | | | THIS IS A 3 STORY STRUCTURE EACH FLOOR IS OVER 12,000 | | | SQUARE FEET IN AREA. BOTH OF THESE REQUIREMENTS WILL | | | REQUIRE THE BUILDING TO BE FIRE SPRINKLERED AND HAVE | | | PLANS SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING | | | PERMIT. | | | 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER | | | SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS | | | CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE | | | FOLLOWING CONDITIONS EXISTS: | | | 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET | | | (1115 M2). | | | 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE | | | STORIES ABOVE GRADE PLANE. | | | | | | 10-12)COMPLIED. | | | | | | | | | 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE | | | OVER 40 FEET, IN COMPLIANCE WITH 2014 FBC-B | | | 2603.5.7(1-7). J.W. | | | | | | 14) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH | | | APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH | | | WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR | | | SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER. | | | FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS | | | SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN | | | CHAPTER 16 OF THIS CODE. | | | | | | 15) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 16) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-04-06 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-04-04 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2017-04-06 08:51:53 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) | | | ADD: 1620 N. CONGRESS AVE. | | | CONT: BRICKELL GROUP | | | TEL: 305-370-3988 | | | TEL: 561-373-3902 / KARI | | | E-MAIL: [email protected] | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: WED. APRIL 05/ 2017 | | | ACTION: DENIED | | | | | | 1) COMPLIED. SUBMITTED SITE PLAN. | | | | | | 2) 2ND REQUEST. THE 2 SOILS REPORTS SUBMITTED ARE | | | COPIES THE SIGNATURE AND SEALS ARE NOT ORIGINAL. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | | | | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE | | | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS | | | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER | | | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE | | | | | | 1ST REVIEW COMMENT. NO SOILS REPORT WAS SUBMITTED. 2014 | | | FBC-B1803.5.2 QUESTIONABLE SOIL. WHERE THE | | | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL | | | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO | | | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING | | | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 3) 2ND REQUEST / SEMI-COMPLIED. SHEET S1.0 INDICATES | | | THE 1ST FLOOR FINISH FLOOR SLAB EL. +0 FEET 0 INCHES. | | | PLEASE PROVIDE THE FINISH FLOOR ELEVATION IN NGVD. CITY | | | FIRM MAPS ARE STILL IN NGVD. | | | | | | 4) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD | | | BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01 | | | BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 4A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | | | | 4B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUESTS FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | FORMS SENT TO E-MAIL ADDRESS: [email protected] | | | SENT: 02/13/2017 04:09 PM. | | | | | | 4C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 4D) COMPLIED, ONLY FOR THE SPECIAL INSPECTOR NO | | | DESIGNEE PAPERWORK PROVIDED. | | | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | | | | 4E)2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 4F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF | | | DOCUMENTS ARE REQUIRED (SOILS REPORTS, PLANS, PRODUCT | | | APPROVALS, STRUCTURAL SHOP DRAWINGS, ETC? FOR DIGITAL | | | PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE PERMIT | | | LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT | | | LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH | | | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF | | | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE | | | THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS | | | OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 4G) NOTICE ONLY111 110.3.7.4.3 ALL SHORING AND | | | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE | | | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. | | | EACH SHORING AND RESHORING INSTALLATION SHALL BE | | | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE | | | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. | | | | | | 4H) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM | | | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 4I) NOTICE ONLY!!! 109.3.6 THRESHOLD BUILDINGS, | | | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. | | | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 5) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT: | | | ART IN PUBLIC PLACES. | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 6) 2ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO | | | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST | | | BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 7)NOTICE ONLY: FOUNDATION PERMIT. 107.3.3 PHASED | | | APPROVAL. | | | THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER | | | PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE | | | HOLDERS OWN RISK WITH THE BUILDING OPERATION AND | | | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE | | | STRUCTURE WILL BE GRANTED. NOTICE THE 1ST 7 COMMENTS | | | ARE ALSO ON THE FOUNDATION PERMIT. | | | | | | VIBRO-REPLACEMENT PERMIT: 17020319, COMMENTS NEED TO BE | | | ADDRESSED. | | | | | | 8) 2ND REQUEST. THE STATED VALUE FOR THE BUILDING | | | PERMIT($5,000,000.00) AND THE FOUNDATION PERMIT | | | ($750,000.00) TOTALS TO $5,750,000.00 DOLLARS. THE | | | CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES | | | IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING. | | | PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE | | | ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE | | | BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE | | | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE | | | CALCULATED VALUE OF THE PERMIT. | | | | | | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT | | | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS | | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST | | | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC | | | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME OR MASTER PERMIT. | | | | | | 9) 2ND REQUEST. NO RESPONSE COMMENT. THIS IS A 3 STORY | | | STRUCTURE EACH FLOOR IS OVER 12,000 SQUARE FEET IN | | | AREA. BOTH OF THESE REQUIREMENTS WILL REQUIRE THE | | | BUILDING TO BE FIRE SPRINKLERED AND HAVE PLANS | | | SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING PERMIT. | | | 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER | | | SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS | | | CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE | | | FOLLOWING CONDITIONS EXISTS: | | | 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET | | | (1115 M2). | | | 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE | | | STORIES ABOVE GRADE PLANE. | | | | | | 10)2ND REVIEW. THIS REVIEW THERE ARE STRUCTURAL PLANS. | | | SET # 1 SHEETS S1.0, S1.1, S2.0 & S3.0 ARE NOT SIGNED | | | AND SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. | | | EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS | | | AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY | | | THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | | | | SET # 2 NONE OF THE STRUCTURAL SHEETS ARE SIGNED AND | | | SEALED. FL ADMIN CODE 61G15-23.002 ENGINEERS. | | | | | | SET # 3 JUST RETURNED FROM THE PALM BEACH COUNTY IMPACT | | | FEE OFFICE DOES NOT HAVE STRUCTURAL SHEETS. | | | | | | | | | 11) 2ND REQUEST. SEMI-COMPLIED. LIFE SAFETY PLAN. THE | | | LIFE SAFETY PLAN A0.5 AND A6.1 BOTH SHOW THE 2 | | | STAIRWELLS WITH A CLEAR WIDTH OF 4 FOOT- 1 INCH. THE | | | COVERSHEET UNDER EGRESS CAPACITY LIST THE STAIR AS 3 | | | FOOT WIDE. THE CODE EXCEPTION TAKEN IS 1009.4.EXCEPTION | | | # 1. PLEASE NOTE THE EXCEPTION # 1 IS THE TOTAL | | | OCCUPANT LOAD IS TO BE TAKEN FOR THE FLOOR. THE 2012 | | | IBC- AND COMMENTARY IS THE BASE CODE THE 2014 FBC-B IS | | | DERIVED FROM. SEE 1005.3.1 PAGE 10-16 SECTION 1009.1. | | | EXCEPTION 1, IS APPLICABLE ONLY WHEN THE ENTIRE | | | OCCUPANT LOAD OF A STORY IS LESS THAN 50. | | | | | | | | | | | | 12) 2ND REQUEST. THE RESPONSE NARRATIVE REFERS BACK TO | | | SPECIFICATIONS SECTION 8.03 ON SHEET A-04. | | | EITHER THE SPECIFICATION SECTION 8.03 IS NOT CODE | | | COMPLIANT OR NOT COVERED IN THIS SECTION, SEE THE CODE | | | REQUIREMENTS THAT WERE REFERENCED UNDER THE 1ST REVIEW: | | | 2014 FBC-B 1008.1.4.3 HORIZONTAL SLIDING DOORS.IN OTHER | | | THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS | | | PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS IN | | | ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2 SHALL | | | COMPLY WITH ALL OF THE FOLLOWING CRITERIA: | | | | | | COMPLIED. 1. THE DOORS SHALL BE POWER OPERATED AND | | | SHALL BE CAPABLE OF BEING OPERATED MANUALLY IN THE | | | EVENT OF POWER FAILURE. | | | | | | COMPLIED. 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE | | | METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR | | | EFFORT. | | | | | | 3) 2ND REQUEST. PLEASE UPDATE PLANS, THE PLANS INDICATE | | | 50 LBS. TO SET THE DOOR IN MOTION AND THERE IS NO | | | REFERENCE TO THE 15 LBS. TO CLOSE THE DOOR. | | | CODE SECTION (3). THE FORCE REQUIRED TO OPERATE THE | | | DOOR SHALL NOT EXCEED 30 POUNDS (133 N) TO SET THE DOOR | | | IN MOTION AND 15 POUNDS (67 N) TO CLOSE THE DOOR OR | | | OPEN IT TO THE MINIMUM REQUIRED WIDTH. | | | | | | 4) .2ND REQUEST.(4) THE DOOR SHALL BE OPENABLE WITH A | | | FORCE NOT TO EXCEED 15 POUNDS (67 N) WHEN A FORCE OF | | | 250 POUNDS (1100 N) IS APPLIED PERPENDICULAR TO THE | | | DOOR ADJACENT TO THE OPERATING DEVICE. | | | | | | 5. NOT REQUIRED. THE DOOR ASSEMBLY SHALL COMPLY WITH | | | THE APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED, | | | SHALL BE SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE | | | DETECTION IN ACCORDANCE WITH SECTION 716.5.9.3, SHALL | | | BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL | | | COMPLY WITH SECTION 716. | | | | | | 6. 2ND REQUEST.(6)THE DOOR ASSEMBLY SHALL HAVE AN | | | INTEGRATED STANDBY POWER SUPPLY. | | | | | | 7. 2ND REQUEST.(7) THE DOOR ASSEMBLY POWER SUPPLY SHALL | | | BE ELECTRICALLY SUPERVISED. | | | | | | 8.2ND REQUEST.(8) THE DOOR SHALL OPEN TO THE MINIMUM | | | REQUIRED WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF | | | THE OPERATING DEVICE. | | | | | | 1ST REVIEW COMMENT: SHEETS A1.1 & A1.2 BOTH HAVE A DOOR | | | DESIGNATED A W5 OR A HORIZONTAL SLIDING DOOR. PLEASE | | | SHOW COMPLIANCE WITH 2014 FBC-B 1008.1.4.3 (1-8). THERE | | | ARE ISSUES THAT SECTION 8.03 EITHER ARE NOT CODE | | | COMPLIANT OR NOT COVERED IN THIS SECTION. SEE LIST | | | BELOW: | | | | | | 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE | | | OVER 40 FEET, INCOMPLIANE WITH 2014 FBC-B | | | 2603.5.7(1-7). J.W. | | | | | | 14) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH | | | APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH | | | WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR | | | SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER. | | | FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS | | | SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN | | | CHAPTER 16 OF THIS CODE. | | | | | | 15) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 16) BUILDING PROVISO/ DEFERRED SUBMITAL: | | | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-02-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-02-14 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-02-13 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2017-02-14 08:13:25 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) | | | ADD: 1620 N. CONGRESS AVE. | | | CONT: TBD | | | TEL: 561-373-3902 / KARI | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: TUES. FEB. 14/ 2017 | | | ACTION: DENIED | | | | | | 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION: | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS | | | 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING | | | MISSING DOCUMENTS: SURVEY AND OR SITE PLAN | | | SITE REQUIREMENTS: | | | PARKING | | | FIRE ACCESS | | | VEHICLE LOADING | | | DRIVING/TURNING RADIUS | | | FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) | | | SET BACK/SEPARATION (ASSUMED PROPERTY LINES) | | | LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES | | | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD | | | ELEVATIONS | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL | | | BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION | | | AND EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT | | | LINES, THE ESTABLISHED STREET GRADES AND | | | THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, FLOOD | | | HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE BOUNDARY LINE SURVEY. | | | IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL SHOW | | | CONSTRUCTION TO BE DEMOLISHED AND THE | | | LOCATION AND SIZE OF EXISTING STRUCTURES AND | | | CONSTRUCTION THAT ARE TO REMAIN ON THE SITE OR PLOT. | | | THE BUILDING OFFICIAL IS AUTHORIZED TO WAIVE OR MODIFY | | | THE REQUIREMENT FOR A SITE PLAN WHEN THE | | | APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR | | | WHEN OTHERWISE WARRANTED. | | | | | | ARCHITECTURAL FLOOR PLANS OF BUILDING | | | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED. | | | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE | | | TABLE 503). | | | | | | 2) NO SOILS REPORT WAS SUBMITTED. 2014 FBC-B1803.5.2 | | | QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH | | | OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A | | | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE | | | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION | | | BE CONDUCTED. | | | | | | 3) PLEASE NOTE NO CIVIL SHEETS SUBMITTED, NO | | | ARCHITECTURAL SHEETS SUBMITTED AND SHEET S1.0 INDICATES | | | THE 1ST FLOOR FINISH FLOOR SLAB EL. +0 FEET 0 INCHES. | | | PLEASE PROVIDE THE FINISH FLOOR ELEVATION IN NGVD. CITY | | | FIRM MAPS ARE STILL IN NGVD. | | | | | | 4) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD | | | BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01 | | | BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. | | | FORMS SENT TO E-MAIL ADDRESS: [email protected] | | | SENT: 02/13/2017 04:09 PM. | | | | | | 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 4F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, | | | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING | | | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE | | | IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 4G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 4H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 4I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | 5) PLEASE NOTE ZONING REQUIREMENT: ART IN PUBLIC | | | PLACES. | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 7)NOTICE ONLY: FOUNDATION PERMIT. 107.3.3 PHASED | | | APPROVAL. | | | THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER | | | PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE | | | HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND | | | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE | | | STRUCTURE WILL BE GRANTED. | | | | | | NOTICE THE 1ST 7 COMMENTS ARE ALSO ON THE FOUNDATION | | | PERMIT. | | | | | | 8) THE STATED VALUE FOR THE BUILDING | | | PERMIT($5,000,000.00) AND THE FOUNDATION PERMIT | | | ($750,000.00) TOTALS TO $5,750,000.00 DOLLARS. THE | | | CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES | | | IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING. | | | PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE | | | ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE | | | BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE | | | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE | | | CALCULATED VALUE OF THE PERMIT. | | | | | | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT | | | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS | | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST | | | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC | | | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME OR MASTER PERMIT. | | | | | | 9) THIS IS A 3 STORY STRUCTURE EACH FLOOR IS OVER | | | 12,000 SQUARE FEET IN AREA. BOTH OF THESE REQUIREMENTS | | | WILL REQUIRE THE BUILDING TO BE FIRE SPRINKLERED AND | | | HAVE PLANS SUBMITTED BEFORE THE ISSUANCE OF THE | | | BUILDING PERMIT. | | | 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER | | | SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS | | | CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE | | | FOLLOWING CONDITIONS EXISTS: | | | 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET | | | (1115 M2). | | | 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE | | | STORIES ABOVE GRADE PLANE. | | | | | | 10) THERE ARE NO STRUCTURAL DRAWINGS WITHIN THIS SET OF | | | PLANS. THE COVERSHEET INDICATES THIS IS A DESIGN BUILD. | | | THERE WERE SOME PLANS WITHIN THE FOUNDATION PLAN BUT NO | | | PLANS WERE SUBMITTED NOR SHOW ON THE INDEX OF DRAWINGS. | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE | | | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL | | | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND | | | DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN; | | | FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL | | | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING | | | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | | SOIL CONDITIONS/ANALYSIS | | | TERMITE PROTECTION | | | DESIGN LOADS | | | WIND REQUIREMENTS | | | BUILDING ENVELOPE | | | FOUNDATION | | | WALL SYSTEMS | | | FLOOR SYSTEMS | | | ROOF SYSTEMS | | | THRESHOLD INSPECTION PLAN | | | STAIR SYSTEMS | | | | | | 11) THE SET OF PLANS ARE MISSING A LIFE SAFETY PLAN FOR | | | EVERY FLOOR LEVEL. | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | COMMON PATH OF EGRESS TRAVEL | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | DOORS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | SPECIFIC OCCUPANCY REQUIREMENTS | | | CONSTRUCTION REQUIREMENTS | | | | | | 12) SHEETS A1.1 & A1.2 BOTH HAVE A DOOR DESIGNATED A W5 | | | OR A HORIZONTAL SLIDING DOOR. PLEASE SHOW COMPLIANCE | | | WITH 2014 FBC-B 1008.1.4.3 (1-8). | | | | | | 13)SHEET A4.1 & THE A5 SERIES OF PLANS INDICATES THE | | | USE OF FOAM EFIS BRACKETS AND EFIS SOFFITS ABOVE 40 | | | FEET ABOVE GRADE. PLEASE SHOW COMPLIANCE WITH FBC-B | | | 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION. | | | ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, | | | EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE | | | CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH | | | THE FOLLOWING LIMITATIONS: | | | 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED | | | TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE. | | | | | | 14) SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER | | | WHICH APPEARS WILL STAY IN THE OPEN POSITION DURING A | | | HIGH WIND EVENT, PLEASE PROVIDE EITHER PRODUCT | | | APPROVALS FOR SUCH OR SITE SPECIFIC ENGINEERING FOR | | | METAL SHUTTER. FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND | | | CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST THE LOADS | | | SET FORTH IN CHAPTER 16 OF THIS CODE. | | | | | | 15) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 16) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-06-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-08 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-06-08 |
Time |
07:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-03-27 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-03-27 |
Time |
07:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-02-07 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2017-02-07 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2017-02-07 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2017-02-07 13:51:27 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | PROJECT NAME: NEW STORAGE BLDG. | | | JOB ADDRESS: 750 PONCE DE LEON PL. | | | DESCRIPTION: | | | MASTER PERMIT: 17011176 | | | | | | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. | | | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF | | | SUBMITTED CORRECTIONS. | | | | | | 1. ELECTRICAL SUB PERMIT REQUIRED | | | 2. ALL FIRE ALARM WORK REQUIRES A SEPARATE PERMIT WITH | | | ITS OWN SUBMITTAL PACKAGE. | | | 3. THERE IS A MISSING EMERGENCY LIGHT IN THE LOUNGE | | | AREA: SECTION 32.7-33.5/I .5-M | | | 4. THERE IS A MISSING EXIT LIGHT IN SECTION 1-2/G-H | | | 5. THERE IS A MISSING EXIT LIGHT IN THE CORRIDOR OF | | | 23-35/F-G | | | 6. THE DRINKING FOUNTAIN IS ELECTRIC SHALL BE ON A GFI | | | PROTECTED CIRCUIT NOT INDICATED ON PANEL | | | 7. THERE IS AN EMERGENCY LIGHT MISSING IN EACH OF THE | | | TOILET ROOMS OF THE SECOND FLOOR. | | | 8. RELOCATE THE SERVICE OUTLETS FOR THE HVAC SO THEY | | | ARE NOT BEHIND THE UNITS. | | | 9. IF A FIRE PUMP IS REQUIRED PER THE FIRE ALARM REVIEW | | | (FIRE SPRINKLERS) IS REQUIRED, A REVISED RISER DRAWING | | | SHOWING THE FIRE PUMP EQUIPMENT AND CONNECTIONS ALONG | | | WITH THE ADDITIONAL LOADS SHALL BE SUBMITTED FOR | | | ELECTRICAL REVIEW AS WELL. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2017-08-14 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
2017-08-13 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mgonzale |
Date |
2017-07-13 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2017-08-14 10:48:47 | PLANS REVISED, APPROVED. 08/14/2017 | | | MGONZALEZ | | 2017-07-13 13:42:42 | COMMENTS WERE EMAILED TO EOR MICHAEL GRZELKA, P.E. ON | | | JUNE 16, 2017 FOR THE CIVIL PLANS AND HE WAS ASLO | | | INFORMED ABOUT ALL PALM BEACH COUNTY PERMIT | | | REQUIREMENTS. | | | | | | ONCE FINAL REVISED PLANS AND PALM BEACH COUNTY PERMITS | | | (E.G. RIGHT-OF-WAY PERMIT FOR OPEN CUT ETC.) ARE | | | RECIVED ARE RECEIVED (IN OUR DEPARTMENT) AND DEEM | | | ACCEPTABLE WE WILL SIGN OFF ON THIS PERMIT. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2017-05-30 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
2017-05-11 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
mkhan |
Date |
2017-04-24 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2017-05-30 11:04:44 | REVISED PLANS WERE SUBMITTED ON 4/24/2017 FOR THE | | | SEPARATE 'ENGINEERING APPROVAL APPLICATION' | | | (E17010028). THERE ARE STILL OUTSTANDING ISSUES AND | | | COMMENTS WERE SENT TO MICHAEL GRIZELKA, P.E., THE CIVIL | | | ENGINEER FOR THIS PROJECT. EXPECTING TO RECEIVE REVISED | | | PLANS WITH THE COMMENTS ADDRESSED AT THE 3RD ROUND | | | REVIEW. THIS PERMIT IS FAILED AT THIS REVIEW CYCLE | | | UNTIL ENGINEERING REVIEW COMMENTS ARE ADDRESSED. | | | | | | MOSTAQUE KHAN, P.E. | | | LAND DEVELOPMENT ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | OFFICE: (561) 494-1124 | | | FAX: (561) 494-1116 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-03-21 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
2017-03-17 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
mkhan |
Date |
2017-03-17 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2017-03-17 16:19:11 | SEPARATE 'ENGINEERING APPROVAL APPLICATION' (E17010028) | | | IS SUBMITTED FOR THIS PROJECT. FOR WHICH, REVIEW IS | | | COMPLETE AND COMMENTS WERE SENT TO MICHAEL GRIZELKA, | | | THE CIVIL ENGINEER FOR THIS PROJECT. EXPECTING TO | | | RECEIVE REVISED PLANS WITH THE COMMENTS ADDRESSED AT | | | THE 2ND ROUND REVIEW. THIS PERMIT IS FAILED AT THIS | | | REVIEW CYCLE UNTIL ENGINEERING REVIEW COMMENTS ARE | | | ADDRESSED. | | | | | | MOSTAQUE KHAN, P.E. | | | LAND DEVELOPMENT ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | OFFICE: (561) 494-1124 | | | FAX: (561) 494-1116 | | | E-MAIL: [email protected] | | 2017-03-02 16:55:50 | MKAHN REVIEWING UNDER E17010028 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-05-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-12 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-03-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-03-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-03-15 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-02-01 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-02-01 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-02-01 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2017-02-01 14:27:24 | 1620 NORTH CONGRESS AVENUE | | | PERMIT #17011176 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | NO CIVIL DRAWINGS SUBMITTED SHOWING AREA SITE PLAN, | | | FIRE DEPARTMENT ACCESS ROADS, UNDERGROUND FIRE MAINS | | | AND NEW/EXISTING FIRE HYDRANTS. | | | | | | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE | | | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE | | | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE | | | OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF | | | THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE | | | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OF 50 | | | OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA | | | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | PROVIDE A LIFE SAFETY PLAN SHOWING ANY FIRE RATED | | | WALLS, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. | | | | | | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK | | | SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH | | | AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED | | | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION | | | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE | | | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING | | | MATERIALS SHALL BE PROVIDED. | | | | | | ARE ANY CONSTRUCTION TRAILERS INTENDED TO OCCUPY THE | | | SITE? THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION | | | TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO | | | "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC | | | SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION | | | REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION | | | TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND | | | COMPLIANCE WITH THE FOLLOWING: | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED | | | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON | | | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED DURING PLAN RESUBMISSION. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-14 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-06-07 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2017-06-07 13:50:20 | IN: SUBMITTED 6/07/17/ BIN:C39. J. W. SHEETS E1.1, | | | E1.2, E-1.3 E-1.4 & E1.5 ALL NEED UPDATES NOT SIGNED | | | AND DATED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-14 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-04-26 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-04-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-04-12 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-14 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2017-03-02 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2017-01-31 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-04-06 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-04-06 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2017-04-06 08:56:45 | PALM BEACH COUNTY IMPACT FEE OFFICE | | | PAID UNDER THE FOUNDATION PERMIT : 17011177 | | | MARCH 16/ 2017 | | | MU-2017-7076 | | | SQ. FT. 104,811 | | | AMOUNT PAID: $58,893.30. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-02-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-02-14 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-02-13 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2017-02-14 08:02:59 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-05 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-05 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2017-07-05 10:49:05 | MECHANICAL PROVISO: | | | | | | 1) COMMISSIONING REPORT REQUIRED AT FINAL | | | INSPECTION/HOLD ON CO. | | | | | | CCOLE- 7/5/17 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-05-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-04 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-03 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2017-05-04 07:21:20 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011176 | | | 5/4/17 | | | | | | 1) THE AC CALCULATIONS FOR THE FC-6 INDICATE THE UNIT | | | IS OVERSIZED. THE CALCULATION INDICATES 2.2 TONS OF | | | COOLING REQUIRED- THE SCHEDULE SHOWS FC-6 IS A 5-TON | | | UNIT- SEE SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | PLEASE NOTE THAT THE FC-6 CALULATION IS LABELED AS | | | "OFFICE" HOWEVER THE UNIT APPEARS TO BE LOCATED IN THE | | | STORAGE AREA. | | | | | | 2) THE AC CALCS ARE INDICTING FC-7 TO BE LOCATED ON THE | | | 2ND FLOOR, HOWEVER THE PLAN SHOWS IT ON THE 1ST FLOOR. | | | | | | 3) THE DUCT SMOKE DETECTORS FOR THE HEAT PUMPS SHALL BE | | | LIOCATED UPSTREAM OF THE OUTSIDE AIR DUCT CONNECTION- | | | SEE SECTION 606.2.1 AND CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-03-24 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-03-24 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2017-03-24 10:36:24 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011176 | | | 3/24/17 | | | | | | 1) IN RESPONSE TO COMMENT #1 FROM THE 1ST REVIEW | | | REQUESTING DOCUMENTATION OF ENERGY CONSERVATION | | | COMPLIANCE, AN OUTDATED ENERGYGAUGE FORM 506-2010 HAS | | | BEEN SUBMITTED. PLEASE SEE SECTION C101.5.1 FBC-14 | | | ENERGY CONSERVATION AND SUBMIT AN UP-TO-DATE COMPLIANCE | | | FORM. | | | | | | 2) THE REQUESTED AC COOLING AND HEATING CALCULATIONS | | | WERE NOT SUBMITTED- PLEASE COMPLY. | | | | | | 3) AS REQUESTED IN THE 1ST REVIEW, PLEASE SUBMIT TWO | | | COPIES OF THE MIAMI-DADE NOA #16-0112.02 FOR THE | | | LOUVER. | | | | | | 4) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION- | | | AC SYSTEM COMMISSIONING IS REQUIRED. | | | | | | C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION | | | REQUIREMENTS. | | | PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE | | | REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE | | | OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN | | | ACCORDANCE THE PROVISIONS OF THIS SECTION. | | | CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE | | | PROVISIONS FOR COMMISSIONING AND COMPLETION | | | REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE | | | PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER | | | REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE | | | GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE | | | OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS | | | C408.2.4 AND C408.2.5. | | | | | | 2A) C408.2.1 COMMISSIONING PLAN. | | | A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED | | | DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL | | | INCLUDE THE FOLLOWING ITEMS: | | | | | | 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL | | | BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, | | | INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF | | | THE ACTIVITIES. | | | 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR | | | SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO | | | BE PERFORMED. | | | 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED | | | TO CALIBRATIONS AND ECONOMIZER CONTROLS. | | | 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. | | | AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER | | | DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. | | | 5. MEASURABLE CRITERIA FOR PERFORMANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-02-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-02-02 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-02-02 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2017-02-02 16:59:57 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011176 | | | 2/2/17 | | | | | | 1) THE PROPOSED BUILDING SHALL BE IN DESIGNED AND | | | CONSTRUCTED IN ACCORDANCE WITH THE FBC-14 ENERGY | | | CONSERVATION CODE. REFER TO SECTIONS C101.2 AND C401.2 | | | AND PROVIDE COMPLIANCE DOCUMENTATION. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 3) SHEET M0.1, NOTE #15: PLEASE UPDATE THE SMACNA | | | REFERENCE TO THE CURRENT 2005 EDITION AND PROVIDE | | | TYPICAL DUCT HANGING AND CONNECTION DETAILS ON THE | | | PLANS. | | | | | | 4) M0.1, NOTE #34: PLEASE CLARIFY IF THE AC SYSTEMS | | | WILL BE LINKED TOGETHER FOR SIMULTANEOUS FAN SHUTDOWN | | | IF ANY SINGLE DUCT SMOKE DETECTOR ACTIVATES. | | | | | | 5) M0.2: PROVIDE THE WIND DESIGN CRITERIA FOR | | | INSTALLATION OF THE CONDENSERS IN COMPLIANCE WITH | | | SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609 | | | FBC-14 BUILDING. | | | | | | 6) SUBMIT TWO COPIES OF A VALID FLORIDA PRODUCT | | | APPROVAL AND/OR MIAMI-DADE NOA FOR THE O/A INTAKE AND | | | EXHAUST LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2017-07-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-06 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-07-05 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-23 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-23 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-04-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-04-11 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-04-11 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2017-04-11 17:50:18 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT COMPLIED. | | | | | | 5. A CLEAN OUT IS REQUIRED AT THE BASE OF ANY WASTE OR | | | SOIL STACK. PER FBC PL 708.3.4 | | | | | | 7. TEMPERED WATER IS REQUIRE AT ALL LAVATORY'S IN | | | PUBLIC BATHROOMS. PER FBC PL 416.5 | | | | | | 8.SHOW THE REQUIRED TRAP PRIMERS ON ALL FLOOR DRAINS. | | | PER FBC PL 1002.4 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-03-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-02 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-02 |
Time |
06:23 |
Sent To |
|
|
| Notes |
| 2017-03-02 12:15:23 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. WILL THE SINGLE USER BATHROOM NEXT TO THE RETAIL | | | SPACE BE ACCESSIBLE FOR THE OCCUPANTS OF THE RETAIL | | | SPACE TO USE, IT APPEARS THAT IT CAN ONLY BE ACCESSED | | | THROUGH THE STORAGE FACILITY PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. THE COFFEE BAR SHALL COMPLY WITH FBC ACC | | | 902.2,902.3, 308 | | | | | | 3.SHT.P0.2 WATER HEATER DETAIL SHALL SHOW PAN. PER FBC | | | PL 504.7 | | | | | | 4.P1.1. P1.2 DISCHARGE FROM ELEVATOR SUMP SHALL | | | TERMINATE A MIN OF 12" FROM BUILDING. FBC 1503.7 | | | | | | 5. A CLEAN OUT IS REQUIRED AT THE BASE OF ANY WASTE OR | | | SOIL STACK. PER FBC PL 708.3.4 | | | | | | 6. A CLEAN OUT IS REQUIRED @ 100' INTERVALS IN THE | | | BUILDING SEWER. PER FBC PL 708.3.2 | | | | | | 7. TEMPERED WATER IS REQUIRE AT ALL LAVATORY'S IN | | | PUBLIC BATHROOMS. PER FBC PL 416.5 | | | | | | 8.SHOW THE REQUIRED TRAP PRIMERS ON ALL FLOOR DRAINS. | | | PER FBC PL 1002.4 | | | | | | 9. PLEASE PROVIDE A WATER RISER. PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2017-06-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-06-02 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-06-02 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2017-06-02 13:47:10 | COMPLETE THRESHOLD DOCUMENTS ARE FOUND UNDER THE | | | FOUNDATION PERMIT 17011177. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2017-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-04-06 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-04-06 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2017-04-06 08:54:00 | THRESHOLD BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) | | | ADD: 1620 N. CONGRESS AVE. | | | CONT: TBD | | | TEL: 561-373-3902 / KARI | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: WED. APRIL 05/ 2017 | | | ACTION: DENIED | | | | | | 1) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD | | | BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01 | | | BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 1A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | | | | 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUESTS FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | FORMS SENT TO E-MAIL ADDRESS: [email protected] | | | SENT: 02/13/2017 04:09 PM. | | | | | | 1C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 1D) COMPLIED, ONLY FOR THE SPECIAL INSPECTOR NO | | | DESIGNEE PAPERWORK PROVIDED. | | | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | | | | 1E)2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 1F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF | | | DOCUMENTS ARE REQUIRED (SOILS REPORTS, PLANS, PRODUCT | | | APPROVALS, STRUCTURAL SHOP DRAWINGS, ETC? FOR DIGITAL | | | PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE PERMIT | | | LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT | | | LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH | | | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF | | | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE | | | THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS | | | OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) NOTICE ONLY111 110.3.7.4.3 ALL SHORING AND | | | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE | | | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. | | | EACH SHORING AND RESHORING INSTALLATION SHALL BE | | | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE | | | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM | | | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) NOTICE ONLY!!! 109.3.6 THRESHOLD BUILDINGS, | | | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. | | | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2017-02-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-02-14 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-02-14 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2017-02-14 08:31:26 | SEE BUILDING NOTES 4A-4I. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2017-08-08 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-08-08 |
Time |
08:57 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2017-08-08 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2017-06-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-06-26 |
Time |
11:29 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2017-06-26 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2017-06-26 11:29:24 | FAILED PENDING THE SUBMITTAL OF THE PALM BEACH COUNTY | | | DRIVEWAY CONNECTION APPROVAL (SEE COMMENT NO. 1. | | | | | | 1) IN ACCORDANCE WITH RESOLUTION NO. 201-16, WHICH | | | APPROVED THIS SITE DEVELOPMENT, PRIOR TO ZONING | | | APPROVAL OF THIS BUILDING PERMIT PROVIDE THE PLANNING | | | DIVISION WITH A COPY OF THE APPROVED DRIVEWAY | | | CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING | | | FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE. | | | | | | 2) PLANS HAVE BEEN STAMPED AS THEY COMPLY WITH ZONING | | | REQUIREMENTS. | | | | | | 3) THERE ARE DOORS SHOWN ON VARIOUS PLANS IN NEW | | | LOCATIONS AND THERE ARE MORE HEAT PUMPS (MECHANICAL | | | EQUIPMENT) SHOWN ALONG THE REAR OF THE BUILDING AS | | | COMPARED TO THE SITE, LANDSCAPE, ELEVATION AND CIVIL | | | PLANS APPROVED AS PART OF THE PLANNING APPROVAL | | | PROCESS. SINCE THESE PLANS HAVE CHANGED, PRIOR TO C.O. | | | OF THIS BUILDING, AN AS BUILT MINOR AMENDMENT IS | | | REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION. | | | | | | 4) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. SIGNAGE | | | B. LANDSCAPE | | | C. IRRIGATION | | | D. SITE LIGHTING | | | E. PARKING LOT STRIPING | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2017-05-25 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-05-25 |
Time |
14:56 |
Rev Time |
1.25 |
| Received By |
eschneid |
Date |
2017-05-08 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2017-05-25 14:56:11 | FAILED | | | | | | PROVIDE WRITTEN RESPONSES. | | | | | | 1) REPEAT UPDATED COMMENT: FOUNDATION SHEET S1.1 DOES | | | NOT SHOW THE RELOCATED DOOR LOCATION THAT IS REFLECTED | | | ON THE REMAINDER OF THE PLANS. ALL PLANS SHALL SHOW THE | | | SAME CONDITIONS. THE STRUCTURAL PLAN MUST BE CORRECTED | | | PRIOR TO ZONING APPROVAL OF THIS BUILDING PERMIT. THE | | | SITE AND CIVIL PLANS SHALL BE CORRECTED PRIOR TO C.O. | | | (SEE COMMENT NO. 3 BELOW). | | | | | | 2) REPEAT COMMENT: THE FIRST FLOOR ELECTRICAL SITE | | | PLANS SHOW HEAT PUMPS (HP-5 AND HP-7) ON THE SOUTH SIDE | | | OF THE BUILDING. MECHANICAL EQUIPMENT IS NOT PERMITTED | | | BETWEEN THE BUILDING AND CONGRESS AVENUE. SHEET M1.1 | | | CORRECTLY SHOWS BOTH OF THESE UNITS TO THE REAR OF THE | | | BUILDING. | | | | | | 3) THERE ARE DOORS SHOWN ON VARIOUS PLANS IN NEW | | | LOCATIONS AND THERE ARE MORE HEAT PUMPS (MECHANICAL | | | EQUIPMENT) SHOWN ALONG THE REAR OF THE BUILDING AS | | | COMPARED TO THE SITE, LANDSCAPE, ELEVATION AND CIVIL | | | PLANS APPROVED AS PART OF THE PLANNING APPROVAL | | | PROCESS. SINCE THESE PLANS HAVE CHANGED, PRIOR TO C.O. | | | OF THIS BUILDING, AN AS BUILT MINOR AMENDMENT IS | | | REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION. | | | | | | 4) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. | | | 201-16, WHICH APPROVED THIS SITE DEVELOPMENT, PRIOR TO | | | ZONING APPROVAL OF THIS BUILDING PERMIT PROVIDE THE | | | PLANNING DIVISION WITH A COPY OF THE APPROVED DRIVEWAY | | | CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING | | | FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE. | | | | | | 5) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. SIGNAGE | | | B. LANDSCAPE | | | C. IRRIGATION | | | D. SITE LIGHTING | | | E. PARKING LOT STRIPING | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-03-30 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-03-30 |
Time |
09:46 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2017-03-28 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2017-03-30 09:47:10 | FAILED | | | | | | PROVIDE WRITTEN RESPONSES. | | | | | | 1) REPEAT UPDATED COMMENT: THE FOLLOWING PLANS DO NOT | | | SHOW THE SAME FIRST FLOOR CONDITIONS - ARCHITECTURAL | | | SITE PLAN (SHEETS A0.5 AND A1.0) THE LIFE SAFETY PLAN | | | (SHEET A0.5), PARTIAL FIRST FLOOR PLANS (SHEETS A1.1 | | | AND A1.2), THE SITE PLAN (SP-1), CIVIL PLAN (SHEET 2 OF | | | 7), SOUTH AND EAST ELEVATIONS (SHEETS A4.1 AND S1.9), | | | PARTIAL 1ST FLOOR ELECTRICAL PLAN (SHEET E1.2), PARTIAL | | | 1ST FLOOR FIRE PROTECTION PLAN (SHEET FP1.1), | | | STRUCTURAL PLANS (SHEETS S1.0 AND S1.1) - EX. DOOR | | | PLACEMENT FOR THE SPRINKLER ROOM (FROM THE FRONT TO THE | | | SIDE) AND ELECTRIC ROOM (FROM INSIDE TO OUTSIDE) AND | | | NEW DOOR ON SOUTH ELEVATION OF LIFE SAFETY PLAN BY THE | | | RETAIL BAY. ALL PLANS SHALL SHOW THE SAME CONDITIONS. | | | THE ARCHITECTURAL, ELECTRICAL, STRUCTURAL AND FIRE | | | PROTECTION PLANS (AND ANY OTHER PLANS WHICH DO NOT | | | MATCH) SHALL BE CORRECTED PRIOR TO ZONING APPROVAL OF | | | THIS BUILDING PERMIT. THE SITE AND CIVIL PLANS SHALL BE | | | CORRECTED PRIOR TO C.O. (SEE COMMENT NO. 4 BELOW). | | | | | | 2) WHY ARE THERE TWO ARCHITECTURAL SITE PLANS, WHICH | | | APPEAR THE SAME, WITH TWO DIFFERENT SHEET NUMBERS? WHY | | | DOES THE LIFE SAFETY PLAN HAVE THE SAME SHEET NUMBER AS | | | ONE OF THE ARCHITECTURAL SITE PLANS? | | | | | | 3) THE FIRST FLOOR ELECTRICAL SITE PLANS SHOW HEAT | | | PUMPS (HP-5 AND HP-7) ON THE SOUTH SIDE OF THE | | | BUILDING. MECHANICAL EQUIPMENT IS NOT PERMITTED BETWEEN | | | THE BUILDING AND CONGRESS AVENUE. SHEET M1.1 CORRECTLY | | | SHOWS BOTH OF THESE UNITS TO THE REAR OF THE BUILDING. | | | | | | 4) AS STATED IN COMMENT NO. 1 ABOVE, THERE ARE DOORS | | | SHOWN ON VARIOUS PLANS IN NEW LOCATIONS AND THERE ARE | | | MORE HEAT PUMPS (MECHANICAL EQUIPMENT) SHOWN ALONG THE | | | REAR OF THE BUILDING AS COMPARED TO THE SITE, | | | LANDSCAPE, ELEVATION AND CIVIL PLANS APPROVED AS PART | | | OF THE PLANNING APPROVAL PROCESS. SINCE THESE PLANS | | | HAVE CHANGED, PRIOR TO C.O. OF THIS BUILDING, AN AS | | | BUILT MINOR AMENDMENT IS REQUIRED TO BE SUBMITTED TO | | | THE PLANNING DIVISION. | | | | | | 5) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. | | | 201-16, WHICH APPROVED THIS SITE DEVELOPMENT, PRIOR TO | | | ZONING APPROVAL OF THIS BUILDING PERMIT PROVIDE THE | | | PLANNING DIVISION WITH A COPY OF THE APPROVED DRIVEWAY | | | CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING | | | FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE. | | | | | | 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. SIGNAGE | | | B. LANDSCAPE | | | C. IRRIGATION | | | D. SITE LIGHTING | | | E. PARKING LOT STRIPING | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-02-23 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-02-23 |
Time |
11:50 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2017-02-22 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2017-02-23 11:58:13 | FAILED | | | | | | 1) PROVIDE THE SURVEY/SITE PLAN SHOWING THE BUILDING | | | SETBACKS AND SITE DATA. | | | | | | 2) THE FIRST FLOOR PLANS DO NOT MATCH THE ARCHITECTURAL | | | SITE PLAN ? DOOR PLACEMENT FOR THE SPRINKLER ROOM (FROM | | | THE FRONT TO THE SIDE). ALL PLANS SHALL SHOW THE SAME | | | CONDITIONS. | | | | | | 3) THE NEW LOCATION OF THE SPRINKLER ROOM DOOR ALSO | | | DIFFERS FROM THE PLANS APPROVED AS PART OF THE RECENT | | | MINOR AMENDMENT. PRIOR TO C.O. OF THIS BUILDING, AN AS | | | BUILT MINOR AMENDMENT IS REQUIRED TO BE SUBMITTED TO | | | THE PLANNING DIVISION. | | | | | | 4) PRIOR TO ZONING APPROVAL OF THE BUILDING PERMIT | | | PROVIDE THE PLANNING DIVISION WITH A COPY OF THE | | | APPROVED DRIVEWAY CONNECTION PERMIT FROM PALM BEACH | | | COUNTY ENGINEERING FOR THE DRIVEWAY CONNECTIONS TO | | | NORTH CONGRESS AVENUE. | | | | | | 5) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED, AND APPROVED BY THE PLANNING | | | DIVISION. | | | | | | 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. SIGNAGE | | | B. LANDSCAPE | | | C. IRRIGATION | | | D. SITE LIGHTING | | | E. PARKING LOT STRIPING | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | |
|
|
|