Plan Review Details - Permit 17011176
Plan Review Stops For Permit 17011176
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-06-08 Cont ID  
Sent By jwitmer Date 2017-06-08 Time 13:32 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 11:42 Sent To  
Notes
2017-06-08 11:43:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: BRICKELL GROUP
 TEL: 305-370-3988
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 5THREVIEW
 DATE: FWED. JUNE 07/ 2017
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE
 CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT:
 ART IN PUBLIC PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5) BUILDING PROVISO/ DEFERRED SUBMITAL:
 SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH
 APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH
 WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR
 SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER.
 FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS
 SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN
 CHAPTER 16 OF THIS CODE.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITAL:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-06-05 Cont ID  
Sent By jwitmer Date 2017-06-05 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2017-06-02 Time 10:10 Sent To  
Notes
2017-06-02 13:45:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: BRICKELL GROUP
 TEL: 305-370-3988
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4THREVIEW
 DATE: FRI. JUNE 02/ 2017
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE
 CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT:
 ART IN PUBLIC PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5) BUILDING PROVISO/ DEFERRED SUBMITAL:
 SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH
 APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH
 WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR
 SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER.
 FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS
 SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN
 CHAPTER 16 OF THIS CODE.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITAL:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-31 Cont ID  
Sent By jwitmer Date 2017-05-31 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2017-05-31 Time 08:29 Sent To  
Notes
2017-05-31 09:00:38 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: BRICKELL GROUP
 TEL: 305-370-3988
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. MAY 30, 2017
 ACTION: DENIED
  
 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE
 CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT:
 ART IN PUBLIC PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5-7) COMPLIED.
  
 8) 3RD REQUEST. PLEASE PROVIDE AN ITEMIZED LIST OF COST
 AND OVERHEAD INCLUDING THE DESIGN TEAM FEES FOR THESE
 PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE
 CALCULATED VALUE OF THE PERMIT. THE STATED VALUE FOR
 THE BUILDING PERMIT($5,000,000.00) AND THE FOUNDATION
 PERMIT ($750,000.00) & VIBRO-PLACEMENT PERMIT
 $85,000.00 TOTALS TO $5,835,000.00 DOLLARS. THE
 CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES
 IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING.
 PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE
 ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE
 BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE
 PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE
 CALCULATED VALUE OF THE PERMIT.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 9) SEMI-COMPLIED. 3RD REQUEST. THIS REVIEW THERE WERE
 ONLY 2 SETS OF FP01 & FP11 DRAWINGS. A3RD SET OF FIRE
 PROTECTION PLANS ARE STILL REQUIRED, FOR A THRESHOLD
 BUILDING.
  
 THIS IS A 3 STORY STRUCTURE EACH FLOOR IS OVER 12,000
 SQUARE FEET IN AREA. BOTH OF THESE REQUIREMENTS WILL
 REQUIRE THE BUILDING TO BE FIRE SPRINKLERED AND HAVE
 PLANS SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING
 PERMIT.
 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS
 CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET
 (1115 M2).
 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE
 STORIES ABOVE GRADE PLANE.
  
 10-12)COMPLIED.
  
  
 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE
 OVER 40 FEET, IN COMPLIANCE WITH 2014 FBC-B
 2603.5.7(1-7). J.W.
  
 14) BUILDING PROVISO/ DEFERRED SUBMITAL:
 SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH
 APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH
 WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR
 SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER.
 FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS
 SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN
 CHAPTER 16 OF THIS CODE.
  
 15) BUILDING PROVISO/ DEFERRED SUBMITAL:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 16) BUILDING PROVISO/ DEFERRED SUBMITAL:
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2017-04-04 Time 11:52 Sent To  
Notes
2017-04-06 08:51:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: BRICKELL GROUP
 TEL: 305-370-3988
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. APRIL 05/ 2017
 ACTION: DENIED
  
 1) COMPLIED. SUBMITTED SITE PLAN.
  
 2) 2ND REQUEST. THE 2 SOILS REPORTS SUBMITTED ARE
 COPIES THE SIGNATURE AND SEALS ARE NOT ORIGINAL.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE
  
 1ST REVIEW COMMENT. NO SOILS REPORT WAS SUBMITTED. 2014
 FBC-B1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) 2ND REQUEST / SEMI-COMPLIED. SHEET S1.0 INDICATES
 THE 1ST FLOOR FINISH FLOOR SLAB EL. +0 FEET 0 INCHES.
 PLEASE PROVIDE THE FINISH FLOOR ELEVATION IN NGVD. CITY
 FIRM MAPS ARE STILL IN NGVD.
  
 4) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD
 BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01
 BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 4A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 4B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUESTS FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 FORMS SENT TO E-MAIL ADDRESS: [email protected]
 SENT: 02/13/2017 04:09 PM.
  
 4C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4D) COMPLIED, ONLY FOR THE SPECIAL INSPECTOR NO
 DESIGNEE PAPERWORK PROVIDED.
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 4E)2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED (SOILS REPORTS, PLANS, PRODUCT
 APPROVALS, STRUCTURAL SHOP DRAWINGS, ETC? FOR DIGITAL
 PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE PERMIT
 LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT
 LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS
 OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 4G) NOTICE ONLY111 110.3.7.4.3 ALL SHORING AND
 RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 EACH SHORING AND RESHORING INSTALLATION SHALL BE
 SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE
 WITH THE SHORING DOCUMENTS BY THE CONTRACTOR.
  
 4H) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4I) NOTICE ONLY!!! 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 5) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT:
 ART IN PUBLIC PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 6) 2ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 7)NOTICE ONLY: FOUNDATION PERMIT. 107.3.3 PHASED
 APPROVAL.
 THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER
 PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDERS OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. NOTICE THE 1ST 7 COMMENTS
 ARE ALSO ON THE FOUNDATION PERMIT.
  
 VIBRO-REPLACEMENT PERMIT: 17020319, COMMENTS NEED TO BE
 ADDRESSED.
  
 8) 2ND REQUEST. THE STATED VALUE FOR THE BUILDING
 PERMIT($5,000,000.00) AND THE FOUNDATION PERMIT
 ($750,000.00) TOTALS TO $5,750,000.00 DOLLARS. THE
 CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES
 IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING.
 PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE
 ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE
 BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE
 PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE
 CALCULATED VALUE OF THE PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 9) 2ND REQUEST. NO RESPONSE COMMENT. THIS IS A 3 STORY
 STRUCTURE EACH FLOOR IS OVER 12,000 SQUARE FEET IN
 AREA. BOTH OF THESE REQUIREMENTS WILL REQUIRE THE
 BUILDING TO BE FIRE SPRINKLERED AND HAVE PLANS
 SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING PERMIT.
 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS
 CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET
 (1115 M2).
 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE
 STORIES ABOVE GRADE PLANE.
  
 10)2ND REVIEW. THIS REVIEW THERE ARE STRUCTURAL PLANS.
 SET # 1 SHEETS S1.0, S1.1, S2.0 & S3.0 ARE NOT SIGNED
 AND SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
 EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 SET # 2 NONE OF THE STRUCTURAL SHEETS ARE SIGNED AND
 SEALED. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 SET # 3 JUST RETURNED FROM THE PALM BEACH COUNTY IMPACT
 FEE OFFICE DOES NOT HAVE STRUCTURAL SHEETS.
  
  
 11) 2ND REQUEST. SEMI-COMPLIED. LIFE SAFETY PLAN. THE
 LIFE SAFETY PLAN A0.5 AND A6.1 BOTH SHOW THE 2
 STAIRWELLS WITH A CLEAR WIDTH OF 4 FOOT- 1 INCH. THE
 COVERSHEET UNDER EGRESS CAPACITY LIST THE STAIR AS 3
 FOOT WIDE. THE CODE EXCEPTION TAKEN IS 1009.4.EXCEPTION
 # 1. PLEASE NOTE THE EXCEPTION # 1 IS THE TOTAL
 OCCUPANT LOAD IS TO BE TAKEN FOR THE FLOOR. THE 2012
 IBC- AND COMMENTARY IS THE BASE CODE THE 2014 FBC-B IS
 DERIVED FROM. SEE 1005.3.1 PAGE 10-16 SECTION 1009.1.
 EXCEPTION 1, IS APPLICABLE ONLY WHEN THE ENTIRE
 OCCUPANT LOAD OF A STORY IS LESS THAN 50.
  
  
  
 12) 2ND REQUEST. THE RESPONSE NARRATIVE REFERS BACK TO
 SPECIFICATIONS SECTION 8.03 ON SHEET A-04.
 EITHER THE SPECIFICATION SECTION 8.03 IS NOT CODE
 COMPLIANT OR NOT COVERED IN THIS SECTION, SEE THE CODE
 REQUIREMENTS THAT WERE REFERENCED UNDER THE 1ST REVIEW:
 2014 FBC-B 1008.1.4.3 HORIZONTAL SLIDING DOORS.IN OTHER
 THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS
 PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS IN
 ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2 SHALL
 COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
  
 COMPLIED. 1. THE DOORS SHALL BE POWER OPERATED AND
 SHALL BE CAPABLE OF BEING OPERATED MANUALLY IN THE
 EVENT OF POWER FAILURE.
  
 COMPLIED. 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE
 METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR
 EFFORT.
  
 3) 2ND REQUEST. PLEASE UPDATE PLANS, THE PLANS INDICATE
 50 LBS. TO SET THE DOOR IN MOTION AND THERE IS NO
 REFERENCE TO THE 15 LBS. TO CLOSE THE DOOR.
 CODE SECTION (3). THE FORCE REQUIRED TO OPERATE THE
 DOOR SHALL NOT EXCEED 30 POUNDS (133 N) TO SET THE DOOR
 IN MOTION AND 15 POUNDS (67 N) TO CLOSE THE DOOR OR
 OPEN IT TO THE MINIMUM REQUIRED WIDTH.
  
 4) .2ND REQUEST.(4) THE DOOR SHALL BE OPENABLE WITH A
 FORCE NOT TO EXCEED 15 POUNDS (67 N) WHEN A FORCE OF
 250 POUNDS (1100 N) IS APPLIED PERPENDICULAR TO THE
 DOOR ADJACENT TO THE OPERATING DEVICE.
  
 5. NOT REQUIRED. THE DOOR ASSEMBLY SHALL COMPLY WITH
 THE APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE
 DETECTION IN ACCORDANCE WITH SECTION 716.5.9.3, SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL
 COMPLY WITH SECTION 716.
  
 6. 2ND REQUEST.(6)THE DOOR ASSEMBLY SHALL HAVE AN
 INTEGRATED STANDBY POWER SUPPLY.
  
 7. 2ND REQUEST.(7) THE DOOR ASSEMBLY POWER SUPPLY SHALL
 BE ELECTRICALLY SUPERVISED.
  
 8.2ND REQUEST.(8) THE DOOR SHALL OPEN TO THE MINIMUM
 REQUIRED WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF
 THE OPERATING DEVICE.
  
 1ST REVIEW COMMENT: SHEETS A1.1 & A1.2 BOTH HAVE A DOOR
 DESIGNATED A W5 OR A HORIZONTAL SLIDING DOOR. PLEASE
 SHOW COMPLIANCE WITH 2014 FBC-B 1008.1.4.3 (1-8). THERE
 ARE ISSUES THAT SECTION 8.03 EITHER ARE NOT CODE
 COMPLIANT OR NOT COVERED IN THIS SECTION. SEE LIST
 BELOW:
  
 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE
 OVER 40 FEET, INCOMPLIANE WITH 2014 FBC-B
 2603.5.7(1-7). J.W.
  
 14) BUILDING PROVISO/ DEFERRED SUBMITAL:
 SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH
 APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH
 WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR
 SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER.
 FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS
 SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN
 CHAPTER 16 OF THIS CODE.
  
 15) BUILDING PROVISO/ DEFERRED SUBMITAL:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 16) BUILDING PROVISO/ DEFERRED SUBMITAL:
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By jwitmer Date 2017-02-14 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2017-02-13 Time 13:38 Sent To  
Notes
2017-02-14 08:13:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: TBD
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. FEB. 14/ 2017
 ACTION: DENIED
  
 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
 MISSING DOCUMENTS: SURVEY AND OR SITE PLAN
 SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL
 BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION
 AND EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND
 THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, FLOOD
 HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE BOUNDARY LINE SURVEY.
 IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL SHOW
 CONSTRUCTION TO BE DEMOLISHED AND THE
 LOCATION AND SIZE OF EXISTING STRUCTURES AND
 CONSTRUCTION THAT ARE TO REMAIN ON THE SITE OR PLOT.
 THE BUILDING OFFICIAL IS AUTHORIZED TO WAIVE OR MODIFY
 THE REQUIREMENT FOR A SITE PLAN WHEN THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 ARCHITECTURAL FLOOR PLANS OF BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
  
 2) NO SOILS REPORT WAS SUBMITTED. 2014 FBC-B1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3) PLEASE NOTE NO CIVIL SHEETS SUBMITTED, NO
 ARCHITECTURAL SHEETS SUBMITTED AND SHEET S1.0 INDICATES
 THE 1ST FLOOR FINISH FLOOR SLAB EL. +0 FEET 0 INCHES.
 PLEASE PROVIDE THE FINISH FLOOR ELEVATION IN NGVD. CITY
 FIRM MAPS ARE STILL IN NGVD.
  
 4) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD
 BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01
 BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS SENT TO E-MAIL ADDRESS: [email protected]
 SENT: 02/13/2017 04:09 PM.
  
 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 4G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 5) PLEASE NOTE ZONING REQUIREMENT: ART IN PUBLIC
 PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7)NOTICE ONLY: FOUNDATION PERMIT. 107.3.3 PHASED
 APPROVAL.
 THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER
 PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED.
  
 NOTICE THE 1ST 7 COMMENTS ARE ALSO ON THE FOUNDATION
 PERMIT.
  
 8) THE STATED VALUE FOR THE BUILDING
 PERMIT($5,000,000.00) AND THE FOUNDATION PERMIT
 ($750,000.00) TOTALS TO $5,750,000.00 DOLLARS. THE
 CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES
 IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING.
 PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE
 ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE
 BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE
 PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE
 CALCULATED VALUE OF THE PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 9) THIS IS A 3 STORY STRUCTURE EACH FLOOR IS OVER
 12,000 SQUARE FEET IN AREA. BOTH OF THESE REQUIREMENTS
 WILL REQUIRE THE BUILDING TO BE FIRE SPRINKLERED AND
 HAVE PLANS SUBMITTED BEFORE THE ISSUANCE OF THE
 BUILDING PERMIT.
 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS
 CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET
 (1115 M2).
 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE
 STORIES ABOVE GRADE PLANE.
  
 10) THERE ARE NO STRUCTURAL DRAWINGS WITHIN THIS SET OF
 PLANS. THE COVERSHEET INDICATES THIS IS A DESIGN BUILD.
 THERE WERE SOME PLANS WITHIN THE FOUNDATION PLAN BUT NO
 PLANS WERE SUBMITTED NOR SHOW ON THE INDEX OF DRAWINGS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 THRESHOLD INSPECTION PLAN
 STAIR SYSTEMS
  
 11) THE SET OF PLANS ARE MISSING A LIFE SAFETY PLAN FOR
 EVERY FLOOR LEVEL.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 COMMON PATH OF EGRESS TRAVEL
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
  
 12) SHEETS A1.1 & A1.2 BOTH HAVE A DOOR DESIGNATED A W5
 OR A HORIZONTAL SLIDING DOOR. PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-B 1008.1.4.3 (1-8).
  
 13)SHEET A4.1 & THE A5 SERIES OF PLANS INDICATES THE
 USE OF FOAM EFIS BRACKETS AND EFIS SOFFITS ABOVE 40
 FEET ABOVE GRADE. PLEASE SHOW COMPLIANCE WITH FBC-B
 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH
 THE FOLLOWING LIMITATIONS:
 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED
 TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
  
 14) SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER
 WHICH APPEARS WILL STAY IN THE OPEN POSITION DURING A
 HIGH WIND EVENT, PLEASE PROVIDE EITHER PRODUCT
 APPROVALS FOR SUCH OR SITE SPECIFIC ENGINEERING FOR
 METAL SHUTTER. FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND
 CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST THE LOADS
 SET FORTH IN CHAPTER 16 OF THIS CODE.
  
 15) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 16) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By jleahy Date 2017-06-08 Time 07:10 Rev Time 0.00
Received By jleahy Date 2017-06-08 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By vperez Date 2017-03-27 Time 07:29 Rev Time 0.00
Received By vperez Date 2017-03-27 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-07 Cont ID  
Sent By albarran Date 2017-02-07 Time 13:50 Rev Time 0.00
Received By albarran Date 2017-02-07 Time 07:49 Sent To  
Notes
2017-02-07 13:51:27ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: NEW STORAGE BLDG.
 JOB ADDRESS: 750 PONCE DE LEON PL.
 DESCRIPTION:
 MASTER PERMIT: 17011176
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. ELECTRICAL SUB PERMIT REQUIRED
 2. ALL FIRE ALARM WORK REQUIRES A SEPARATE PERMIT WITH
 ITS OWN SUBMITTAL PACKAGE.
 3. THERE IS A MISSING EMERGENCY LIGHT IN THE LOUNGE
 AREA: SECTION 32.7-33.5/I .5-M
 4. THERE IS A MISSING EXIT LIGHT IN SECTION 1-2/G-H
 5. THERE IS A MISSING EXIT LIGHT IN THE CORRIDOR OF
 23-35/F-G
 6. THE DRINKING FOUNTAIN IS ELECTRIC SHALL BE ON A GFI
 PROTECTED CIRCUIT NOT INDICATED ON PANEL
 7. THERE IS AN EMERGENCY LIGHT MISSING IN EACH OF THE
 TOILET ROOMS OF THE SECOND FLOOR.
 8. RELOCATE THE SERVICE OUTLETS FOR THE HVAC SO THEY
 ARE NOT BEHIND THE UNITS.
 9. IF A FIRE PUMP IS REQUIRED PER THE FIRE ALARM REVIEW
 (FIRE SPRINKLERS) IS REQUIRED, A REVISED RISER DRAWING
 SHOWING THE FIRE PUMP EQUIPMENT AND CONNECTIONS ALONG
 WITH THE ADDITIONAL LOADS SHALL BE SUBMITTED FOR
 ELECTRICAL REVIEW AS WELL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2017-08-14 Cont ID  
Sent By mkhan Date 2017-08-13 Time 12:50 Rev Time 0.00
Received By mgonzale Date 2017-07-13 Time 12:50 Sent To  
Notes
2017-08-14 10:48:47PLANS REVISED, APPROVED. 08/14/2017
 MGONZALEZ
2017-07-13 13:42:42COMMENTS WERE EMAILED TO EOR MICHAEL GRZELKA, P.E. ON
 JUNE 16, 2017 FOR THE CIVIL PLANS AND HE WAS ASLO
 INFORMED ABOUT ALL PALM BEACH COUNTY PERMIT
 REQUIREMENTS.
  
 ONCE FINAL REVISED PLANS AND PALM BEACH COUNTY PERMITS
 (E.G. RIGHT-OF-WAY PERMIT FOR OPEN CUT ETC.) ARE
 RECIVED ARE RECEIVED (IN OUR DEPARTMENT) AND DEEM
 ACCEPTABLE WE WILL SIGN OFF ON THIS PERMIT.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2017-05-30 Cont ID  
Sent By mkhan Date 2017-05-11 Time 11:00 Rev Time 0.00
Received By mkhan Date 2017-04-24 Time 10:59 Sent To  
Notes
2017-05-30 11:04:44REVISED PLANS WERE SUBMITTED ON 4/24/2017 FOR THE
 SEPARATE 'ENGINEERING APPROVAL APPLICATION'
 (E17010028). THERE ARE STILL OUTSTANDING ISSUES AND
 COMMENTS WERE SENT TO MICHAEL GRIZELKA, P.E., THE CIVIL
 ENGINEER FOR THIS PROJECT. EXPECTING TO RECEIVE REVISED
 PLANS WITH THE COMMENTS ADDRESSED AT THE 3RD ROUND
 REVIEW. THIS PERMIT IS FAILED AT THIS REVIEW CYCLE
 UNTIL ENGINEERING REVIEW COMMENTS ARE ADDRESSED.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 OFFICE: (561) 494-1124
 FAX: (561) 494-1116
 E-MAIL: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-03-21 Cont ID  
Sent By mkhan Date 2017-03-17 Time 16:16 Rev Time 0.00
Received By mkhan Date 2017-03-17 Time 16:16 Sent To  
Notes
2017-03-17 16:19:11SEPARATE 'ENGINEERING APPROVAL APPLICATION' (E17010028)
 IS SUBMITTED FOR THIS PROJECT. FOR WHICH, REVIEW IS
 COMPLETE AND COMMENTS WERE SENT TO MICHAEL GRIZELKA,
 THE CIVIL ENGINEER FOR THIS PROJECT. EXPECTING TO
 RECEIVE REVISED PLANS WITH THE COMMENTS ADDRESSED AT
 THE 2ND ROUND REVIEW. THIS PERMIT IS FAILED AT THIS
 REVIEW CYCLE UNTIL ENGINEERING REVIEW COMMENTS ARE
 ADDRESSED.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 OFFICE: (561) 494-1124
 FAX: (561) 494-1116
 E-MAIL: [email protected]
2017-03-02 16:55:50MKAHN REVIEWING UNDER E17010028

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-05-12 Cont ID  
Sent By pleduc Date 2017-05-12 Time   Rev Time 0.00
Received By pleduc Date 2017-05-12 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-16 Cont ID  
Sent By pleduc Date 2017-03-16 Time   Rev Time 0.00
Received By pleduc Date 2017-03-15 Time 16:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By wjolin Date 2017-02-01 Time 15:20 Rev Time 0.00
Received By wjolin Date 2017-02-01 Time 14:21 Sent To  
Notes
2017-02-01 14:27:241620 NORTH CONGRESS AVENUE
 PERMIT #17011176
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 NO CIVIL DRAWINGS SUBMITTED SHOWING AREA SITE PLAN,
 FIRE DEPARTMENT ACCESS ROADS, UNDERGROUND FIRE MAINS
 AND NEW/EXISTING FIRE HYDRANTS.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OF 50
 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ANY FIRE RATED
 WALLS, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 ARE ANY CONSTRUCTION TRAILERS INTENDED TO OCCUPY THE
 SITE? THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-14 Cont ID  
Sent By cpuell Date 2017-07-14 Time 11:09 Rev Time 0.00
Received By cpuell Date 2017-06-07 Time 13:48 Sent To  
Notes
2017-06-07 13:50:20IN: SUBMITTED 6/07/17/ BIN:C39. J. W. SHEETS E1.1,
 E1.2, E-1.3 E-1.4 & E1.5 ALL NEED UPDATES NOT SIGNED
 AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-14 Cont ID  
Sent By cpuell Date 2017-07-14 Time 11:09 Rev Time 0.00
Received By cpuell Date 2017-04-26 Time 11:20 Sent To  
Notes
2017-04-27 11:29:29C39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-12 Cont ID  
Sent By gjohnson Date 2017-04-12 Time 08:35 Rev Time 0.00
Received By gjohnson Date 2017-03-14 Time 14:45 Sent To  
Notes
2017-03-14 14:50:06C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-02 Cont ID  
Sent By skennedy Date 2017-03-02 Time 16:56 Rev Time 0.00
Received By skennedy Date 2017-01-31 Time 16:00 Sent To  
Notes
2017-01-31 16:00:34C39

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2017-04-06 Time 08:54 Sent To  
Notes
2017-04-06 08:56:45PALM BEACH COUNTY IMPACT FEE OFFICE
 PAID UNDER THE FOUNDATION PERMIT : 17011177
 MARCH 16/ 2017
 MU-2017-7076
 SQ. FT. 104,811
 AMOUNT PAID: $58,893.30.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By jwitmer Date 2017-02-14 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2017-02-13 Time 13:38 Sent To  
Notes
2017-02-14 08:02:59IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-07-05 Cont ID  
Sent By ccole Date 2017-07-05 Time 10:18 Rev Time 0.00
Received By ccole Date 2017-07-05 Time 09:50 Sent To  
Notes
2017-07-05 10:49:05MECHANICAL PROVISO:
  
 1) COMMISSIONING REPORT REQUIRED AT FINAL
 INSPECTION/HOLD ON CO.
  
 CCOLE- 7/5/17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-05-04 Cont ID  
Sent By ccole Date 2017-05-04 Time 07:12 Rev Time 0.00
Received By ccole Date 2017-05-03 Time 16:27 Sent To  
Notes
2017-05-04 07:21:201ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17011176
 5/4/17
  
 1) THE AC CALCULATIONS FOR THE FC-6 INDICATE THE UNIT
 IS OVERSIZED. THE CALCULATION INDICATES 2.2 TONS OF
 COOLING REQUIRED- THE SCHEDULE SHOWS FC-6 IS A 5-TON
 UNIT- SEE SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
 PLEASE NOTE THAT THE FC-6 CALULATION IS LABELED AS
 "OFFICE" HOWEVER THE UNIT APPEARS TO BE LOCATED IN THE
 STORAGE AREA.
  
 2) THE AC CALCS ARE INDICTING FC-7 TO BE LOCATED ON THE
 2ND FLOOR, HOWEVER THE PLAN SHOWS IT ON THE 1ST FLOOR.
  
 3) THE DUCT SMOKE DETECTORS FOR THE HEAT PUMPS SHALL BE
 LIOCATED UPSTREAM OF THE OUTSIDE AIR DUCT CONNECTION-
 SEE SECTION 606.2.1 AND CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-24 Cont ID  
Sent By ccole Date 2017-03-24 Time 10:28 Rev Time 0.00
Received By ccole Date 2017-03-24 Time 10:28 Sent To  
Notes
2017-03-24 10:36:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17011176
 3/24/17
  
 1) IN RESPONSE TO COMMENT #1 FROM THE 1ST REVIEW
 REQUESTING DOCUMENTATION OF ENERGY CONSERVATION
 COMPLIANCE, AN OUTDATED ENERGYGAUGE FORM 506-2010 HAS
 BEEN SUBMITTED. PLEASE SEE SECTION C101.5.1 FBC-14
 ENERGY CONSERVATION AND SUBMIT AN UP-TO-DATE COMPLIANCE
 FORM.
  
 2) THE REQUESTED AC COOLING AND HEATING CALCULATIONS
 WERE NOT SUBMITTED- PLEASE COMPLY.
  
 3) AS REQUESTED IN THE 1ST REVIEW, PLEASE SUBMIT TWO
 COPIES OF THE MIAMI-DADE NOA #16-0112.02 FOR THE
 LOUVER.
  
 4) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION-
 AC SYSTEM COMMISSIONING IS REQUIRED.
  
 C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
 PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE
 REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE
 OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN
 ACCORDANCE THE PROVISIONS OF THIS SECTION.
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE
 OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS
 C408.2.4 AND C408.2.5.
  
 2A) C408.2.1 COMMISSIONING PLAN.
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED
 DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL
 INCLUDE THE FOLLOWING ITEMS:
  
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED
 TO CALIBRATIONS AND ECONOMIZER CONTROLS.
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
 DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
 5. MEASURABLE CRITERIA FOR PERFORMANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By ccole Date 2017-02-02 Time 16:33 Rev Time 0.00
Received By ccole Date 2017-02-02 Time 15:23 Sent To  
Notes
2017-02-02 16:59:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17011176
 2/2/17
  
 1) THE PROPOSED BUILDING SHALL BE IN DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE FBC-14 ENERGY
 CONSERVATION CODE. REFER TO SECTIONS C101.2 AND C401.2
 AND PROVIDE COMPLIANCE DOCUMENTATION.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 3) SHEET M0.1, NOTE #15: PLEASE UPDATE THE SMACNA
 REFERENCE TO THE CURRENT 2005 EDITION AND PROVIDE
 TYPICAL DUCT HANGING AND CONNECTION DETAILS ON THE
 PLANS.
  
 4) M0.1, NOTE #34: PLEASE CLARIFY IF THE AC SYSTEMS
 WILL BE LINKED TOGETHER FOR SIMULTANEOUS FAN SHUTDOWN
 IF ANY SINGLE DUCT SMOKE DETECTOR ACTIVATES.
  
 5) M0.2: PROVIDE THE WIND DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSERS IN COMPLIANCE WITH
 SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609
 FBC-14 BUILDING.
  
 6) SUBMIT TWO COPIES OF A VALID FLORIDA PRODUCT
 APPROVAL AND/OR MIAMI-DADE NOA FOR THE O/A INTAKE AND
 EXHAUST LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 14:17 Rev Time 0.00
Received By gjohnson Date 2017-07-05 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 16:21 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 16:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-11 Cont ID  
Sent By gjohnson Date 2017-04-11 Time 17:48 Rev Time 0.00
Received By gjohnson Date 2017-04-11 Time 17:26 Sent To  
Notes
2017-04-11 17:50:182ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT COMPLIED.
  
 5. A CLEAN OUT IS REQUIRED AT THE BASE OF ANY WASTE OR
 SOIL STACK. PER FBC PL 708.3.4
  
 7. TEMPERED WATER IS REQUIRE AT ALL LAVATORY'S IN
 PUBLIC BATHROOMS. PER FBC PL 416.5
  
 8.SHOW THE REQUIRED TRAP PRIMERS ON ALL FLOOR DRAINS.
 PER FBC PL 1002.4
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By gjohnson Date 2017-03-02 Time 12:09 Rev Time 0.00
Received By gjohnson Date 2017-03-02 Time 06:23 Sent To  
Notes
2017-03-02 12:15:231ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WILL THE SINGLE USER BATHROOM NEXT TO THE RETAIL
 SPACE BE ACCESSIBLE FOR THE OCCUPANTS OF THE RETAIL
 SPACE TO USE, IT APPEARS THAT IT CAN ONLY BE ACCESSED
 THROUGH THE STORAGE FACILITY PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE COFFEE BAR SHALL COMPLY WITH FBC ACC
 902.2,902.3, 308
  
 3.SHT.P0.2 WATER HEATER DETAIL SHALL SHOW PAN. PER FBC
 PL 504.7
  
 4.P1.1. P1.2 DISCHARGE FROM ELEVATOR SUMP SHALL
 TERMINATE A MIN OF 12" FROM BUILDING. FBC 1503.7
  
 5. A CLEAN OUT IS REQUIRED AT THE BASE OF ANY WASTE OR
 SOIL STACK. PER FBC PL 708.3.4
  
 6. A CLEAN OUT IS REQUIRED @ 100' INTERVALS IN THE
 BUILDING SEWER. PER FBC PL 708.3.2
  
 7. TEMPERED WATER IS REQUIRE AT ALL LAVATORY'S IN
 PUBLIC BATHROOMS. PER FBC PL 416.5
  
 8.SHOW THE REQUIRED TRAP PRIMERS ON ALL FLOOR DRAINS.
 PER FBC PL 1002.4
  
 9. PLEASE PROVIDE A WATER RISER. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2017-06-02 Cont ID  
Sent By jwitmer Date 2017-06-02 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2017-06-02 Time 13:45 Sent To  
Notes
2017-06-02 13:47:10COMPLETE THRESHOLD DOCUMENTS ARE FOUND UNDER THE
 FOUNDATION PERMIT 17011177.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2017-04-06 Time 08:52 Sent To  
Notes
2017-04-06 08:54:00THRESHOLD BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: TBD
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. APRIL 05/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD
 BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01
 BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 1A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUESTS FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 FORMS SENT TO E-MAIL ADDRESS: [email protected]
 SENT: 02/13/2017 04:09 PM.
  
 1C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) COMPLIED, ONLY FOR THE SPECIAL INSPECTOR NO
 DESIGNEE PAPERWORK PROVIDED.
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 1E)2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED (SOILS REPORTS, PLANS, PRODUCT
 APPROVALS, STRUCTURAL SHOP DRAWINGS, ETC? FOR DIGITAL
 PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE PERMIT
 LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT
 LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS
 OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) NOTICE ONLY111 110.3.7.4.3 ALL SHORING AND
 RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 EACH SHORING AND RESHORING INSTALLATION SHALL BE
 SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE
 WITH THE SHORING DOCUMENTS BY THE CONTRACTOR.
  
 1H) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) NOTICE ONLY!!! 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By jwitmer Date 2017-02-14 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2017-02-14 Time 08:30 Sent To  
Notes
2017-02-14 08:31:26SEE BUILDING NOTES 4A-4I.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2017-08-08 Cont ID  
Sent By eschneid Date 2017-08-08 Time 08:57 Rev Time 0.25
Received By eschneid Date 2017-08-08 Time 08:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2017-06-26 Cont ID  
Sent By eschneid Date 2017-06-26 Time 11:29 Rev Time 0.25
Received By eschneid Date 2017-06-26 Time 11:12 Sent To  
Notes
2017-06-26 11:29:24FAILED PENDING THE SUBMITTAL OF THE PALM BEACH COUNTY
 DRIVEWAY CONNECTION APPROVAL (SEE COMMENT NO. 1.
  
 1) IN ACCORDANCE WITH RESOLUTION NO. 201-16, WHICH
 APPROVED THIS SITE DEVELOPMENT, PRIOR TO ZONING
 APPROVAL OF THIS BUILDING PERMIT PROVIDE THE PLANNING
 DIVISION WITH A COPY OF THE APPROVED DRIVEWAY
 CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING
 FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE.
  
 2) PLANS HAVE BEEN STAMPED AS THEY COMPLY WITH ZONING
 REQUIREMENTS.
  
 3) THERE ARE DOORS SHOWN ON VARIOUS PLANS IN NEW
 LOCATIONS AND THERE ARE MORE HEAT PUMPS (MECHANICAL
 EQUIPMENT) SHOWN ALONG THE REAR OF THE BUILDING AS
 COMPARED TO THE SITE, LANDSCAPE, ELEVATION AND CIVIL
 PLANS APPROVED AS PART OF THE PLANNING APPROVAL
 PROCESS. SINCE THESE PLANS HAVE CHANGED, PRIOR TO C.O.
 OF THIS BUILDING, AN AS BUILT MINOR AMENDMENT IS
 REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION.
  
 4) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. SIGNAGE
 B. LANDSCAPE
 C. IRRIGATION
 D. SITE LIGHTING
 E. PARKING LOT STRIPING
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2017-05-25 Cont ID  
Sent By eschneid Date 2017-05-25 Time 14:56 Rev Time 1.25
Received By eschneid Date 2017-05-08 Time 17:05 Sent To  
Notes
2017-05-25 14:56:11FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT UPDATED COMMENT: FOUNDATION SHEET S1.1 DOES
 NOT SHOW THE RELOCATED DOOR LOCATION THAT IS REFLECTED
 ON THE REMAINDER OF THE PLANS. ALL PLANS SHALL SHOW THE
 SAME CONDITIONS. THE STRUCTURAL PLAN MUST BE CORRECTED
 PRIOR TO ZONING APPROVAL OF THIS BUILDING PERMIT. THE
 SITE AND CIVIL PLANS SHALL BE CORRECTED PRIOR TO C.O.
 (SEE COMMENT NO. 3 BELOW).
  
 2) REPEAT COMMENT: THE FIRST FLOOR ELECTRICAL SITE
 PLANS SHOW HEAT PUMPS (HP-5 AND HP-7) ON THE SOUTH SIDE
 OF THE BUILDING. MECHANICAL EQUIPMENT IS NOT PERMITTED
 BETWEEN THE BUILDING AND CONGRESS AVENUE. SHEET M1.1
 CORRECTLY SHOWS BOTH OF THESE UNITS TO THE REAR OF THE
 BUILDING.
  
 3) THERE ARE DOORS SHOWN ON VARIOUS PLANS IN NEW
 LOCATIONS AND THERE ARE MORE HEAT PUMPS (MECHANICAL
 EQUIPMENT) SHOWN ALONG THE REAR OF THE BUILDING AS
 COMPARED TO THE SITE, LANDSCAPE, ELEVATION AND CIVIL
 PLANS APPROVED AS PART OF THE PLANNING APPROVAL
 PROCESS. SINCE THESE PLANS HAVE CHANGED, PRIOR TO C.O.
 OF THIS BUILDING, AN AS BUILT MINOR AMENDMENT IS
 REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION.
  
 4) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 201-16, WHICH APPROVED THIS SITE DEVELOPMENT, PRIOR TO
 ZONING APPROVAL OF THIS BUILDING PERMIT PROVIDE THE
 PLANNING DIVISION WITH A COPY OF THE APPROVED DRIVEWAY
 CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING
 FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE.
  
 5) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. SIGNAGE
 B. LANDSCAPE
 C. IRRIGATION
 D. SITE LIGHTING
 E. PARKING LOT STRIPING
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-03-30 Cont ID  
Sent By eschneid Date 2017-03-30 Time 09:46 Rev Time 2.00
Received By eschneid Date 2017-03-28 Time 18:05 Sent To  
Notes
2017-03-30 09:47:10FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT UPDATED COMMENT: THE FOLLOWING PLANS DO NOT
 SHOW THE SAME FIRST FLOOR CONDITIONS - ARCHITECTURAL
 SITE PLAN (SHEETS A0.5 AND A1.0) THE LIFE SAFETY PLAN
 (SHEET A0.5), PARTIAL FIRST FLOOR PLANS (SHEETS A1.1
 AND A1.2), THE SITE PLAN (SP-1), CIVIL PLAN (SHEET 2 OF
 7), SOUTH AND EAST ELEVATIONS (SHEETS A4.1 AND S1.9),
 PARTIAL 1ST FLOOR ELECTRICAL PLAN (SHEET E1.2), PARTIAL
 1ST FLOOR FIRE PROTECTION PLAN (SHEET FP1.1),
 STRUCTURAL PLANS (SHEETS S1.0 AND S1.1) - EX. DOOR
 PLACEMENT FOR THE SPRINKLER ROOM (FROM THE FRONT TO THE
 SIDE) AND ELECTRIC ROOM (FROM INSIDE TO OUTSIDE) AND
 NEW DOOR ON SOUTH ELEVATION OF LIFE SAFETY PLAN BY THE
 RETAIL BAY. ALL PLANS SHALL SHOW THE SAME CONDITIONS.
 THE ARCHITECTURAL, ELECTRICAL, STRUCTURAL AND FIRE
 PROTECTION PLANS (AND ANY OTHER PLANS WHICH DO NOT
 MATCH) SHALL BE CORRECTED PRIOR TO ZONING APPROVAL OF
 THIS BUILDING PERMIT. THE SITE AND CIVIL PLANS SHALL BE
 CORRECTED PRIOR TO C.O. (SEE COMMENT NO. 4 BELOW).
  
 2) WHY ARE THERE TWO ARCHITECTURAL SITE PLANS, WHICH
 APPEAR THE SAME, WITH TWO DIFFERENT SHEET NUMBERS? WHY
 DOES THE LIFE SAFETY PLAN HAVE THE SAME SHEET NUMBER AS
 ONE OF THE ARCHITECTURAL SITE PLANS?
  
 3) THE FIRST FLOOR ELECTRICAL SITE PLANS SHOW HEAT
 PUMPS (HP-5 AND HP-7) ON THE SOUTH SIDE OF THE
 BUILDING. MECHANICAL EQUIPMENT IS NOT PERMITTED BETWEEN
 THE BUILDING AND CONGRESS AVENUE. SHEET M1.1 CORRECTLY
 SHOWS BOTH OF THESE UNITS TO THE REAR OF THE BUILDING.
  
 4) AS STATED IN COMMENT NO. 1 ABOVE, THERE ARE DOORS
 SHOWN ON VARIOUS PLANS IN NEW LOCATIONS AND THERE ARE
 MORE HEAT PUMPS (MECHANICAL EQUIPMENT) SHOWN ALONG THE
 REAR OF THE BUILDING AS COMPARED TO THE SITE,
 LANDSCAPE, ELEVATION AND CIVIL PLANS APPROVED AS PART
 OF THE PLANNING APPROVAL PROCESS. SINCE THESE PLANS
 HAVE CHANGED, PRIOR TO C.O. OF THIS BUILDING, AN AS
 BUILT MINOR AMENDMENT IS REQUIRED TO BE SUBMITTED TO
 THE PLANNING DIVISION.
  
 5) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 201-16, WHICH APPROVED THIS SITE DEVELOPMENT, PRIOR TO
 ZONING APPROVAL OF THIS BUILDING PERMIT PROVIDE THE
 PLANNING DIVISION WITH A COPY OF THE APPROVED DRIVEWAY
 CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING
 FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE.
  
 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. SIGNAGE
 B. LANDSCAPE
 C. IRRIGATION
 D. SITE LIGHTING
 E. PARKING LOT STRIPING
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By eschneid Date 2017-02-23 Time 11:50 Rev Time 2.00
Received By eschneid Date 2017-02-22 Time 15:38 Sent To  
Notes
2017-02-23 11:58:13FAILED
  
 1) PROVIDE THE SURVEY/SITE PLAN SHOWING THE BUILDING
 SETBACKS AND SITE DATA.
  
 2) THE FIRST FLOOR PLANS DO NOT MATCH THE ARCHITECTURAL
 SITE PLAN ? DOOR PLACEMENT FOR THE SPRINKLER ROOM (FROM
 THE FRONT TO THE SIDE). ALL PLANS SHALL SHOW THE SAME
 CONDITIONS.
  
 3) THE NEW LOCATION OF THE SPRINKLER ROOM DOOR ALSO
 DIFFERS FROM THE PLANS APPROVED AS PART OF THE RECENT
 MINOR AMENDMENT. PRIOR TO C.O. OF THIS BUILDING, AN AS
 BUILT MINOR AMENDMENT IS REQUIRED TO BE SUBMITTED TO
 THE PLANNING DIVISION.
  
 4) PRIOR TO ZONING APPROVAL OF THE BUILDING PERMIT
 PROVIDE THE PLANNING DIVISION WITH A COPY OF THE
 APPROVED DRIVEWAY CONNECTION PERMIT FROM PALM BEACH
 COUNTY ENGINEERING FOR THE DRIVEWAY CONNECTIONS TO
 NORTH CONGRESS AVENUE.
  
 5) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED, AND APPROVED BY THE PLANNING
 DIVISION.
  
 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. SIGNAGE
 B. LANDSCAPE
 C. IRRIGATION
 D. SITE LIGHTING
 E. PARKING LOT STRIPING
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  