| Plan Review Stops For Permit 17011073 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2017-03-07 16:48:21 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING | | | TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS | | | LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND | | | REVISE THE DESIGN PRESSURES ON SHEET 5B. ALSO, CLARIFY | | | WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00? | | | 2- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL. | | | SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND | | | SPACING. | | | 3- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) REVISE DOOR TYPE INFORMATION SHOWN ON PAGE 3 OF 4. | | | WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR ENTRY | | | DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR NEEDS TO | | | BE ENTERED IN THE WINDOW AREA. | | | B) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR | | | THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON | | | SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-06 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-06 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2017-03-06 18:06:41 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW | | | COMMENTS. | | | CODE; FBC 5TH EDITION (2014). | | | | | | 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING | | | TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS | | | LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND | | | REVISE THE DESIGN PRESSURES ON SHEET 5B. ALSO, CLARIFY | | | WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00? | | | | | | 2- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL. | | | SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND | | | SPACING. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | 3- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) REVISE/CLARIFY DOOR TYPE INFORMATION SHOWN ON PAGE 3 | | | OF 4. WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR | | | ENTRY DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR | | | NEEDS TO BE ENTERED IN THE WINDOW AREA AS REQUIRED BY | | | SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. | | | | | | B) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR | | | THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON | | | SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-02-15 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-02-15 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-02-15 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-02-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-15 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-15 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-01-27 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2017-03-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-06 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-06 |
Time |
18:24 |
Sent To |
|
|
| Notes |
| 2017-03-06 18:24:54 | $10,003.08 PAID. MU-2017-1848. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-07 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-07 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2017-02-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-15 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-15 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-03-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-06 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-06 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2017-03-06 18:36:03 | A) ROOF TILE NOA 16-0314.08 | | | B) ROOF TILE UNDERLAYMENT NOA 15-0410.04. | | | C) ROOF VENTS FL16588-R1 AND NOA 13-0122.07 | | | D) ROOF TILE ADHESIVE FL6332-R5. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-02-07 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-02-07 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-02-07 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2017-02-07 16:50:35 | ROUTED TO RAY CARANCI | | 2017-02-07 16:43:45 | 2/7/17- PASSED | | | | | | IBIS RESIDENTIAL PLANNED DEVELOPMENT | | | | | | ONE KITCHEN ONE UNIT | | | NON-ZERO SETBACK IS 14.07FT. MEETING 7.5FT. REQUIREMENT | | | REAR SETBACK IS 84.94 MEETS 15FT. REQUIREMENT | | | A/C UNIT IS NOT IN A REQUIRED SETBACK | | | ONE STORY MEETS HEIGHT LIMIT | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | |
|
|