Plan Review Details - Permit 17011057
Plan Review Stops For Permit 17011057
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-02 Cont ID  
Sent By jwitmer Date 2017-03-02 Time 06:45 Rev Time  
Received By jwitmer Date 2017-03-02 Time 06:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-24 Cont ID  
Sent By vperez Date 2017-02-24 Time 11:45 Rev Time 0.00
Received By vperez Date 2017-02-24 Time 11:36 Sent To  
Notes
2017-02-24 11:51:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PROVISO COMMENTS:
  
 1. PLEASE SHOW ON DOCUMENTS THE ELECTRICAL INFORMATION
 OF FEEDER AND BRANCH CIRCUITS FEEDING SPLASH PAD PUMPS.
 REFER TO MASTER DRAWINGS SHOWING LOADS AND PANEL BOARDS
 FEEDING AREA.
 2. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-11 Cont ID  
Sent By cpuell Date 2017-05-11 Time 08:49 Rev Time 0.00
Received By cpuell Date 2017-04-26 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-21 Cont ID  
Sent By tklarge Date 2017-04-21 Time 06:46 Rev Time 0.00
Received By tklarge Date 2017-04-12 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-27 Cont ID  
Sent By ajones Date 2017-03-27 Time 13:23 Rev Time 0.00
Received By ajones Date 2017-02-21 Time 15:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-05-11 Cont ID  
Sent By tklarge Date 2017-05-11 Time 08:37 Rev Time 0.00
Received By tklarge Date 2017-05-11 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-21 Cont ID  
Sent By tklarge Date 2017-04-21 Time 06:45 Rev Time 0.00
Received By tklarge Date 2017-04-21 Time 05:50 Sent To  
Notes
2017-04-20 14:28:241) THE CHEMICAL FEEDERS SHALL COMPLY WITH 2014 FBC
 SEC.454.1.9.8.3. AUTOMATED OXIDATION REDUCTION
 POTENTIAL (ORP) AND PH CONTROLLERS WITH SENSING PROBES
 SHALL BE INSTALLED TO ASSIST IN MAINTAINING PROPER
 DISINFECTION AND PH LEVELS. SEE COMMENT #6 FROM
 PREVIOUS REVIEW DATED 3/1/17. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-01 Cont ID  
Sent By tklarge Date 2017-03-01 Time 13:48 Rev Time 0.00
Received By tklarge Date 2017-03-01 Time 04:25 Sent To  
Notes
2017-03-01 11:56:391) SHT. CF1.0 - THE PLANS SHOW THE FILTER TANK OVERFLOW
 DISCHARGING TO THE SANITARY SYSTEM. THE OVERFLOW WATER
 SHALL NOT DISCHARGE TO THE CITY OF WEST PALM BEACH
 SANITARY SYSTEM OR THE STORM SYSTEM PER CITY OF WPB
 CODE OF ORDINANCES ARTICLE III, SEC. 90-126 ( SANITARY)
 & ARTICLE 5, SEC. 90-203 (A) .
 SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE.
 DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE INTO
 THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE PASS
 THROUGH OR INTERFERE WITH THE OPERATION OR PERFORMANCE
 OF THE WWF. NO USER SHALL DISCHARGE INTO THE WWF OR ANY
 CONNECTED SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY
 OF THE FOLLOWING:
 (B) (5) - STORMWATER, SURFACE WATER, GROUNDWATER,
 ARTESIAN WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE,
 SWIMMING POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
 SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
 PLEASE CONTACT MANNY GONZALEZ IN CITY'S ENGINEERING
 DEPARTMENT FOR FURTHER DIRECTION ON THIS MATTER. HIS
 CONTACT INFO IS: [email protected], 561-494-1085.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN COVERS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. CF5.0 - TANK PLAN VIEW SHOWS A 6 INCH MAIN
 DRAIN ON THE RIGHT SIDE OF THE TANK AND THE TANK
 ELEVATION VIEW BELOW IT SHOWS A 8 INCH MAIN DRAIN. THE
 EQUIPMENT SCHEMATIC ALSO SHOWS AN 8 INCH MAIN DRAIN
 FROM THE SPLASH PAD. CLARIFY.
 4) SHT. CF5.0 - THE DECK SHOWER DETAIL DOES NOT
 CORRESPOND TO THE SHOWER UNIT SPECIFIED UNDER PERMIT
 #16120787. CLARIFY. THE SHOWER SHALL COMPLY WITH THE
 2014 FBC -ACCESS
 5) SHT. CF5.0 -THE TANK PLAN VIEW SHOWS A 2 INCH
 OVERFLOW TO A 6 INCH S.S. I DON'T KNOW IF THIS IS
 SUPPOSED TO BE A SANITARY SEWER OR STORM SEWER BUT
 SHT.CF1.0 SHOWS A 4 INCH SANITARY SEWER. IF APPROVAL IS
 RECEIVED FROM THE CITY TO DISCHARGE THE FILTER TANK
 OVERFLOW TO THE SANITARY SEWER THIS SIZE DISCREPANCY
 NEEDS TO BE CORRECTED. THE SPLASH PAD EQUIPMENT
 SCHEMATIC SHOWS THE 2 INCH OVERFLOW TO THE STORM WHICH
 IS NOT PERMITTED. CLARIFY. WPB AMEND. TO FBC SEC.
 107.2.1.
 6) THE CHEMICAL FEEDERS SHALL COMPLY WITH 2014 FBC SEC.
 454.1.9.8.3.
 CHEMICAL FEEDERS SHALL BE IN ACCORDANCE WITH SECTION
 454.1.6.5; EXCEPT THAT THE DISINFECTION FEEDER SHALL BE
 CAPABLE OF FEEDING 12 PPM OF FREE CHLORINE TO THE
 PRESSURE SIDE OF THE RECIRCULATION SYSTEM OR THE
 COLLECTOR TANK (BASED UPON A HYPOTHETICAL 30-MINUTE
 TURNOVER OF THE CONTAINED VOLUME WITHIN THE SYSTEM).
 AUTOMATED OXIDATION REDUCTION POTENTIAL (ORP) AND PH
 CONTROLLERS WITH SENSING PROBES SHALL BE INSTALLED TO
 ASSIST IN MAINTAINING PROPER DISINFECTION AND PH
 LEVELS.
 7) SHT. CF5.0 - SOME PIPE SIZES ON THE SPLASH PAD
 EQUIPMENT SCHMATIC DO NOT CORRELATE WITH THE PIPE SIZES
 SHOWN ON THE HYDRAULIC ELEVATION DETAIL. REFER TO 8
 INCH MAIN DRAIN FROM TANK & 8 INCH MAIN DRAIN SUCTION.
 CLARIFY.
 8) THE FLOW RATE THROUGH THE FEATURE NOZZLES OF WATER
 FEATURES SHALL NOT EXCEED 20 FEET PER SECOND PER 2014
 FBC SEC.454.1.9.8.6.4. I COULD NOT FIND THIS
 INFORMATION/STATEMENT ON THE PLANS.
 9) SHOW CCOMPLIANCE WITH 2014 FBC SEC.454.1.9.8.6.8 -
 454.1.9.8.6.8
 WHERE THE FILTER SYSTEM DESCRIBED IN SECTION
 454.1.9.8.6.1 IS UTILIZED, A SECOND FILTER SYSTEM AND
 DISINFECTION SYSTEM SHALL BE PROVIDED TO TREAT THE
 WATER IN THE COLLECTOR TANK WHEN THE FEATURE/FILTER
 PUMP IS NOT IN OPERATION. SAID SYSTEM SHALL BE CAPABLE
 OF FILTERING THE TOTAL VOLUME OF WATER IN THE COLLECTOR
 TANK IN 30 MINUTES AND THE DISINFECTION SYSTEM SHALL BE
 CAPABLE OF PROVIDING 12 MG/L OF DISINFECTANT TO THIS
 FLOW RATE.
 454.1.9.8.6.1
 THE FILTER SYSTEM SHALL FILTER AND CHEMICALLY TREAT ALL
 WATER THAT IS RETURNED TO THE SPRAY FEATURES. THE
 FILTER SYSTEM SHALL DRAFT FROM THE COLLECTOR TANK AND
 RETURN FILTERED WATER DIRECTLY TO THE SPRAY FEATURES.
 EXCESS WATER NOT REQUIRED BY THE SPRAY FEATURES SHALL
 BE RETURNED TO THE COLLECTOR TANK.
 10) SHT. CF2.0 - SECTION A - SHOWS THE SLOPE TO DRAIN
 AS 20:1. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-02 Cont ID  
Sent By jwitmer Date 2017-03-02 Time 06:42 Rev Time 0.00
Received By jwitmer Date 2017-03-02 Time 06:30 Sent To  
Notes
2017-03-02 06:42:48SIGNATURES FOR ALL CF SHEETS VERIFIED. 3/02/2017. JW

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-27 Cont ID  
Sent By ajones Date 2017-03-27 Time 13:23 Rev Time 0.00
Received By ajones Date 2017-03-27 Time 13:23 Sent To  
Notes
***NONE***