| 2017-03-01 11:56:39 | 1) SHT. CF1.0 - THE PLANS SHOW THE FILTER TANK OVERFLOW |
| | DISCHARGING TO THE SANITARY SYSTEM. THE OVERFLOW WATER |
| | SHALL NOT DISCHARGE TO THE CITY OF WEST PALM BEACH |
| | SANITARY SYSTEM OR THE STORM SYSTEM PER CITY OF WPB |
| | CODE OF ORDINANCES ARTICLE III, SEC. 90-126 ( SANITARY) |
| | & ARTICLE 5, SEC. 90-203 (A) . |
| | SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF |
| | DISCHARGE. |
| | DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE INTO |
| | THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE PASS |
| | THROUGH OR INTERFERE WITH THE OPERATION OR PERFORMANCE |
| | OF THE WWF. NO USER SHALL DISCHARGE INTO THE WWF OR ANY |
| | CONNECTED SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY |
| | OF THE FOLLOWING: |
| | (B) (5) - STORMWATER, SURFACE WATER, GROUNDWATER, |
| | ARTESIAN WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, |
| | SWIMMING POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| | UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| | CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| | IN WRITING. |
| | SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT |
| | CONNECTIONS. |
| | (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION |
| | 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR |
| | INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY |
| | OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER |
| | SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT |
| | COMPOSED ENTIRELY OF STORMWATER. |
| | PLEASE CONTACT MANNY GONZALEZ IN CITY'S ENGINEERING |
| | DEPARTMENT FOR FURTHER DIRECTION ON THIS MATTER. HIS |
| | CONTACT INFO IS: [email protected], 561-494-1085. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| | DRAIN COVERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHT. CF5.0 - TANK PLAN VIEW SHOWS A 6 INCH MAIN |
| | DRAIN ON THE RIGHT SIDE OF THE TANK AND THE TANK |
| | ELEVATION VIEW BELOW IT SHOWS A 8 INCH MAIN DRAIN. THE |
| | EQUIPMENT SCHEMATIC ALSO SHOWS AN 8 INCH MAIN DRAIN |
| | FROM THE SPLASH PAD. CLARIFY. |
| | 4) SHT. CF5.0 - THE DECK SHOWER DETAIL DOES NOT |
| | CORRESPOND TO THE SHOWER UNIT SPECIFIED UNDER PERMIT |
| | #16120787. CLARIFY. THE SHOWER SHALL COMPLY WITH THE |
| | 2014 FBC -ACCESS |
| | 5) SHT. CF5.0 -THE TANK PLAN VIEW SHOWS A 2 INCH |
| | OVERFLOW TO A 6 INCH S.S. I DON'T KNOW IF THIS IS |
| | SUPPOSED TO BE A SANITARY SEWER OR STORM SEWER BUT |
| | SHT.CF1.0 SHOWS A 4 INCH SANITARY SEWER. IF APPROVAL IS |
| | RECEIVED FROM THE CITY TO DISCHARGE THE FILTER TANK |
| | OVERFLOW TO THE SANITARY SEWER THIS SIZE DISCREPANCY |
| | NEEDS TO BE CORRECTED. THE SPLASH PAD EQUIPMENT |
| | SCHEMATIC SHOWS THE 2 INCH OVERFLOW TO THE STORM WHICH |
| | IS NOT PERMITTED. CLARIFY. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) THE CHEMICAL FEEDERS SHALL COMPLY WITH 2014 FBC SEC. |
| | 454.1.9.8.3. |
| | CHEMICAL FEEDERS SHALL BE IN ACCORDANCE WITH SECTION |
| | 454.1.6.5; EXCEPT THAT THE DISINFECTION FEEDER SHALL BE |
| | CAPABLE OF FEEDING 12 PPM OF FREE CHLORINE TO THE |
| | PRESSURE SIDE OF THE RECIRCULATION SYSTEM OR THE |
| | COLLECTOR TANK (BASED UPON A HYPOTHETICAL 30-MINUTE |
| | TURNOVER OF THE CONTAINED VOLUME WITHIN THE SYSTEM). |
| | AUTOMATED OXIDATION REDUCTION POTENTIAL (ORP) AND PH |
| | CONTROLLERS WITH SENSING PROBES SHALL BE INSTALLED TO |
| | ASSIST IN MAINTAINING PROPER DISINFECTION AND PH |
| | LEVELS. |
| | 7) SHT. CF5.0 - SOME PIPE SIZES ON THE SPLASH PAD |
| | EQUIPMENT SCHMATIC DO NOT CORRELATE WITH THE PIPE SIZES |
| | SHOWN ON THE HYDRAULIC ELEVATION DETAIL. REFER TO 8 |
| | INCH MAIN DRAIN FROM TANK & 8 INCH MAIN DRAIN SUCTION. |
| | CLARIFY. |
| | 8) THE FLOW RATE THROUGH THE FEATURE NOZZLES OF WATER |
| | FEATURES SHALL NOT EXCEED 20 FEET PER SECOND PER 2014 |
| | FBC SEC.454.1.9.8.6.4. I COULD NOT FIND THIS |
| | INFORMATION/STATEMENT ON THE PLANS. |
| | 9) SHOW CCOMPLIANCE WITH 2014 FBC SEC.454.1.9.8.6.8 - |
| | 454.1.9.8.6.8 |
| | WHERE THE FILTER SYSTEM DESCRIBED IN SECTION |
| | 454.1.9.8.6.1 IS UTILIZED, A SECOND FILTER SYSTEM AND |
| | DISINFECTION SYSTEM SHALL BE PROVIDED TO TREAT THE |
| | WATER IN THE COLLECTOR TANK WHEN THE FEATURE/FILTER |
| | PUMP IS NOT IN OPERATION. SAID SYSTEM SHALL BE CAPABLE |
| | OF FILTERING THE TOTAL VOLUME OF WATER IN THE COLLECTOR |
| | TANK IN 30 MINUTES AND THE DISINFECTION SYSTEM SHALL BE |
| | CAPABLE OF PROVIDING 12 MG/L OF DISINFECTANT TO THIS |
| | FLOW RATE. |
| | 454.1.9.8.6.1 |
| | THE FILTER SYSTEM SHALL FILTER AND CHEMICALLY TREAT ALL |
| | WATER THAT IS RETURNED TO THE SPRAY FEATURES. THE |
| | FILTER SYSTEM SHALL DRAFT FROM THE COLLECTOR TANK AND |
| | RETURN FILTERED WATER DIRECTLY TO THE SPRAY FEATURES. |
| | EXCESS WATER NOT REQUIRED BY THE SPRAY FEATURES SHALL |
| | BE RETURNED TO THE COLLECTOR TANK. |
| | 10) SHT. CF2.0 - SECTION A - SHOWS THE SLOPE TO DRAIN |
| | AS 20:1. CLARIFY. |
| | |
| | TIM LARGE |