Plan Review Details - Permit 17010997
Plan Review Stops For Permit 17010997
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-06-06 Cont ID  
Sent By jgomez Date 2017-06-06 Time 10:39 Rev Time 0.00
Received By jgomez Date 2017-06-06 Time 09:18 Sent To  
Notes
2017-06-06 09:25:37BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR SINGLE HUNG
 WINDOWS THAT MEET THE DESIGN PRESSURES CALCULATED BY
 THE ENGINEER OF RECORD.
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 BEFORE SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-24 Cont ID  
Sent By jgomez Date 2017-05-24 Time 07:48 Rev Time 0.00
Received By jgomez Date 2017-05-23 Time 17:00 Sent To  
Notes
2017-05-23 17:36:18NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 NOTE:
 COMMENTS BELOW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO PROVIDE THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE: REVISION
 FEES MAY APPLY. CONTRACTOR TO ADVICE IN WRITING IF
 PROVISO OPTION IS PREFERRED AT THIS TIME.
  
 NEED THE COUNTY IMPACT FEES STAMP AND PAID RECEIPT IN
 ORDER TO PROCESS THE PERMIT.
  
  
 1- ORIGINAL COMMENT: REVISE ENERGY CALCULATIONS: REVISE
 # OF BEDROOMS TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 2- ORIGINAL COMMENT: TRUSS PACKAGE:
 A) NEW COVER SHEET SUBMITTED NEEDS THE INFORMATION OF
 THE ENGINEER OF RECORD AS REQUIRED BY F.A.C.
 61G15-31.003(5).
 B) TRUSS ENGINEER TO PROVIDE TITTLE BLOCK IN ALL SHEETS
 AS REQUIRED BY F.A.C. 61G15-31.003(5).
 NOTE: ONLY ONE COPY OF TRUSS PACKAGE WAS SUBMITTED.
 AFTER REQUIRED INFORMATION IS PROVIDED, CONTRACTOR MAY
 HANDLE ONE COPY OF THE TRUSS PACKAGE TO BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTIONS. PLEASE MAKE
 SURE PACKAGE IS REVIEWED BY THE ENGINEER OF RECORD.
 RESPONSE: REPEAT COMMENT. NOT RESPONSE. DON'T KNOW IF
 CONTRACTOR WILL PROVIDE REQUIRED INFORMATION NOW OR AT
 FRAMING INSPECTION.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3 FOR:
 A) ORIGINAL COMMENT: SINGLE HUNG WINDOWS. WINDOWS
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL17499-R1
 DON'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD.
 RESPONSE: REPEAT COMMENT. NEW DRAWINGS SUBMITTED STILL
 DON'T MEET THE CALCULATED DESIGN PRESSURES. NOTE:
 ENGINEER TO CLARIFY WHY HE APPROVED THE SINGLE HUNG
 WINDOWS PRODUCT APPROVAL IF THEY DON'T MEET THE
 CALCULATED DESIGN PRESSURES.
  
 4- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: ENGINEER TO CLARIFY WHY HE APPROVED
 THE SINGLE HUNG WINDOWS PRODUCT APPROVAL IF THEY DON'T
 MEET THE CALCULATED DESIGN PRESSURES.
  
 NOTE:
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-03 Cont ID  
Sent By jgomez Date 2017-05-03 Time 18:04 Rev Time 0.00
Received By jgomez Date 2017-05-02 Time 18:10 Sent To P
Notes
2017-05-02 19:00:48NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 NOTE:
 COMMENTS BELOW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO PROVIDE THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE: REVISION
 FEES MAY APPLY. CONTRACTOR TO ADVICE IN WRITING IF
 PROVISO OPTION IS PREFERRED AT THIS TIME.
 NEED THE COUNTY IMPACT FEES STAMP AND PAID RECEIPT IN
 ORDER TO PROCESS THE PERMIT.
  
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SURFACE DRAINAGE PLAN (2 COPIES) SHOWING
 COMPLIANCE WITH SEC. R401.3 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 3- TRUSS PACKAGE:
 A) NEW COVER SHEET SUBMITTED NEEDS THE INFORMATION OF
 THE ENGINEER OF RECORD AS REQUIRED BY F.A.C.
 61G15-31.003(5).
  
 B) TRUSS ENGINEER TO PROVIDE TITTLE BLOCK IN ALL SHEETS
 AS REQUIRED BY F.A.C. 61G15-31.003(5).
  
 NOTE: ONLY ONE COPY OF TRUSS PACKAGE WAS SUBMITTED.
 AFTER REQUIRED INFORMATION IS PROVIDED, CONTRACTOR MAY
 HANDLE ONE COPY OF THE TRUSS PACKAGE TO BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTIONS. PLEASE MAKE
 SURE PACKAGE IS REVIEWED BY THE ENGINEER OF RECORD.
  
 4- REVISE ENERGY CALCULATIONS.
 A) WHY IT WAS ROTATED 225 DEGREES. PROVIDE CALCULATIONS
 FOR THE ACTUAL ORIENTATION OF THE PROPOSED BUILDING.
 B) REVISE # OF BEDROOMS TO MATCH PLANS.
 C) REVISE THE WINDOWS ORIENTATION, SQUARE FOOTAGE AND
 OVERHANG DEPTH TO MATCH PLANS.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3 FOR:
 A) SINGLE HUNG WINDOWS. WINDOW DRAWING NO 08-02546
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL17499 IS FOR
 NON-IMPACT WINDOWS. THESE WINDOWS DON'T MEET THE DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD FOR
 WINDOWS LOCATED IN-THE END ZONE. IN ADDITION. WINDOW
 GLASS PROTECTION IS REQUIRED.
  
 B) HURRICANE MISSILE IMPACT PROTECTION FOR WINDOWS
 WITHOUT IMPACT GLASS. AND, PROVIDE COMPLETE SHUTTERS
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 C) ENTRY DOORS: DRAWINGS SUBMITTED WITH FLORIDA PRODUCT
 APPROVAL FL15213-R2 ARE TOO SMALL AND ARE NOT LEGIBLE.
 PROVIDE LARGER AND CLEAR DRAWINGS.
  
 D) REAR FIBERGLASS DOOR. DRAWINGS SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL15213-R2 ARE NOT FOR SINGLE
 DOORS AND ARE TOO SMALL AND ARE NOT LEGIBLE. PROVIDE
 CORRECT DRAWINGS AND LARGER AND CLEAR DRAWINGS.
  
 6- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By jgomez Date 2017-03-06 Time 13:59 Rev Time 0.00
Received By jgomez Date 2017-03-06 Time 07:23 Sent To  
Notes
2017-03-03 15:14:10NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE SURFACE DRAINAGE PLAN (2 COPIES) SHOWING
 COMPLIANCE WITH SEC. R401.3 FBC-RESIDENTIAL.
  
 4- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE ALL
 THE DESIGN INFORMATION SHOWN ON SHEET D1 AND ALL THE
 DESIGN PRESSURES SHOWN ON SHEET 1 OF 7.
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE DESIGN
 PRESSURES ARE REVISED. ENGINEER OF RECORD TO REVIEW AND
 APPROVE ALL PRODUCT APPROVALS AFTER THE DESIGN
 PRESSURES ARE REVISED.
  
 5- REVISE ALL ROOF LOADS SHOWN ON SHEET D1 TO INCLUDE
 THE ATTIC LIVE LOADS REQUIRED BY NOTES "B" AND "G" OF
 TABLE R301.5 FBC-RESIDENTIAL.
  
 6- SHEET D1: CLARIFY THE REQUIRED SOIL BEARING
 CAPACITY. NOTE #14 OF THE 2014 FBC RESIDENTIAL NOTES
 SPECIFY 2,000 PSF SOIL BEARING CAPACITY, WHILE NOTE # 5
 ON THE TOP RIGHT HAND SIDE OF THE SHEET AND TYPICAL
 WALL SECTION CALL FOR 2,500 PSF. REVISE AS REQUIRED TO
 MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- ROOF FRAMING PLAN (TRUSS LAYOUT):
 A) REVISE THE DESIGN CRITERIA. THE BUILDING EXPOSURE IS
 "D" NOT "C". SEC. R301.2.1.4 FBC-RESIDENTIAL. REVISE
 ALL THE DESIGN PRESSURES ACCORDINGLY.
  
 B) LETTERING ON THE STRAPPING & NAILING REQUIREMENT IS
 NOT LEGIBLE. IT'S TOO SMALL. REVISE AS REQUIRED. SEC.
 107.2.1.4 CITY AMENDMENTS.
  
 8- TRUSS PACKAGE SUBMITTED.
 A) REVISE THE DESIGN CRITERIA. THE BUILDING EXPOSURE IS
 "D" NOT "C". SEC. R301.2.1.4 FBC-RESIDENTIAL. REVISE
 THE DESIGN PRESSURES ACCORDINGLY.
  
 B) TRUSS ENGINEER TO SIGN AND SEAL ALL SHEETS AS
 REQUIRED BY CHAPTER 471 F.S. AND 61G15-23.002.
  
 C) TRUSS ENGINEER TO PROVIDE TITTLE BLOCK IN ALL SHEETS
 AS REQUIRED BY CHAPTER 471 F.S. AND 61G15-23.002.
  
 D) ENGINEER OF RECORD TO REVIEW AND APPROVE ALL TRUSS
 DRAWINGS PRIOR TO-SUBMITTAL. SEC. 107.3.4.2 CITY
 AMENDMENTS.
  
 9- SPECIFY SELF CLOSING DEVICE FOR THE GARAGE SWING
 DOOR LEADING TO THE HOUSE AS REQUIRED BY SEC. R302.5.1
 FBBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE ENTRY AREA AND COVERED PATIO
 SOFFITS SHOWING COMPLIANCE WITH SEC. R703.1.3
 FBC-RESIDENTIAL. SPECIFY ALL MATERIALS AND FASTENING.
  
 11- PROPERTY IS LOCATED IN FLOOD ZONE "B" NOT "C".
 REVISE INFORMATION ON SURVEY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 12- REVISE ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING PROJECT ADDRESS AND OWNER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 NOTE: LABELS WILL BE REQUIRED FOR THE WINDOWS AND DOORS
 SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE
 ENERGY CALCULATIONS.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF RIDGE VENT AS SPECIFIED ON PLANS.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE 2014 FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR. NOTE:
 FLORIDA PRODUCT APPROVAL NUMBERS LISTED ON THE ROOF
 FRAMING PLANS (TRUSS LAYOUT) ARE FOR THE 2010 CODE
 VERSION. NEED FLORIDA PRODUCT APPROVAL NUMBER FOR THE
 CURRENT 2014 CODE.
  
 D) ROOF SHINGLES. FLORIDA PRODUCT APPROVAL FL10124-R5
 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL FL10124-R19.
  
 E) GARAGE OVERHEAD DOOR. NOA 11-0414.12 SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL15371-R2 EXPIRED ON JULY 21,
 2015. NEED CURRENT NOA. NOTE: COORDINATE WITH THE
 REVISED DESIGN PRESSURES REQUIRED ON ITEM #4 ABOVE.
  
 F) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR WINDOW
 MULLIONS. THERE ARE NOT WINDOW MULLIONS SPECIFIED ON
 PLANS. IN ADDITION, FLORIDA PRODUCT APPROVAL FL15353-R2
 SUBMITTED HAS A "PENDING FBC APPROVAL" STATUS.
  
 G) FIXED WINDOWS. FLORIDA PRODUCT APPROVAL FL15349-R5
 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL FL15349-R8. NOTE: COORDINATE WITH THE
 REVISED DESIGN PRESSURES REQUIRED ON ITEM #4 ABOVE.
  
 H) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL17499 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT
 FLORIDA PRODUCT APPROVAL FL17499-R1. NOTE: COORDINATE
 WITH THE REVISED DESIGN PRESSURES REQUIRED ON ITEM #4
 ABOVE.
  
 14- ENGINEER OF RECORD TO REVIEW/APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-20 Cont ID  
Sent By vperez Date 2017-04-20 Time 10:39 Rev Time 0.00
Received By vperez Date 2017-04-20 Time 10:39 Sent To  
Notes
2017-04-20 10:39:47FPL LETTER ON RECORD AIC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By vperez Date 2017-02-15 Time 08:46 Rev Time 0.00
Received By vperez Date 2017-02-15 Time 08:46 Sent To  
Notes
2017-02-15 08:50:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN. FBC
 107.3.5
 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 3. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 4. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-06-06 Cont ID  
Sent By jgomez Date 2017-06-06 Time 10:41 Rev Time 0.00
Received By jgomez Date 2017-05-30 Time 14:42 Sent To  
Notes
2017-05-31 14:43:02RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-24 Cont ID  
Sent By jgomez Date 2017-05-24 Time 08:52 Rev Time 0.00
Received By jgomez Date 2017-05-18 Time 16:02 Sent To  
Notes
2017-05-19 16:02:20RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By gjohnson Date 2017-05-04 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2017-04-14 Time 11:17 Sent To  
Notes
2017-04-17 11:17:34R30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-07 Cont ID  
Sent By jgomez Date 2017-03-07 Time 10:23 Rev Time 0.00
Received By jgomez Date 2017-01-26 Time 11:33 Sent To  
Notes
2017-01-27 11:33:21R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-06-06 Cont ID  
Sent By jgomez Date 2017-06-06 Time 10:39 Rev Time 0.00
Received By jgomez Date 2017-06-06 Time 10:39 Sent To  
Notes
2017-06-06 10:41:37$10,003.08 PAID. MU-2017-14822.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-05-23 Cont ID  
Sent By jgomez Date 2017-05-23 Time 19:01 Rev Time 0.00
Received By jgomez Date 2017-05-23 Time 19:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-05-03 Cont ID  
Sent By jgomez Date 2017-05-03 Time 09:17 Rev Time 0.00
Received By jgomez Date 2017-05-03 Time 09:17 Sent To  
Notes
2017-05-03 09:17:241- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By jgomez Date 2017-03-03 Time 15:14 Rev Time 0.00
Received By jgomez Date 2017-03-03 Time 15:14 Sent To  
Notes
2017-03-03 15:14:341- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-24 Cont ID  
Sent By jgomez Date 2017-05-24 Time 08:52 Rev Time 0.00
Received By jgomez Date 2017-05-24 Time 07:59 Sent To  
Notes
2017-05-24 08:52:04 
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-03 Cont ID  
Sent By jgomez Date 2017-05-03 Time 18:01 Rev Time 0.00
Received By jgomez Date 2017-05-03 Time 17:34 Sent To P
Notes
2017-05-03 18:01:02NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
  
 NOTE:
 COMMENTS BELOW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO PROVIDE THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE: REVISION
 FEES APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED;
 CALCULATIONS ARE DONE FOR WORST CASE SCENARIO.
 CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION
 OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. CALCULATIONS SUBMITTED ARE
 DONE FOR THE WORST CASE SCENARIO AGAIN. CALCULATIONS
 NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE
 BUILDING. NOTE: SEE BUILDING REVIEW COMMENTS FOR
 COMMENTS REGARDING THE ENERGY CALCULATIONS ACTUAL
 ORIENTATION OF THE BUILDING.
  
 2- EQUIPMENT SHOWN ON-THE A/C PLAN SUBMITTED DOESN'T
 MATCH INFORMATION SHOWN ON THE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS. REVISE AS REQUIRED TO
 MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-07 Cont ID  
Sent By jgomez Date 2017-03-07 Time 10:23 Rev Time 0.00
Received By jgomez Date 2017-03-07 Time 10:22 Sent To  
Notes
2017-03-07 10:27:56NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED;
 CALCULATIONS ARE DONE FOR WORST CASE SCENARIO.
 CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION
 OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-04 Cont ID  
Sent By gjohnson Date 2017-05-04 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2017-05-04 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-02-15 Cont ID  
Sent By gjohnson Date 2017-02-15 Time 13:08 Rev Time 0.00
Received By gjohnson Date 2017-02-15 Time 09:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By jgomez Date 2017-05-03 Time 18:01 Rev Time 0.00
Received By jgomez Date 2017-05-03 Time 18:01 Sent To  
Notes
2017-05-03 18:04:211) RIDGE VENT FLORIDA PRODUCT APPROVAL FL10758-R6.
  
 2) SHINGLES FLORIDA PRODUCT APPROVAL FL10124-R19.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By jgomez Date 2017-03-06 Time 14:03 Rev Time 0.00
Received By jgomez Date 2017-03-06 Time 14:03 Sent To  
Notes
2017-03-06 14:04:24 
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF RIDGE VENT AS SPECIFIED ON PLANS.
  
 B) ROOF SHINGLES. FLORIDA PRODUCT APPROVAL FL10124-R5
 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL FL10124-R19.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-05-23 Cont ID  
Sent By awooten Date 2017-05-23 Time 09:09 Rev Time 0.00
Received By awooten Date 2017-05-23 Time 09:08 Sent To  
Notes
2017-05-22 14:32:18ROUTED TO ALANA WOOTEN

Review Stop Z ZONING
Rev No 2 Status F Date 2017-04-25 Cont ID  
Sent By awooten Date 2017-04-25 Time 14:51 Rev Time 0.00
Received By awooten Date 2017-04-25 Time   Sent To P
Notes
2017-04-25 14:50:31*********ZONING REVIEW************
  
 THE LANDSCAPE PLANS WERE INCLUDED IN WITH THIS PERMIT.
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 DRIVEWAYS REQUIRE A SEPARATE PERMIT.
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 PLANNING AND ZONING
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By awooten Date 2017-02-10 Time 14:11 Rev Time 0.00
Received By awooten Date 2017-02-10 Time 11:00 Sent To  
Notes
2017-02-13 11:09:49*****ZONING REVIEW FAILED********
  
 SETBACK ENCROACHMENTS:
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK.
  
 LANDSCAPING:
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 PLANNING AND ZONING
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  