Plan Review Details - Permit 17010986
Plan Review Stops For Permit 17010986
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By jwitmer Date 2017-11-02 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2017-11-02 Time 09:58 Sent To  
Notes
2017-11-02 10:00:24SEE RAILINGS UNDER PERMIT 15120896/ SUBMITTAL 16120807.
 11/02/2017. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By jwitmer Date 2017-02-02 Time 11:38 Rev Time  
Received By jwitmer Date 2017-02-02 Time 06:32 Sent To  
Notes
2017-02-02 11:38:07BUILDING PLAN REVIEW
 W. P. B. REVISION: 17010986 SCREEN ENCLOSURES
 W. P. B. PERMIT: 15120896
 ADD: 7140 OKEECHOBEE BLVD. BLDG. # 3/ BLDG. (MASTER)
 CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. FEB 02/2017
 ACTION: DENIED
  
 1) PLANS WERE BROUGHT IN AS A SUBMITTAL; THE SCREEN
 ENCLOSURE NEVER WAS SHOWN ON THE ORIGINAL PERMITTED SET
 OF DRAWINGS AND WILL REQUIRE A NEW PERMIT FOR EACH
 BUILDING. THERE WILL BE AN INCREASE IN VALUE DUE TO THE
 SCREEN ENCLOSURE BEING ADDED TO EACH UNIT THROUGHOUT
 THE WHOLE COMPLEX. THE SCREEN ENCLOSURE CAN BE MASTERED
 AS HAS BEEN THE CASE WITH THE PRODUCT APPROVALS AND
 VARIOUS SUBMITTALS.
  
 108.3* BUILDING PERMIT VALUATION. ALL OTHER PERMITS
 FIRE SPRINKLER, FIRE ALARM, EXHAUST HOODS, ANSUL
 SYSTEMS OR ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING
 SYSTEMS, WALK IN COOLERS & FREEZERS, ALL LOW VOLTAGE
 PERMITS, GENERATORS & FUEL TANKS, GAS PERMIT, POOL,
 JACUZZI AND ASSOCIATED SUB-PERMITS, AWNING, SCREEN
 ENCLOSURES, CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER
 CAST PILE AND OR FOUNDATION OR STRUCTURE ONLY PERMIT
 WILL BE SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH
 PERMIT.
  
 2) THE LAYOUT SHEET 2 OF 11 INDICATES DETAILS FOR
 FLOORS 2-4 OF SCREEN ENCLOSURE WITH THE REQUIRED GUARD
 RAIL SYSTEM. ON THE (1ST) FLOOR THE PLANS DO NOT SHOW A
 GUARDRAIL SYSTEM. A FORMER REVISION HAS REMOVED THE
 GUARDRAIL FORM ALL FIRST FLOOR UNITS.
 THE FIRST FLOOR PLAN SHOWS THE ELEVATION OF THE SCREEN
 ENCLOSURE AND NO GUARDRAIL, NO NOTATION BELOW THE 3
 FOOT 6 INCH HORIZONTAL RAIL THAT THERE IS ANY OTHER
 MATERIAL OTHER THAN SCREENING MATERIAL.
  
 BUILDINGS 3, 4, 5 & 6 ALL SURROUND THE COMMUNITY POOL
 AND WILL NEED TO SHOW COMPLIANCE WITH SECTION
 454.1.3.1.9 OF THE 2014 FBC-B SCREEN POOL ENCLOSURES
 MUST BE HARDENED ON THE BOTTOM 3 FEET OR BE SURROUNDED
 BY A MINIMUM 48 INCH HIGH FENCE OR OTHER SUBSTANTIAL
 BARRIER.
  
 3) FOR THE FIRST FLOOR FOR BUILDINGS 3, 4, 5 & 6 WILL
 REQUIRE A NEW ELEVATION SHOWING HOW THE VARIOUS 1ST
 FLOOR RESIDENTIAL UNITS MET THE REQUIREMENT OF FBC-B
 454.1.3.1.9 BY A 4 FOOT HIGH FENCE/ RAIL OR 3 FOOT HIGH
 HARDENED BOTTOM PANEL WITHIN THE SCREEN ENCLOSURE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-02 Cont ID  
Sent By   Date 2017-02-02 Time   Rev Time 0.00
Received By lmarchan Date 2017-01-26 Time 11:28 Sent To  
Notes
2017-01-27 11:28:43SUBMITTAL ROUTED TO JWITMER


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved