Plan Review Details - Permit 17010983
Plan Review Stops For Permit 17010983
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-27 Cont ID  
Sent By shill Date 2017-04-27 Time 10:48 Rev Time 0.00
Received By shill Date 2017-04-27 Time 10:48 Sent To  
Notes
2017-04-27 10:48:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010983
 ADD: 7130 OKEECHOBEE BLVD. / OPEN AIR PAVILION
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 3RD REVIEW
 DATE: THURS. APRIL 06/2017
 ACTION: BUILDING PROVISOS:
  
 1) THE SIGNED AND SEALED SITE GEOTECHNICAL SOILS REPORT
 IS IN THE DIGITAL FOLDER WITH THE PERMIT:
 16020377 RECREATION & LEASING CENTER PERMIT.
  
 2) A SEPARATE ROOFING PERMIT NEEDS TO BE APPLIED FOR.
 105.1 PERMITS.
  
 S.HILL (FOR JAMES A. WITMER BN, PX, CBO)
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2017-04-06 Time 13:01 Sent To  
Notes
2017-04-06 13:39:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010983
 ADD: 7130 OKEECHOBEE BLVD. / OPEN AIR PAVILION
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. APRIL 06/2017
 ACTION: BUILDING PROVISOS:
  
 1) THE SIGNED AND SEALED SITE GEOTECHNICAL SOILS REPORT
 IS IN THE DIGITAL FOLDER WITH THE PERMIT:
 16020377 RECREATION & LEASING CENTER PERMIT.
  
 2) A SEPARATE ROOFING PERMIT NEEDS TO BE APPLIED FOR.
 105.1 PERMITS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By jwitmer Date 2017-01-30 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2017-01-30 Time 10:51 Sent To  
Notes
2017-01-30 13:35:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010983
 ADD: 7130 OKEECHOBEE BLVD. / OPEN PAVILION
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. JAN. 2017
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS, SEE SHEET A1.12 UNDER THE
 HEADING STRUCTURAL NOTES WINDLOADS, EXPOSURE CONDITION,
 EXPOSURE B WHEREAS ON THE SAME SHEET UNDER THE HEADING
 OF DESIGN PARAMETERS AND ASSUMPTIONS THE EXPOSURE
 CONDITION IS LISTED AS C. PLEASE CORRECT THE
 DISCREPANCY IN EXPOSURES, THE CORRECT EXPOSURE IS A C
 EXPOSURE. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIED
 PLEASE UPDATE THE PLANS TO THE CORRECT EXPOSURE.
  
 2) DISCREPANCY IN PLAN SECTION SHEET A1.12 SEE DETAIL
 A. THE DETAIL INDICATES THE BEAM TO BE 12 INCHES WIDE
 AND 24 INCHES DEEP. THE CUT SECTION SHOWS THE ELEVATION
 TO THE TOP OF THE COLUMN TO BE 9 FOOT AND DIRECTLY
 ABOVE THIS DIMENSION THE PLAN INDICATES A VERTICAL 2
 FOOT DISTANCE FOR THE BEEM. TO THE LEFT OF THE COLUMN
 WORKING THE DIMENSIONS FROM THE TOP OF THE BEAM
 INDICATED AS 11 FEET THE PLANS SHOW A ELEVATION OF
 ELEVATION 10 FEET TOP OF COLUMN. IT WOULD APPEAR THIS
 MAYBE A TYPO SHOULD THE BOTTOM OF THE BEAM BE AT 9 FEET
 AND THE TOP OF THE COLUMN AT 9 FEET? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED, APPEARS TO BE A TYPO.
  
 3A) PLEASE CLARIFY THAT FOR BOTH THE GAS GRILLE AND
 SINKE LOCATED ON BOTH SIDES OF THE BUILDING THESE AREAS
 ARE NOT UNDER COVER OF THE ROOF AND WILL ALLOW THE
 PARTICLES OF COMBUSTION TO DISPERSE FREELY WITHOUT
 RESTRICTION OF ROOF COVER? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 3B) THE SITE PLAN A1.01 HAS A DIFFERENT CONFIGURATION
 THAN SHEET A1.12 AGAIN A DISCREPANCY IN PLANS, WHICH
 ONE IS CORRECT? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET A1.12 DOES NOT SHOW COMPLIANCE WITH: SECTION
 1209.2 ATTIC SPACE/ ATTIC ACCESS. 2014 FBC-B 1209.2
 ATTIC SPACES. AN OPENING NOT LESS THAN 20 INCHES BY 30
 INCHES (559 MM BY 762 MM) SHALL BE PROVIDED TO ANY
 ATTIC AREA HAVING A CLEAR HEIGHT OF OVER 30 INCHES (762
 MM). CLEAR HEADROOM OF NOT LESS THAN 30 INCHES (762 MM)
 SHALL BE PROVIDED IN THE ATTIC SPACE AT OR ABOVE THE
 ACCESS OPENING.
 / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) SHEET A1.13 THE PLANS INDICATE THE USE OF HIGH RIB
 METAL LATH FOR THE CEMENT PLASTER PAVILION CEILING.
 WHAT THE PLANS DO NO PROVIDE IS THE HEIGHT OF THE RIB
 LATH 3/8 INCH OR 3/4 INCH RIB LATH OR THE WEIGHT OF THE
 METAL PLASTER BASE, LB/YD(2). 2014 FBC-B 2511.1.1. AND
 ASTM C1063. PLEASE ALSO PROVIDE THE TYPE OF NAIL AND
 FREQUENCY OF NAILING AND LENGTH OF NAIL INTO THE
 FRAMING MEMBERS.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-05-01 Cont ID  
Sent By vperez Date 2017-05-01 Time 14:08 Rev Time 0.00
Received By vperez Date 2017-05-01 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 08:46 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-07 Cont ID  
Sent By vperez Date 2017-03-07 Time 12:00 Rev Time 0.00
Received By vperez Date 2017-03-07 Time 12:00 Sent To  
Notes
2017-03-07 12:02:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW ON DOCUMENTS SUBMITTED THE ELECTRICAL
 SCOPE OF WORK FOR THE PAVILLION. ADD SHEETS FROM MASTER
 IF THEY EXIST FOR THIS AREA. FBC 107.3.5
 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2017-04-14 Cont ID  
Sent By gjohnson Date 2017-04-14 Time 08:19 Rev Time 0.00
Received By gjohnson Date 2017-04-14 Time 08:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By scaldero Date 2017-03-27 Time 12:23 Rev Time 0.00
Received By scaldero Date 2017-03-27 Time 12:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By scaldero Date 2017-01-30 Time 11:04 Rev Time 0.00
Received By scaldero Date 2017-01-30 Time 10:56 Sent To  
Notes
2017-01-30 11:04:39PERMIT # 17010983
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET A1.01 INDICATES A LARGER AND DIFFERENT LAYOUT
 THAN THAT SHOWN ON SHEET A1.12.
 A) SHEET A1.01 APPEARS TO SHOW 2 BBQ GRILLS ON EACH
 SIDE FOR A TOTAL OF 4, WHEREAS SHEET A1.12 SHOWS 1 BBQ
 GRILL ON EACH SIDE FOR A TOTAL OF 2.
 B) THE FURNITURE LAYOUT AND OVERALL STRUCTURAL
 DIMENIONS AND DESIGN DO NO APPEAR TO MATCH ON BOTH
 SHEETS.
  
 1) THE BBQ GRILLS ARE LOCATED 3 FEET FROM THE
 STRUCTURE; 2 FEET FROM THE EDGE OF THE OVERHANG. THE
 BBQ UNITS SHALL BE RELOCATED ACCORDING TO THE CODE.
 PER NFPA 1, CHAPTER 10: 10.11.6 COOKING EQUIPMENT.
 10.11.6.1: FOR OTHER THAN ONE- AND TWO-FAMILY
 DWELLINGS, NO HIBACHI, GRILL, OR OTHER SIMILAR DEVICES
 USED FOR COOKING, HEATING, OR ANY OTHER PURPOSE SHALL
 BE USED OR KINDLED ON ANY BALCONY, UNDER ANY
 OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF ANY
 STRUCTURE.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2017-04-13 Cont ID  
Sent By gjohnson Date 2017-04-13 Time 13:01 Rev Time 0.00
Received By gjohnson Date 2017-04-13 Time 13:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By gjohnson Date 2017-02-22 Time 16:53 Rev Time 0.00
Received By gjohnson Date 2017-02-22 Time 16:53 Sent To  
Notes
2017-02-22 17:04:401ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. PLEASE PROVIDE MANUFACTURE SPECS FOR GRILL. PER WPB
 AMEND TO FBC 107.2.1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-03 Cont ID  
Sent By vperez Date 2017-05-03 Time 14:30 Rev Time  
Received By cpuell Date 2017-05-01 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-14 Cont ID  
Sent By gjohnson Date 2017-04-14 Time 08:19 Rev Time 0.00
Received By gjohnson Date 2017-03-21 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-21 Cont ID  
Sent By lmarchan Date 2017-03-21 Time 09:30 Rev Time 0.00
Received By lmarchan Date 2017-01-26 Time 16:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-04-13 Cont ID  
Sent By jwitmer Date 2017-04-13 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2017-04-13 Time 13:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By jwitmer Date 2017-01-30 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2017-01-30 Time 10:51 Sent To  
Notes
2017-01-30 13:36:25BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By ccole Date 2017-02-06 Time 09:33 Rev Time 0.00
Received By ccole Date 2017-02-06 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-04-27 Cont ID  
Sent By gjohnson Date 2017-04-27 Time 14:41 Rev Time 0.00
Received By gjohnson Date 2017-04-27 Time 14:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-13 Cont ID  
Sent By gjohnson Date 2017-04-13 Time 13:02 Rev Time 0.00
Received By gjohnson Date 2017-04-13 Time 13:01 Sent To  
Notes
2017-04-13 13:04:452ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENT HAS NOT BEEN
 COMPLIED WITH.
  
 2ND REQUEST 1. HOT OR TEMPERED WATER IS REQUIRED AT
 SINKS. PER FBC PL
 607.1 WHERE REQUIRED.
 IN RESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 TO PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE. IN NONRESIDENTIAL
 OCCUPANCIES,HOT WATER SHALL BE SUPPLIED FOR CULINARY
 PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE
 PURPOSES. IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR
 TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND
 WASHING PURPOSES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By gjohnson Date 2017-02-22 Time 16:58 Rev Time 0.00
Received By gjohnson Date 2017-02-22 Time 16:58 Sent To  
Notes
2017-02-22 17:02:121ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. HOT OR TEMPERED WATER IS REQUIRED AT SINKS. PER FBC
 PL
 607.1 WHERE REQUIRED.
 IN RESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 TO PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE. IN NONRESIDENTIAL
 OCCUPANCIES,HOT WATER SHALL BE SUPPLIED FOR CULINARY
 PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE
 PURPOSES. IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR
 TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND
 WASHING PURPOSES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-04-27 Cont ID  
Sent By shill Date 2017-04-27 Time 10:52 Rev Time 0.00
Received By shill Date 2017-04-27 Time 10:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2017-04-06 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By llouie Date 2017-05-03 Time   Rev Time 0.00
Received By llouie Date 2017-05-03 Time   Sent To  
Notes
2017-05-03 12:30:00MINOR CHANGES DETECTED IN THE BUILDING PERMIT SITE PLAN
 (SHEET A1.01) THAT DOES NOT MATCH THE LATEST APPROVED
 SITE PLAN BY THE PLANNING DIVISION. AS A CONDITION OF
 APPROVAL, AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY, THE DEVELOPER WILL BE REQUIRED TO SUBMIT AN
 APPLICATION FOR A MINOR DSI AMENDMENT FOR THE AS BUILT.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-10 Cont ID  
Sent By llouie Date 2017-02-10 Time   Rev Time  
Received By llouie Date 2017-02-10 Time   Sent To  
Notes
2017-02-10 09:19:56 
 MINOR CHANGES DETECTED IN THE BUILDING PERMIT SITE PLAN
 (SHEET A1.01) THAT DOES NOT MATCH THE LATEST APPROVED
 SITE PLAN BY THE PLANNING DIVISION. AS A CONDITION OF
 APPROVAL, AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY, THE DEVELOPER WILL BE REQUIRED TO SUBMIT AN
 APPLICATION FOR A MINOR DSI AMENDMENT FOR THE AS BUILT.
  
 CHANGES DETECTED:
 - CHANGE IN THE CONFIGURATION OF THE SWIMMING POOL
 - CHANGE IN THE CONFIGURATION OF THE POOL PAVILION
 - CHANGE IN THE CONFIGURATION OF THE POOL DECK
 - CHANGE IN THE CONFIGURATION OF THE PERIMETER FENCE
  