Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-31 Cont ID  
Sent By jwitmer Date 2017-01-31 Time 06:29 Rev Time  
Received By jwitmer Date 2017-01-30 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-02 Cont ID  
Sent By jleahy Date 2017-03-02 Time 13:59 Rev Time 0.00
Received By jleahy Date 2017-03-02 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-10 Cont ID  
Sent By vperez Date 2017-02-10 Time 14:28 Rev Time 0.00
Received By vperez Date 2017-02-10 Time 14:28 Sent To  
Notes
2017-02-10 14:30:03PLEASE ADDRESS MECHANICAL COMMENT REGARDING AHU #4 AND
 REFLECT CHANGES TO PANEL SCHEDULE C ON SHEET E3.1 FBC
 107.3.5
  
 V. PEREZ
 *6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-08 Cont ID  
Sent By pleduc Date 2017-02-08 Time   Rev Time 0.00
Received By pleduc Date 2017-02-07 Time 17:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-02 Cont ID  
Sent By jleahy Date 2017-03-02 Time 15:02 Rev Time 0.00
Received By jleahy Date 2017-03-02 Time 15:02 Sent To  
Notes
2017-03-01 14:05:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-10 Cont ID  
Sent By vperez Date 2017-02-10 Time 14:30 Rev Time 0.00
Received By vperez Date 2017-02-10 Time 14:30 Sent To  
Notes
2017-01-26 10:17:39B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-31 Cont ID  
Sent By jwitmer Date 2017-01-31 Time 06:23 Rev Time 0.00
Received By jwitmer Date 2017-01-31 Time 06:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-02 Cont ID  
Sent By ccole Date 2017-03-02 Time 08:21 Rev Time 0.00
Received By ccole Date 2017-03-02 Time 07:46 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By ccole Date 2017-02-02 Time 07:16 Rev Time 0.00
Received By ccole Date 2017-02-02 Time 06:53 Sent To  
Notes
2017-02-02 07:25:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010886
 2/2/17
  
 1) THE AC EQUIPMENT SCHEDULE INDICATES NO HEATING DATA
 FOR AHU-4, HOWEVER HEAT IS REQUIRED FOR THE CLUBHOUSE
 PER SECTION 309.1 PLEASE NOTE THE SUBMITTED AC
 CALCULATIONS INDICATE 10.1 MBH CENTRAL HEATING COIL
 SIZING DATA.
  
 CHRISTOPHER L. COLE