Plan Review Details - Permit 17010884
Plan Review Stops For Permit 17010884
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-07 Cont ID  
Sent By shill Date 2017-04-07 Time 07:20 Rev Time 0.00
Received By shill Date 2017-04-07 Time 06:27 Sent To  
Notes
2017-04-07 07:20:52****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FIRE SPRINKLERS REQUIRED FOR C.O.
  
 MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B
 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE
 PUBLIC WAY.
  
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED. PER ARCHITECT, ALL OUTDOOR EQUIPMENT IS
 LOCATED ON THE ROOFTOP. ELEVATION CERTIFICATE IS TO
 INCLUDE ROOFTOP EQUIPMENT. IF ANY EQUIPMENT IS AT
 GRADE, A REVISION SHOWING ELEVATION IS REQUIRED
 (INCLUDING OTHER TENANTS).
  
 ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES,
 TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-17 Cont ID  
Sent By shill Date 2017-03-17 Time 15:24 Rev Time 0.00
Received By shill Date 2017-03-24 Time 06:20 Sent To  
Notes
2017-03-17 15:24:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS
 FOR THE MILL, FBC 107.
  
 2ND REVIEW, A DRAWING WAS PROVIDED. PROVIDE SPEC SHEETS
 AND INSTALLATION INSTRUCTIONS SO THAT ANY MANUFACTURER
 REQUIREMENTS CAN BE VERIFIED. THIS MAY BE SENT VIA
 EMAIL FOR REVIEW. SEE NEW COMMENT REGARDING TWO SETS
 REQUIRED. WHEN ADDRESSING THAT COMMENT, PROVIDE TWO
 PAPER SETS FOR ISSUANCE.
  
 9. SEE IMPACT FEE REVIEW.
  
 NEW COMMENTS:
  
 10. FBC 107, TWO COMPLETE COLLATED SETS ARE REQUIRED
 FOR PERMIT ISSUANCE. TWO PLAN SETS WERE PROVIDED BUT
 ONLY ONE SET OF SUPPORTING DOCUMENTS WAS PROVIDED. THE
 SET WAS STAPLED ON THE SIDE OF ONE PLAN. IT IS NOT
 NECESSARY TO STAPLE IT IN THIS MANNER (WE PREFER TWO
 IDENTICAL CLIPPED SETS OF SUPPORTING DOCUMENTS, TABBED
 ONLY IF DOCUMENTS ARE EXTREMELY EXTENSIVE). DUE TO WORK
 LOAD, THERE ARE NOT ANY STAFF PEOPLE AVAILABLE TO
 PERFORM COPY DUTIES. PROVIDE A SECOND IDENTICAL SET.
  
 11. IS A8.0 A NEW SHEET? I WAS UNABLE TO LOCATE THE OLD
 SHEET. SEE FBC A 604.4, SEAT HEIGHT TO BE MEASURED AT
 TOP OF SEAT, DETAIL SHOWS MEASUREMENT TO TOP OF LID. IF
 THIS SHEET IS REVISED FOR ANOTHER TRADE, REVISE ALL
 AFFECTED DETAILS. IF IT IS NOT REVISED FOR ANOTHER
 TRADE, PLEASE ADVISE AND THIS WILL BE REDLINED. PLEASE
 HAVE THIS CORRECTED ON ALL FUTURE SUBMITTALS.
  
 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISO:
  
 FIRE SPRINKLERS REQUIRED FOR C.O.
  
 MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B
 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE
 PUBLIC WAY.
  
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED. PER ARCHITECT, ALL OUTDOOR EQUIPMENT IS
 LOCATED ON THE ROOFTOP. ELEVATION CERTIFICATE IS TO
 INCLUDE ROOFTOP EQUIPMENT. IF ANY EQUIPMENT IS AT
 GRADE, A REVISION SHOWING ELEVATION IS REQUIRED
 (INCLUDING OTHER TENANTS).
  
 ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES,
 TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 10:53 Rev Time 0.00
Received By shill Date 2017-02-15 Time 10:39 Sent To  
Notes
2017-02-16 10:53:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY, FBC EB
 CHAPTER 10. REVISE PLAN TO SHOW COMPLIANCE. NO
 INFORMATION REGARDING BUILDING AREA FBC TABLE 503 WAS
 PROVIDED.
  
 REVISE PLAN TO INCLUDE INFORMATION REGARDING THE OTHER
 TENANT SPACES, INCLUDING SF AREA AND OCCUPANCY
 CLASSIFICATION, AND BUILDING TYPE FBC CHAPTER 6.
  
 REVISE PLAN TO INCLUDE PREVIOUS OCCUPANCY, FBC EB 1012,
 TABLES 1012.4, 1012.5, 1012.6.
  
 REVISE PLAN TO SHOW COMPLIANCE WITH ALL CHANGE OF
 OCCUPANCY REQUIREMENTS FBC EB 1012.
  
 NO SITE PLAN PROVIDED; THIS WILL LIKELY BE REQUIRED FBC
 EB TABLE 1012.6.
  
 2. THIS APPEARS TO BE A NON SPRINKLERED BUILDING.
 SPRINKLERS ARE PROPOSED. SEE FIRE COMMENTS; THIS IS
 ALSO APPLICABLE FOR BUILDING. IF THE BUILDING IS
 CURRENTLY FULLY SPRINKLERED, REVISE PLAN TO STATE. IF A
 NEW SPRINKLER SYSTEM IS PROPOSED, PROVIDE SPRINKLER
 INFORMATION.
  
 IF A NEW SPRINKLER SYSTEM IS PROPOSED, AN ENGINEERING
 PERMIT IS REQUIRED. CONTACT ENGINEERING DEPARTMENT AND
 SUBMIT ANY REQUIRED APPLICATIONS.
  
 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS
 FOR THE MILL, FBC 107.
  
 4. DETAIL 13-A9.0, THE FOOT REST APPEARS TO OBSTRUCT
 THE REQUIRED TOE CLEARANCE, FBC A 306.2. REVISE PLAN TO
 SHOW COMPLIANCE.
  
 5. REVISE PLAN TO INCLUDE FINISHED FLOOR ELEVATION, FBC
 B 1612. THIS IS CONSIDERED A SUBSTANTIAL IMPROVEMENT.
  
 6. PROVIDE A SITE PLAN OR SURVEY WHICH INCLUDES ALL
 EQUIPMENT AT GRADE. IF ALL EQUIPMENT SERVICING THE
 BUILDING IS LOCATED ON THE ROOF, REVISE PLAN TO NOTE,
 FBC B 1612.
  
 7. SHEET A7.0 INCLUDES A NOTE REGARDING PANIC HARDWARE.
 SEE FBC B 1008.1.10; WILL BOTH EXIT DOORS INCLUDE PANIC
 BARS? REVISE PLAN TO CLARIFY.
  
 8. PLAN SPECIFIES TRULITE STOREFRONT SYSTEM AND DOORS,
 OVERHEAD DOORS. PROVIDE PRODUCT APPROVALS, FBC 107. ANY
 PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES,
 TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION.
  
 9. SEE IMPACT FEE REVIEW.
  
 THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISO:
  
 MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B
 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE
 PUBLIC WAY.
  
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED. THIS SHOULD INCLUDE ALL EQUIPMENT SERVICING
 THE BUILDING.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-04-11 Cont ID  
Sent By rlecky Date 2017-04-11 Time 11:36 Rev Time 0.00
Received By rlecky Date 2017-04-11 Time 10:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-09 Cont ID  
Sent By rlecky Date 2017-03-09 Time 10:20 Rev Time 0.00
Received By rlecky Date 2017-03-07 Time 10:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By rlecky Date 2017-02-02 Time 14:25 Rev Time 0.00
Received By rlecky Date 2017-02-02 Time 12:09 Sent To  
Notes
2017-02-02 14:28:06PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE. NEC 110.9, 110.10
  
 PROVIDE THE SERVICE WIRE AND SERVICE MAST SIZE. NEC
 230.23
  
 INDICATE THE MINIMUM HEIGHT REQUIRED FOR THE OVERHEAD
 SERVICE ABOVE THE ALLEWAY TO THE BOTTOM OF THE SERVICE
 DRIP LOOP. NEC 230.24, 230.26
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE MAIN DISCONNECTING MEANS. NEC 110.16,
 110.22, 110.24
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40
  
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE ELECTRICAL
 SERVICE. NEC 250.94
  
 PROVIDE THE LOCATION OF THE LIGHTING CONTROL PANEL AND
 SWITCH BANK. NEC 110.3
  
 PROVIDE A BOLLARD OR EQUALIVENT PROTECTION DETAIL FOR
 THE ELECTRICAL SERVICE LOCATED IN THE DELIVERY ALLEWAY.
 NEC 110.2, 110.3, 110.11
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-03-22 Cont ID  
Sent By mgonzale Date 2017-03-22 Time   Rev Time 1.00
Received By mgonzale Date 2017-03-22 Time   Sent To I
Notes
2017-03-22 16:55:35PROVISO: ENGINEERING PERMIT IS REQUIRED.
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLEASE CONTACT:
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 536-3981
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By mgonzale Date 2017-02-21 Time   Rev Time 0.00
Received By mgonzale Date 2017-02-21 Time   Sent To I
Notes
2017-02-21 16:37:38ALL NEW FIRELINE CONNECTIONS TO EXISTING WATERMAINS
 WILL REQUIRE A SEPARATE SUBMITTAL TO THE CITY OF WPB
 ENGINEERING DEPT VIA DEVELOPMENT PERMIT.
 PLEASE SUBMIT TWO SETS OF CIVIL PLANS WITH THE
 DEVELOPMENT APPLICATION AS CERTIFIED COST ESTIMATE FOR
 REVIEW.
 HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-07 Cont ID  
Sent By pleduc Date 2017-03-07 Time   Rev Time 0.00
Received By pleduc Date 2017-03-07 Time 14:52 Sent To  
Notes
2017-03-07 15:37:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) EOR 61G DOCUMENTS ARE REQUIRED TO BE WITH THIS
 PERMIT AND WILL ALLOOWED TO BE SUBMITTED AS A REVISION
 TO THIS PERMIT, BUT PRIOR TO THE SHOP DRAWINGS
 SUBMITTAL.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PLEASE DO NOT MISUNDERSTAND AND ENSURE COMPLIANCE WITH
 THE ABOVE.
  
  
  
 2) A MONITORED FIRE ALARM SYSTEM IS REQUIRED TO MONITOR
 THE FIRE SPRINKLER SYSTEM PER NFPA 101, 5TH EDITION.
  
 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A
 MULTIPLE OCCUPANCY PROTECTED AS A MIXED OCCUPANCY (SEE
 6.1.14) SHALL BE PERMITTED TO BE SERVED BY A COMMON
 FIRE ALARM SYSTEM, PROVIDED THAT THE INDIVIDUAL
 REQUIREMENTS OF EACH OCCUPANCY ARE MET.
  
  
 PLEASE PROVIDE A FIRE ALARM FOR MONIORTING THE FIRE
 SPRINKLER SYSTEM.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-08 Cont ID  
Sent By pleduc Date 2017-02-08 Time   Rev Time 0.00
Received By pleduc Date 2017-02-02 Time 15:57 Sent To  
Notes
2017-02-07 13:57:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS1.0 - THERE A SEVERAL OCCUPANCY TYPES
 INDICATED; HOWEVER, IS THIS A MIXED OCCUPANCY OR
 SEPARATED OCCUPANCY AND WHAT OCCUPANCY TYPE IS THE
 PROPOSED PROJECT DESIGNED UNDER.
  
 PER THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, NFPA 101
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE
 RESISTANCE?RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
  
 PLEASE PROVIDE THE SPECIFICS FOR COMPLIANCE WITH THE
 ABOVE NOTED AND RELATED CODES.
  
  
  
 2) SHEET ALS 1.0 - A BOLIER IS INDICATED IN ROOM 110.
  
 PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS FOR THE
 BOLIER INCLUDING EXPLOSION HAZARD INFORMATION. PROVIDE
 ANY RELATED CONSTRUCTION RELATED REVISONS FOR EXPLOSION
 PROTECTION IF APPLICABLE.
  
  
 3) SHEET ALS 1.0 - A MILL IS INDICATED IN ROOM 112.
  
 PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS FOR THE
 MILL INCLUDING EXPLOSION HAZARD INFORMATION. PROVIDE
 ANY RELATED CONSTRUCTION RELATED REVISONS FOR EXPLOSION
 PROTECTION IF APPLICABLE.
  
 PLEASE PROVIDE A NOTE AND/OR REVSIONS RELATED TO MILL
 ROOM REGARDING ALL WIRING, LIGHTS, SWITCHES,
 HOUSEKEEPING, ETC, ARE ALL EXPLOSION PROOF, IF
 APPLICABLE.
  
  
  
 4) SHEET A 1.0 - THE INDICATED OCCUPANCY LOAD; 221, AND
 EXIT CAPACITY; 117, CALCULATIONS DO NOT MATCH.
 ADDITIONALLY, THERE IS AN INDICATION OF THE EXIT
 CAPACITY CALCULATION OF .2 LEVEL TRAVEL; HOWEVER, THE
 TWO EXITS ARE INDICATED WITH STAIRS.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS, STAIRS SHALL
 BE CALCULATED WITH .3. THE EXIT CAPACITY APPEARS TO BE
 SUFFICIENT; HOWEVER, THE CALULATIONS NEED CORRECTION.
  
 PLEASE PROVIDE CORRECTIONS.
  
  
  
 5) SHEET ALS 1.0 - A DOUBLE DOOR EXIT IS INDICATING
 LEADING INTO THE PATIO. THERE ARE TABLES AND CHAIRS
 INDICATED IN THE PATIO. THE DOOR SWINGS INTO THE PATIO
 AND INTO AND RESTRICTING THE EXIT PATHWAY.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE PROVIDE FOR THE REQUIRED WIDTH.
  
  
 6) SHEET E2.1 & A1.1 - THERE IS ONLY ONE EXIT LIGHTS
 INDICATED ON THE ON E2.1 AT THE FRONT DOOR. THERE ARE
 NO OTHER EXITS LIGHTS AS INDICATED ON A1.1 IN THE PATH
 OF TRAVEL.
  
 PLEASE ADD ALL APPLICABLE EXIT LIGHTS PER ALL EXIT PATH
 AND EXIT DISCHARGE LOCATION. PLEASE ENSURE TO ADD NA
 EXIT LIGHT INSIDE THE LOADING AREA AT THE STAIRS
 LEADING TO OTHER EXIT ACCESS.
  
  
  
 7) SHEET E2.1- THERE SOME EMERGENCY LIGHTING INDICATED;
 HOWEVER, IT MAY NOT PROVIDE SUFFICIENT LIGHTING ALONG
 THE EXXIT PATH OF TRAVEL.
  
 PLEASE ESURE THAT ALL EXITS AND EXIT PATHS HAVE THE
 REQUIRED EMERGENCY LIGHT LUMINATION PER THE OCCUPANCY
 CLASSIFICATION CODE REQUIREMENTS AS REQUIRED BY # 1
 ABOVE.
  
  
  
 8) NO SHEET - A NOTE INDICATING THAT A FIRE SPRINKLER
 SHOP DRAWING WILL BE PROVIDED; HOWEVER, IT APPEARS IT
 WILL BE A NEW SYSTEM.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 THIS INFORMATION MAY BE PROVIDED WITH AN OFFICIAL
 SIGNED AND SEALED DRAWING OR LETTER NARRATIVE FORM A
 QUALIFIED DESIGN PROFESSIONAL.
  
 PLEASE PROVIDE DOCUMENTATION PER THE REQUIRMENTS.
  
  
 9) THERE IS NO INDICATION OF ANY FIRE ALARM SYSTEM.
  
 PROVIDE AN APPLICABLE REFERENCE OF A FIRE ALARM SYSTEM
 PER THE APPLICABLE OCCUPANCY CLASSIFICATION OF # 1
 ABOVE AND/OR FOR THE MONITORING OF THE FIRE SPRINKLER
 SYSTEM.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-04-10 Cont ID  
Sent By tklarge Date 2017-04-10 Time 13:52 Rev Time 0.00
Received By tklarge Date 2017-04-10 Time 13:44 Sent To  
Notes
2017-04-20 06:07:14THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED
 SUBMITTALS. COMPLETE PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED FOR REVIEW FOR THE FOLLOWING ITEMS PRIOR TO
 THE INSTALLATION OF NOTED SYSTEMS:
 1) BOILER AND ASSOCIATED PIPING AND VENT - SUBMIT AN
 EQUIPMENT SCHEDULE FOR THE BOILER, BOILER VENT PIPE(S),
 AND MANUFACTURER'S SPECIFICATIONS FOR EACH. PROVIDE A
 DIMENSIONAL ELEVATION VIEW THAT SHOWS THE TOTAL VENT
 RUN FROM THE OUTLET OF THE BOILER TO THE TERMINATION
 CAP ABOVE THE ROOF. SHOW HOW THE VENT WILL BE SUPPORTED
 AND ANCHORED TO THE ROOF STRUCTURE.
 2) STEAM PIPING - PROVIDE STEAM PIPING DRAWINGS THAT
 SHOW THE PIPING RUNS, TYPES AND SIZES OF PIPES & PIPE
 INSULATION.
 3) EQUIPMENT SCHEDULE AND PIPING PLAN FOR THE TANKS AND
 KETTLES USED IN THE BREWING PROCESS.
 4)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2014 FBC-FUEL GAS SECS.
 502 THRU 505.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-03-27 Cont ID  
Sent By tklarge Date 2017-03-27 Time 10:35 Rev Time 0.00
Received By tklarge Date 2017-03-27 Time 09:31 Sent To  
Notes
2017-03-27 09:42:46GAS REVIEW
  
 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE
 NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC
 TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS
 SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ.
 INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE
 CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG
 SIZE BOILER.
 2) THERE IS A DISCREPANCY ON THE BTU LOAD OF THE BOILER
 ON THE MANUFACTURER'S SPECIFICATIONS AND MECHANICAL
 DRAWINGS M2.1 & M6.1 AND THE GAS RISER ON P5.1.
 CLARIFY.
 3) SHT. P5.1 - THE GAS RISER SHOWS THE BOILER AS
 850,000 BTUS AND THE MANUFACTURER'S SPECIFICATIONS
 SHOWS THE BTU LOAD AS 2,100,000 BTU'S. IF THE BOILER IS
 2,100,000 BTU'S THE MINIMUM PIPE SIZE TO THE BOILER
 SHALL BE 2 1/2 INCHES AND THE SIZE OF THE LINE FROM THE
 METER SHALL BE INCREASED TO 3 INCHES. 2014 FBC-FUEL GAS
 TABLE 402.4 (2).
 4) THE GAS LINE TO THE GAS WATER HEATER IS UNDERSIZED.
 THE MINIMUM SIZE SHALL BE 1 1/4 INCHES. 2014 FBC-FUEL
 GAS TABLE 402.4 (2).
 5) THE AJAX BOILER DRAWING # G62200 APPEARS TO SHOW
 VENTS FOR THE SAFETY VALVES COMBINED WITH THE VENTS FOR
 THE GAS REGULATOR. THE VENT FOR THE GAS REGULATOR SHALL
 BE RUN INDEPENDENTLY TO THE OUTDOORS AND SHALL SERVE
 ONLYY A SINGLE DEVICE VENT. 2014 FBC-FUEL GAS SEC.
 410.3.1.
 6) SHT. M2.1 - ROOM #110 - SHOWS A 12 INCH ROUND DUCT
 UP THROUGH THE ROOF BUT IT IS NOT IDENTIFIED AS TO ITS
 PURPOSE. CLARIFY.
  
 THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED
 SUBMITTALS. COMPLETE PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED FOR REVIEW FOR THE FOLLOWING ITEMS PRIOR TO
 THE INSTALLATION OF NOTED SYSTEMS:
 1) BOILER AND ASSOCIATED PIPING AND VENT - SUBMIT AN
 EQUIPMENT SCHEDULE FOR THE BOILER, BOILER VENT PIPE(S),
 AND MANUFACTURER'S SPECIFICATIONS FOR EACH. PROVIDE A
 DIMENSIONAL ELEVATION VIEW THAT SHOWS THE TOTAL VENT
 RUN FROM THE OUTLET OF THE BOILER TO THE TERMINATION
 CAP ABOVE THE ROOF. SHOW HOW THE VENT WILL BE SUPPORTED
 AND ANCHORED TO THE ROOF STRUCTURE.
 2) STEAM PIPING - PROVIDE STEAM PIPING DRAWINGS THAT
 SHOW THE PIPING RUNS, TYPES AND SIZES OF PIPES & PIPE
 INSULATION.
 3) EQUIPMENT SCHEDULE AND PIPING PLAN FOR THE TANKS AND
 KETTLES USED IN THE BREWING PROCESS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By gjohnson Date 2017-02-21 Time 15:41 Rev Time 0.00
Received By gjohnson Date 2017-02-21 Time 15:41 Sent To  
Notes
2017-02-21 15:43:171ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-05-25 Cont ID  
Sent By shill Date 2017-05-25 Time 12:35 Rev Time 0.00
Received By shill Date 2017-05-23 Time 12:05 Sent To  
Notes
2017-05-24 12:05:36IMPACT ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-04-20 Cont ID  
Sent By tklarge Date 2017-04-20 Time 07:03 Rev Time 0.00
Received By tklarge Date 2017-04-14 Time 13:12 Sent To  
Notes
2017-04-17 13:12:27RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-11 Cont ID  
Sent By rlecky Date 2017-04-11 Time 11:36 Rev Time 0.00
Received By rlecky Date 2017-04-03 Time 15:08 Sent To  
Notes
2017-04-04 15:08:21C22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-27 Cont ID  
Sent By tklarge Date 2017-03-27 Time 10:35 Rev Time 0.00
Received By tklarge Date 2017-03-06 Time 10:44 Sent To  
Notes
2017-03-07 10:50:23C22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-21 Cont ID  
Sent By gjohnson Date 2017-02-21 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2017-01-24 Time 16:23 Sent To  
Notes
2017-01-25 16:23:37C22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-05-25 Cont ID  
Sent By shill Date 2017-05-25 Time 12:34 Rev Time 0.00
Received By shill Date 2017-05-25 Time 11:51 Sent To  
Notes
2017-05-25 12:35:20MU 2017-10909
 MU 2017-10901
 $31,313.58 RDS
 $853.23 PUB BLD
 **ESCROW** SEE EMAIL FROM WILLIE SWOPE DATED 5/25/17
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 10:54 Rev Time 0.00
Received By shill Date 2017-02-16 Time 10:54 Sent To  
Notes
2017-02-16 10:55:08IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES HAVE BEEN PAID ARE REQUIRED TO BE SUBMITTED
 PRIOR TO PERMIT ISSUANCE.
  
 561-233-5025 FOR MORE INFORMATION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-04-10 Cont ID  
Sent By ccole Date 2017-04-10 Time 15:51 Rev Time 0.00
Received By ccole Date 2017-04-10 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-13 Cont ID  
Sent By ccole Date 2017-03-13 Time 14:12 Rev Time 0.00
Received By ccole Date 2017-03-13 Time 13:10 Sent To  
Notes
2017-03-13 14:29:072ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010884
 3/13/17
  
 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE
 NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC
 TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS
 SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ.
 INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE
 CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG
 SIZE BOILER.
  
 2) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR
 SYSTEMS OF THE NEW RTU'S- SECTION 606.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 12:20 Rev Time 0.00
Received By ccole Date 2017-02-01 Time 11:36 Sent To  
Notes
2017-02-01 12:51:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010884
 2/1/2017
  
 1 ) M2.1 & M6.1: THE O/A CALCULATION SCHEDULE IS
 INCORRECT. RTU-1 IS CONDITIONING THE BAR AREA, NOT
 RTU-3.
  
 2 ) M6.1: REFER TO TABLE 403.3 AND REVISE THE
 CALCULATION FOR THE BAR AREA TO 100 PERSONS PER 1000
 SF/ 7.5 CFRMS PERSON/ AND 0.18 CFMS PER SF. THE
 CALCULATION SHOULD ADJUST TO 2186 CFMS OF O/A REQUIRED.
 PLEASE NOTE THE INCREASED LOAD MAY REQUIRE INCREASED
 COOLING AND HEATING CAPACITIES FOR RTU-1.
  
 3) THE AC HEATING CALCULATIONS SHOW THE HEAT CAPACITIES
 OF RTU-1 & 2 ARE UNDERSIZED.
  
 4) THE AC CALCULATIONS DO NOT SHOW ANY APPLIANCE OR
 EQUIPMENT LOADS. PLEASE CLARIFY IF THE ADDED HEAT AND
 HUMNIDITY LOAD FROM THE STEAM TANKS AND KETTLES HAVE
 BEEN CALCULATED INTO THE TOTAL LOAD.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE BOILER, BOILER
 VENT PIPE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 EACH. PROVIDE A DIMENSIONED ELEVATION VIEW THAT
 INDICATES THE TOTAL VENT RUN FROM THE OUTLET OF THE
 BOILER TO THE TERMINATION CAP ABOVE THE ROOF. INDICATE
 HOW THE VENT WILL BE SUPPORTED AND ANCHORED TO THE ROOF
 STRUCTURE.
  
 6) PROVIDE STEAM PIPING DRAWINGS THAT SHOW THE PIPING
 RUNS, TYPES AND SIZES OF PIPE AND PIPE INSULATION.
  
 7) M2.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE
 BOILER PER SECTION 304 FBC-14 FUEL GAS. IT APPEARS BY
 THE DRAWING THAT THE ONE-PERMANENT-OPENING METHOD IS
 BEING PROVIDED. PLEASE SEE SECTION 304.6.2 AND RELOCATE
 THE OPENING OF THE AIR INTAKE TO A LOCATION WITHIN 12
 INCHES OF THE TOP OF THE ENCLOSURE.
  
 8) PROVIDE AN EQUIPMENT PLAN AND SCHEDULES FOR THE
 BREWERY TANKS AND KETTLES. LABEL EACH PIECE OF
 EQUIPMENT AND SHOW THE REQUIRED WORKING CLEARANCES.
 PLEASE NOTE COMPLIANCE WITH SECTION 1003.1 MAY BE
 REQUIRED FOR THE EQUIPMENT.
  
 9) PROVIDE AN EQUIPMENT SCHEDULE FOR THE CHILLED WATER,
 AND PIPING PLANS THAT SHOW PIPING RUNS, TYPES AND SIZES
 OF PIPES AND PIPE INSULATIONS.
  
 10) PROVIDE STRUCTURAL ENGINEERING FOR INSTALLATION OF
 THE RTU'S INCLUDING THE ROOF OPENING AND
 REINFORCEMENTS, ATTACHMENT OF THE CURB TO THE ROOF
 STRUCTURE, AND MOUNTING THE RTU'S TO THE CURBS- SECTION
 301.15.
  
 11) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 THE WALK-IN COOLER AND REFRIGERATION SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2017-03-17 Cont ID  
Sent By shill Date 2017-03-17 Time 15:25 Rev Time 0.00
Received By shill Date 2017-03-17 Time 15:25 Sent To  
Notes
2017-03-17 15:26:04THIS IS A SUBSTANTIAL IMPROVEMENT - $1,000,000 > 50% OF
 PAPA VALUE FOR STRUCTURE $392,458
 ELEVATION CERTIFICATE SHOWS FFE AT 17.6, SO BUILDING
 COMPLIES WITH BFE OF 13.0 + 1' FREEBOARD
 AFTER CONSTRUCTION IS COMPLETE, A FINISHED CONSTRUCTION
 ELEVATION CERTIFICATE WHICH INCLUDES EQUIPMENT
 SERVICING THE BUILDING WILL BE REQUIRED.
  
 FLOOD MAP 1202290020B
 A9, 13' NGVD29
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 10:33 Rev Time 0.00
Received By shill Date 2017-02-16 Time 10:33 Sent To  
Notes
2017-02-16 07:23:03THIS IS A SUBSTANTIAL IMPROVEMENT - $1,000,000 > 50% OF
 PAPA VALUE FOR STRUCTURE $392,458
 SEE BUILDING COMMENTS (NEED ELEVATION OF EQUIPMENT
 SERVICING THE BUILDING)
 ELEVATION CERTIFICATE SHOWS FFE AT 17.6, SO BUILDING
 COMPLIES WITH BFE OF 13.0 + 1' FREEBOARD
  
 FLOOD MAP 1202290020B
 A9, 13' NGVD29

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-04-20 Cont ID  
Sent By tklarge Date 2017-04-20 Time 07:02 Rev Time 0.00
Received By tklarge Date 2017-04-20 Time 06:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-04-10 Cont ID  
Sent By tklarge Date 2017-04-10 Time 13:43 Rev Time 0.00
Received By tklarge Date 2017-04-10 Time 08:21 Sent To  
Notes
2017-04-10 13:43:411) THE LETTER THAT WAS SUBMITTED FROM GLIDDEN SPINA
 PARTNERS FOR THE OCCUPANT LOAD FOR THE REQUIRED
 SANITARY FACILITIES IS UNACCEPTABLE. THE NON-ASSEMBLY
 ROOM NUMBERS ARE LACKING THE CORRESPONDING SQUARE
 FOOTAGE OF EACH ROOM IN ORDER TO CONFIRM THE NEW
 OCCUPANT LOAD. WITHOUT THIS INFORMATION I CANNOT
 DETERMINE THE MINIMUM REQUIRED SANITARY FACILITIES AND
 THIS FACILITY SHALL COMPLY WITH THE POTTY PARITY
 REQUIREMENTS AS MANDATED IN THE 2014 FBC-PLUMBING
 SEC.403.1.3. I DISCUSSED THIS ITEM IN LENGTH WITH THE
 REPRESENTATIVE FROM GLIDDEN SPINA IN A MEETING AND I
 PROVIDED CLEAR DIRECTION AS TO WHAT WOULD BE REQUIRED
 TO MEET THE EXCEPTION LISTED IN SEC. 603.1.3. THE
 DIRECTION THAT I PROVIDED WAS NOT FOLLOWED AND
 THEREFORE THE EXCEPTION HAS NOT BEEN MET. 2ND REQUEST.
 2) SHT. P5.1 - THE VENT FOR THE TRENCH DRAIN LOCATED IN
 ROOM #111 DOES NOT COMPLY WITH 2014 FBC-PLUMBING
 SEC.905.3. THE VENT SHALL CONNECT TO THE HORIZONTAL
 DRAIN ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 3) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE
 VENT COMPLYING WITH ASSA 1012 OR CSA B64.3 PER FBC
 -PLUMBING SEC. 608.16.2. THE NOTE ON THE PLAN REFERS TO
 MANUFACTURER REQUIREMENTS. THIS IS A PLUMBING CODE
 REQUIREMENT AND THE PROPER BACKFLOW DEVICE SHALL BE
 PROVIDED. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-03-27 Cont ID  
Sent By tklarge Date 2017-03-27 Time 09:30 Rev Time 0.00
Received By tklarge Date 2017-03-25 Time 07:54 Sent To  
Notes
2017-03-25 08:09:271) 2014 FBC-PLUMBING SEC.403.1.3 - SEE REQUIREMENTS FOR
 POTTY PARITY.
 403.1.3 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
 2) THE TOILET COMPARTMENT IN THE MEN'S RESTROOM THAT IS
 SHOWN AS A NON-HANDICAPPED ACCESSIBLE COMPARTMENT SHALL
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY SEC.604.8.2 PER
 FAC SEC. SEC.213.3.1. - AMBULATORY ACCESSIBLE
 COMPARTMENTS - (213.3.1- TOILET COMPARTMENTS.)
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES. )
 3) SHT.A-8.0 THE SIDE WALL GRAB BAR FOR THE WATER
 CLOSET IN THE HANDICAPPED ACCESSIBLE TOILET
 COMPARTMENTS SHALL BE LOCATED AS SPECIFIED IN 2014
 FBC-ACCESS. SEC.604.5.1 AND THE REAR WALL GRAB BAR
 SHALL BE LOCATED AS SPECIFIED IN SEC.604.5.2.
 4) SHT. A-1.3 - EQUIPMENT PLAN NOTE #6 REFERS TO AN 80
 GAL. AIR COMPRESSOR BUT IT IS NOT INDICATED ON THE
 FLOOR PLAN. SHOW THE LOCATION ON THE FLOOR PLAN AND
 SUBMIT A COMPRESSED AIR RISER DIAGRAM FOR ANY
 COMPRESSED AIR PIPING TO BE INSTALLED.SHOW TYPE OF
 MATERIAL AND PIPE SIZES, VALVES, ETC. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) SHT. A-9.2 - DETAIL #11 - THE NOTED DIMENSIONS ON
 THE LAVATORY DETAIL ARE VERY SMALL AND ALMOST
 ILLEGIBLE. DETAILS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT.P5.1 - SIZE ALL SECTIONS OF THE VENT SYSTEM ON
 THE SANITARY RISER. COMPLY WITH 2014 FBC-PLUMBING SECS.
 906.1 & 906.2.
 7) THE BRANCH VENT CONNECTING THE STACK VENTS ON THE
 SANITARY RISER SHALL BE INCREASED BY ONE NOMINAL PIPE
 SIZE PER 2014 FBC-PLUMBING SEC. 906.2 - VENTS EXCEEDING
 40 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE
 NOMINAL PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF
 THE VENT PIPE.
 8) SHT. P5.1 - A VENT IS REQUIRED BETWEEN THE TWO WATER
 CLOSETS IN THE WOMEN'S RESTROOM PER 2014 FBC-PLUMBING
 SEC.909.1.
 9) THE TRENCH DRAIN LOCATED IN ROOM #111 SHALL COMPLY
 WITH FBC-PLUMBING TABLE 909.1 FOR THE MAXIMUM DISTANCE
 OF THE FIXTURE TRAP FROM A VENT. THIS WILL BE CHECKED
 IN THE FIELD AND IS NOTED HERE AS A POSSIBLE CODE
 VIOLATION.
 10) SHT. P5.1 - A URINAL IS DISCHARGING INTO THE WET
 VENT AT THE FURTHEST UPSTREAM WATER CLOSETS IN TOILET
 ROOMS #101 & 102. THE URINAL MUST DISCHARGE DOWNSTREAM
 OF THE HORIZONTAL WET VENT PER FBC-PLUMBING SEC.912.1.
 11) THE SANITARY RISER SHOWS A 2 1/2 INCH VENT. WHERE
 DOES THIS VENT CONNECT? CLARIFY.
 12) SIZE THE URINAL WASTE STACKS AND VENTS.
 FBC-PLUMBING SEC.906.1.
 13) THE WATER SUPPLY LINE FOR THE ICE CHEST & BEER
 FILLER SHOWN ON THE WATER RISER SHALL BE EQUIPPED WITH
 A BACKFLOW PREVENTER COMPLYING WITH ASSE 1022 PER
 FBC-PLUMBING SEC.608.3.
 14) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE
 VENT COMPLYING WITH ASSE 1012 OR CSA B64.3.
 FBC-PLUMBING SEC.608.16.2.
 15) ROOM #110 SHOWS THE BOILER BLOW-OFF DISCHARGING TO
 A FLOOR DRAIN. WASTE WATER THAT IS DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT
 GREATER THAN 140 DEGREES FARENHEIT. WHERE HIGHER
 TEMPERATURES EXIST, APPROVED COOLING METHODS SHALL BE
 PROVIDED. 2014 FBC SEC.701.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-21 Cont ID  
Sent By gjohnson Date 2017-02-21 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2017-02-21 Time 14:11 Sent To  
Notes
2017-02-21 15:03:001ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW DIMENSION ON THE PLAN OF THE MIRROR IN
 THE ACCESSIBLE BATHROOM STALL. PER FBC ACC 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 2.PLEASE INDICATE ON PLAN WHICH URINAL IS ACCESSIBLE.
 PER FBC ACC 213.3.3
  
 3. SHT. P-5.1 THE FLOOR DRAINS AND TRENCH DRAINS ARE
 NOT VENTED. PER FBC PL 901.2.1
  
 4. PLEASE COMPLY WITH MECHANICAL COMMENTS. PER WPB
 AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved