| Plan Review Stops For Permit 17010884 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-07 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-07 |
Time |
06:27 |
Sent To |
|
|
| Notes |
| 2017-04-07 07:20:52 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FIRE SPRINKLERS REQUIRED FOR C.O. | | | | | | MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B | | | 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE | | | PUBLIC WAY. | | | | | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE | | | REQUIRED. PER ARCHITECT, ALL OUTDOOR EQUIPMENT IS | | | LOCATED ON THE ROOFTOP. ELEVATION CERTIFICATE IS TO | | | INCLUDE ROOFTOP EQUIPMENT. IF ANY EQUIPMENT IS AT | | | GRADE, A REVISION SHOWING ELEVATION IS REQUIRED | | | (INCLUDING OTHER TENANTS). | | | | | | ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT | | | ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES, | | | TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-17 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-24 |
Time |
06:20 |
Sent To |
|
|
| Notes |
| 2017-03-17 15:24:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FROM PREVIOUS LIST: | | | | | | 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS | | | FOR THE MILL, FBC 107. | | | | | | 2ND REVIEW, A DRAWING WAS PROVIDED. PROVIDE SPEC SHEETS | | | AND INSTALLATION INSTRUCTIONS SO THAT ANY MANUFACTURER | | | REQUIREMENTS CAN BE VERIFIED. THIS MAY BE SENT VIA | | | EMAIL FOR REVIEW. SEE NEW COMMENT REGARDING TWO SETS | | | REQUIRED. WHEN ADDRESSING THAT COMMENT, PROVIDE TWO | | | PAPER SETS FOR ISSUANCE. | | | | | | 9. SEE IMPACT FEE REVIEW. | | | | | | NEW COMMENTS: | | | | | | 10. FBC 107, TWO COMPLETE COLLATED SETS ARE REQUIRED | | | FOR PERMIT ISSUANCE. TWO PLAN SETS WERE PROVIDED BUT | | | ONLY ONE SET OF SUPPORTING DOCUMENTS WAS PROVIDED. THE | | | SET WAS STAPLED ON THE SIDE OF ONE PLAN. IT IS NOT | | | NECESSARY TO STAPLE IT IN THIS MANNER (WE PREFER TWO | | | IDENTICAL CLIPPED SETS OF SUPPORTING DOCUMENTS, TABBED | | | ONLY IF DOCUMENTS ARE EXTREMELY EXTENSIVE). DUE TO WORK | | | LOAD, THERE ARE NOT ANY STAFF PEOPLE AVAILABLE TO | | | PERFORM COPY DUTIES. PROVIDE A SECOND IDENTICAL SET. | | | | | | 11. IS A8.0 A NEW SHEET? I WAS UNABLE TO LOCATE THE OLD | | | SHEET. SEE FBC A 604.4, SEAT HEIGHT TO BE MEASURED AT | | | TOP OF SEAT, DETAIL SHOWS MEASUREMENT TO TOP OF LID. IF | | | THIS SHEET IS REVISED FOR ANOTHER TRADE, REVISE ALL | | | AFFECTED DETAILS. IF IT IS NOT REVISED FOR ANOTHER | | | TRADE, PLEASE ADVISE AND THIS WILL BE REDLINED. PLEASE | | | HAVE THIS CORRECTED ON ALL FUTURE SUBMITTALS. | | | | | | 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING | | | PROVISO: | | | | | | FIRE SPRINKLERS REQUIRED FOR C.O. | | | | | | MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B | | | 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE | | | PUBLIC WAY. | | | | | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE | | | REQUIRED. PER ARCHITECT, ALL OUTDOOR EQUIPMENT IS | | | LOCATED ON THE ROOFTOP. ELEVATION CERTIFICATE IS TO | | | INCLUDE ROOFTOP EQUIPMENT. IF ANY EQUIPMENT IS AT | | | GRADE, A REVISION SHOWING ELEVATION IS REQUIRED | | | (INCLUDING OTHER TENANTS). | | | | | | ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT | | | ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES, | | | TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-02-16 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-02-15 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2017-02-16 10:53:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY, FBC EB | | | CHAPTER 10. REVISE PLAN TO SHOW COMPLIANCE. NO | | | INFORMATION REGARDING BUILDING AREA FBC TABLE 503 WAS | | | PROVIDED. | | | | | | REVISE PLAN TO INCLUDE INFORMATION REGARDING THE OTHER | | | TENANT SPACES, INCLUDING SF AREA AND OCCUPANCY | | | CLASSIFICATION, AND BUILDING TYPE FBC CHAPTER 6. | | | | | | REVISE PLAN TO INCLUDE PREVIOUS OCCUPANCY, FBC EB 1012, | | | TABLES 1012.4, 1012.5, 1012.6. | | | | | | REVISE PLAN TO SHOW COMPLIANCE WITH ALL CHANGE OF | | | OCCUPANCY REQUIREMENTS FBC EB 1012. | | | | | | NO SITE PLAN PROVIDED; THIS WILL LIKELY BE REQUIRED FBC | | | EB TABLE 1012.6. | | | | | | 2. THIS APPEARS TO BE A NON SPRINKLERED BUILDING. | | | SPRINKLERS ARE PROPOSED. SEE FIRE COMMENTS; THIS IS | | | ALSO APPLICABLE FOR BUILDING. IF THE BUILDING IS | | | CURRENTLY FULLY SPRINKLERED, REVISE PLAN TO STATE. IF A | | | NEW SPRINKLER SYSTEM IS PROPOSED, PROVIDE SPRINKLER | | | INFORMATION. | | | | | | IF A NEW SPRINKLER SYSTEM IS PROPOSED, AN ENGINEERING | | | PERMIT IS REQUIRED. CONTACT ENGINEERING DEPARTMENT AND | | | SUBMIT ANY REQUIRED APPLICATIONS. | | | | | | 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS | | | FOR THE MILL, FBC 107. | | | | | | 4. DETAIL 13-A9.0, THE FOOT REST APPEARS TO OBSTRUCT | | | THE REQUIRED TOE CLEARANCE, FBC A 306.2. REVISE PLAN TO | | | SHOW COMPLIANCE. | | | | | | 5. REVISE PLAN TO INCLUDE FINISHED FLOOR ELEVATION, FBC | | | B 1612. THIS IS CONSIDERED A SUBSTANTIAL IMPROVEMENT. | | | | | | 6. PROVIDE A SITE PLAN OR SURVEY WHICH INCLUDES ALL | | | EQUIPMENT AT GRADE. IF ALL EQUIPMENT SERVICING THE | | | BUILDING IS LOCATED ON THE ROOF, REVISE PLAN TO NOTE, | | | FBC B 1612. | | | | | | 7. SHEET A7.0 INCLUDES A NOTE REGARDING PANIC HARDWARE. | | | SEE FBC B 1008.1.10; WILL BOTH EXIT DOORS INCLUDE PANIC | | | BARS? REVISE PLAN TO CLARIFY. | | | | | | 8. PLAN SPECIFIES TRULITE STOREFRONT SYSTEM AND DOORS, | | | OVERHEAD DOORS. PROVIDE PRODUCT APPROVALS, FBC 107. ANY | | | PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT | | | ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES, | | | TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. | | | | | | 9. SEE IMPACT FEE REVIEW. | | | | | | THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISO: | | | | | | MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B | | | 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE | | | PUBLIC WAY. | | | | | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE | | | REQUIRED. THIS SHOULD INCLUDE ALL EQUIPMENT SERVICING | | | THE BUILDING. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-04-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2017-04-11 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2017-04-11 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-03-09 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2017-03-09 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2017-03-07 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-02-02 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2017-02-02 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2017-02-02 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2017-02-02 14:28:06 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | ELECTRIC SERVICE. NEC 110.9, 110.10 | | | | | | PROVIDE THE SERVICE WIRE AND SERVICE MAST SIZE. NEC | | | 230.23 | | | | | | INDICATE THE MINIMUM HEIGHT REQUIRED FOR THE OVERHEAD | | | SERVICE ABOVE THE ALLEWAY TO THE BOTTOM OF THE SERVICE | | | DRIP LOOP. NEC 230.24, 230.26 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE MAIN DISCONNECTING MEANS. NEC 110.16, | | | 110.22, 110.24 | | | | | | PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40 | | | | | | PROVIDE AN INTERSYSTEM BONDING BAR AT THE ELECTRICAL | | | SERVICE. NEC 250.94 | | | | | | PROVIDE THE LOCATION OF THE LIGHTING CONTROL PANEL AND | | | SWITCH BANK. NEC 110.3 | | | | | | PROVIDE A BOLLARD OR EQUALIVENT PROTECTION DETAIL FOR | | | THE ELECTRICAL SERVICE LOCATED IN THE DELIVERY ALLEWAY. | | | NEC 110.2, 110.3, 110.11 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS | | | | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654 | | | 561-373-3701 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2017-03-22 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2017-03-22 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2017-03-22 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-03-22 16:55:35 | PROVISO: ENGINEERING PERMIT IS REQUIRED. | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | PLEASE CONTACT: | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 536-3981 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-02-21 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2017-02-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
mgonzale |
Date |
2017-02-21 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-02-21 16:37:38 | ALL NEW FIRELINE CONNECTIONS TO EXISTING WATERMAINS | | | WILL REQUIRE A SEPARATE SUBMITTAL TO THE CITY OF WPB | | | ENGINEERING DEPT VIA DEVELOPMENT PERMIT. | | | PLEASE SUBMIT TWO SETS OF CIVIL PLANS WITH THE | | | DEVELOPMENT APPLICATION AS CERTIFIED COST ESTIMATE FOR | | | REVIEW. | | | HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO | | | RMS,-PERMITS-APPLICATIONS | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-03-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-03-07 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2017-03-07 15:37:46 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) EOR 61G DOCUMENTS ARE REQUIRED TO BE WITH THIS | | | PERMIT AND WILL ALLOOWED TO BE SUBMITTED AS A REVISION | | | TO THIS PERMIT, BUT PRIOR TO THE SHOP DRAWINGS | | | SUBMITTAL. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | PLEASE DO NOT MISUNDERSTAND AND ENSURE COMPLIANCE WITH | | | THE ABOVE. | | | | | | | | | | | | 2) A MONITORED FIRE ALARM SYSTEM IS REQUIRED TO MONITOR | | | THE FIRE SPRINKLER SYSTEM PER NFPA 101, 5TH EDITION. | | | | | | 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A | | | MULTIPLE OCCUPANCY PROTECTED AS A MIXED OCCUPANCY (SEE | | | 6.1.14) SHALL BE PERMITTED TO BE SERVED BY A COMMON | | | FIRE ALARM SYSTEM, PROVIDED THAT THE INDIVIDUAL | | | REQUIREMENTS OF EACH OCCUPANCY ARE MET. | | | | | | | | | PLEASE PROVIDE A FIRE ALARM FOR MONIORTING THE FIRE | | | SPRINKLER SYSTEM. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-02-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-02-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-02-02 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2017-02-07 13:57:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET ALS1.0 - THERE A SEVERAL OCCUPANCY TYPES | | | INDICATED; HOWEVER, IS THIS A MIXED OCCUPANCY OR | | | SEPARATED OCCUPANCY AND WHAT OCCUPANCY TYPE IS THE | | | PROPOSED PROJECT DESIGNED UNDER. | | | | | | PER THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, NFPA 101 | | | | | | 6.1 CLASSIFICATION OF OCCUPANCY. | | | 6.1.1 GENERAL. | | | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A | | | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR | | | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 | | | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE | | | SUBJECT TO THE RULING OF THE AUTHORITY HAVING | | | JURISDICTION WHERE THERE IS A QUESTION OF PROPER | | | CLASSIFICATION IN ANY INDIVIDUAL CASE. | | | | | | 6.1.14 MULTIPLE OCCUPANCIES. | | | 6.1.14.1 GENERAL. | | | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE | | | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: | | | (1) MIXED OCCUPANCIES ? 6.1.14.3 | | | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 | | | | | | 6.1.14.2 DEFINITIONS. | | | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE | | | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. | | | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE | | | THE OCCUPANCIES ARE INTERMINGLED. | | | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY | | | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE | | | RESISTANCE?RATED ASSEMBLIES. | | | 6.1.14.3 MIXED OCCUPANCIES. | | | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE | | | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 | | | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST | | | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, | | | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. | | | | | | PLEASE PROVIDE THE SPECIFICS FOR COMPLIANCE WITH THE | | | ABOVE NOTED AND RELATED CODES. | | | | | | | | | | | | 2) SHEET ALS 1.0 - A BOLIER IS INDICATED IN ROOM 110. | | | | | | PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS FOR THE | | | BOLIER INCLUDING EXPLOSION HAZARD INFORMATION. PROVIDE | | | ANY RELATED CONSTRUCTION RELATED REVISONS FOR EXPLOSION | | | PROTECTION IF APPLICABLE. | | | | | | | | | 3) SHEET ALS 1.0 - A MILL IS INDICATED IN ROOM 112. | | | | | | PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS FOR THE | | | MILL INCLUDING EXPLOSION HAZARD INFORMATION. PROVIDE | | | ANY RELATED CONSTRUCTION RELATED REVISONS FOR EXPLOSION | | | PROTECTION IF APPLICABLE. | | | | | | PLEASE PROVIDE A NOTE AND/OR REVSIONS RELATED TO MILL | | | ROOM REGARDING ALL WIRING, LIGHTS, SWITCHES, | | | HOUSEKEEPING, ETC, ARE ALL EXPLOSION PROOF, IF | | | APPLICABLE. | | | | | | | | | | | | 4) SHEET A 1.0 - THE INDICATED OCCUPANCY LOAD; 221, AND | | | EXIT CAPACITY; 117, CALCULATIONS DO NOT MATCH. | | | ADDITIONALLY, THERE IS AN INDICATION OF THE EXIT | | | CAPACITY CALCULATION OF .2 LEVEL TRAVEL; HOWEVER, THE | | | TWO EXITS ARE INDICATED WITH STAIRS. | | | | | | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS, STAIRS SHALL | | | BE CALCULATED WITH .3. THE EXIT CAPACITY APPEARS TO BE | | | SUFFICIENT; HOWEVER, THE CALULATIONS NEED CORRECTION. | | | | | | PLEASE PROVIDE CORRECTIONS. | | | | | | | | | | | | 5) SHEET ALS 1.0 - A DOUBLE DOOR EXIT IS INDICATING | | | LEADING INTO THE PATIO. THERE ARE TABLES AND CHAIRS | | | INDICATED IN THE PATIO. THE DOOR SWINGS INTO THE PATIO | | | AND INTO AND RESTRICTING THE EXIT PATHWAY. | | | | | | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS | | | | | | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY | | | OPEN. | | | | | | PLEASE PROVIDE FOR THE REQUIRED WIDTH. | | | | | | | | | 6) SHEET E2.1 & A1.1 - THERE IS ONLY ONE EXIT LIGHTS | | | INDICATED ON THE ON E2.1 AT THE FRONT DOOR. THERE ARE | | | NO OTHER EXITS LIGHTS AS INDICATED ON A1.1 IN THE PATH | | | OF TRAVEL. | | | | | | PLEASE ADD ALL APPLICABLE EXIT LIGHTS PER ALL EXIT PATH | | | AND EXIT DISCHARGE LOCATION. PLEASE ENSURE TO ADD NA | | | EXIT LIGHT INSIDE THE LOADING AREA AT THE STAIRS | | | LEADING TO OTHER EXIT ACCESS. | | | | | | | | | | | | 7) SHEET E2.1- THERE SOME EMERGENCY LIGHTING INDICATED; | | | HOWEVER, IT MAY NOT PROVIDE SUFFICIENT LIGHTING ALONG | | | THE EXXIT PATH OF TRAVEL. | | | | | | PLEASE ESURE THAT ALL EXITS AND EXIT PATHS HAVE THE | | | REQUIRED EMERGENCY LIGHT LUMINATION PER THE OCCUPANCY | | | CLASSIFICATION CODE REQUIREMENTS AS REQUIRED BY # 1 | | | ABOVE. | | | | | | | | | | | | 8) NO SHEET - A NOTE INDICATING THAT A FIRE SPRINKLER | | | SHOP DRAWING WILL BE PROVIDED; HOWEVER, IT APPEARS IT | | | WILL BE A NEW SYSTEM. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | THIS INFORMATION MAY BE PROVIDED WITH AN OFFICIAL | | | SIGNED AND SEALED DRAWING OR LETTER NARRATIVE FORM A | | | QUALIFIED DESIGN PROFESSIONAL. | | | | | | PLEASE PROVIDE DOCUMENTATION PER THE REQUIRMENTS. | | | | | | | | | 9) THERE IS NO INDICATION OF ANY FIRE ALARM SYSTEM. | | | | | | PROVIDE AN APPLICABLE REFERENCE OF A FIRE ALARM SYSTEM | | | PER THE APPLICABLE OCCUPANCY CLASSIFICATION OF # 1 | | | ABOVE AND/OR FOR THE MONITORING OF THE FIRE SPRINKLER | | | SYSTEM. | | | | | | | | | | | | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-04-10 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-04-10 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2017-04-20 06:07:14 | THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED | | | SUBMITTALS. COMPLETE PLANS AND SPECIFICATIONS SHALL BE | | | SUBMITTED FOR REVIEW FOR THE FOLLOWING ITEMS PRIOR TO | | | THE INSTALLATION OF NOTED SYSTEMS: | | | 1) BOILER AND ASSOCIATED PIPING AND VENT - SUBMIT AN | | | EQUIPMENT SCHEDULE FOR THE BOILER, BOILER VENT PIPE(S), | | | AND MANUFACTURER'S SPECIFICATIONS FOR EACH. PROVIDE A | | | DIMENSIONAL ELEVATION VIEW THAT SHOWS THE TOTAL VENT | | | RUN FROM THE OUTLET OF THE BOILER TO THE TERMINATION | | | CAP ABOVE THE ROOF. SHOW HOW THE VENT WILL BE SUPPORTED | | | AND ANCHORED TO THE ROOF STRUCTURE. | | | 2) STEAM PIPING - PROVIDE STEAM PIPING DRAWINGS THAT | | | SHOW THE PIPING RUNS, TYPES AND SIZES OF PIPES & PIPE | | | INSULATION. | | | 3) EQUIPMENT SCHEDULE AND PIPING PLAN FOR THE TANKS AND | | | KETTLES USED IN THE BREWING PROCESS. | | | 4)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, | | | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING | | | DETAILS OF THE GAS VENT(S) PER 2014 FBC-FUEL GAS SECS. | | | 502 THRU 505. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-27 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-27 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2017-03-27 09:42:46 | GAS REVIEW | | | | | | 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE | | | NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC | | | TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS | | | SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ. | | | INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE | | | CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG | | | SIZE BOILER. | | | 2) THERE IS A DISCREPANCY ON THE BTU LOAD OF THE BOILER | | | ON THE MANUFACTURER'S SPECIFICATIONS AND MECHANICAL | | | DRAWINGS M2.1 & M6.1 AND THE GAS RISER ON P5.1. | | | CLARIFY. | | | 3) SHT. P5.1 - THE GAS RISER SHOWS THE BOILER AS | | | 850,000 BTUS AND THE MANUFACTURER'S SPECIFICATIONS | | | SHOWS THE BTU LOAD AS 2,100,000 BTU'S. IF THE BOILER IS | | | 2,100,000 BTU'S THE MINIMUM PIPE SIZE TO THE BOILER | | | SHALL BE 2 1/2 INCHES AND THE SIZE OF THE LINE FROM THE | | | METER SHALL BE INCREASED TO 3 INCHES. 2014 FBC-FUEL GAS | | | TABLE 402.4 (2). | | | 4) THE GAS LINE TO THE GAS WATER HEATER IS UNDERSIZED. | | | THE MINIMUM SIZE SHALL BE 1 1/4 INCHES. 2014 FBC-FUEL | | | GAS TABLE 402.4 (2). | | | 5) THE AJAX BOILER DRAWING # G62200 APPEARS TO SHOW | | | VENTS FOR THE SAFETY VALVES COMBINED WITH THE VENTS FOR | | | THE GAS REGULATOR. THE VENT FOR THE GAS REGULATOR SHALL | | | BE RUN INDEPENDENTLY TO THE OUTDOORS AND SHALL SERVE | | | ONLYY A SINGLE DEVICE VENT. 2014 FBC-FUEL GAS SEC. | | | 410.3.1. | | | 6) SHT. M2.1 - ROOM #110 - SHOWS A 12 INCH ROUND DUCT | | | UP THROUGH THE ROOF BUT IT IS NOT IDENTIFIED AS TO ITS | | | PURPOSE. CLARIFY. | | | | | | THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED | | | SUBMITTALS. COMPLETE PLANS AND SPECIFICATIONS SHALL BE | | | SUBMITTED FOR REVIEW FOR THE FOLLOWING ITEMS PRIOR TO | | | THE INSTALLATION OF NOTED SYSTEMS: | | | 1) BOILER AND ASSOCIATED PIPING AND VENT - SUBMIT AN | | | EQUIPMENT SCHEDULE FOR THE BOILER, BOILER VENT PIPE(S), | | | AND MANUFACTURER'S SPECIFICATIONS FOR EACH. PROVIDE A | | | DIMENSIONAL ELEVATION VIEW THAT SHOWS THE TOTAL VENT | | | RUN FROM THE OUTLET OF THE BOILER TO THE TERMINATION | | | CAP ABOVE THE ROOF. SHOW HOW THE VENT WILL BE SUPPORTED | | | AND ANCHORED TO THE ROOF STRUCTURE. | | | 2) STEAM PIPING - PROVIDE STEAM PIPING DRAWINGS THAT | | | SHOW THE PIPING RUNS, TYPES AND SIZES OF PIPES & PIPE | | | INSULATION. | | | 3) EQUIPMENT SCHEDULE AND PIPING PLAN FOR THE TANKS AND | | | KETTLES USED IN THE BREWING PROCESS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-02-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-21 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-21 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2017-02-21 15:43:17 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402. | | | | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2017-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-25 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-23 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2017-05-24 12:05:36 | IMPACT ROUTED TO SHILL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-04-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-04-20 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-04-14 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2017-04-17 13:12:27 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-04-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2017-04-11 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2017-04-03 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-27 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-06 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-02-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-21 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-24 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-25 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-25 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2017-05-25 12:35:20 | MU 2017-10909 | | | MU 2017-10901 | | | $31,313.58 RDS | | | $853.23 PUB BLD | | | **ESCROW** SEE EMAIL FROM WILLIE SWOPE DATED 5/25/17 | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-02-16 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-02-16 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2017-02-16 10:55:08 | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES HAVE BEEN PAID ARE REQUIRED TO BE SUBMITTED | | | PRIOR TO PERMIT ISSUANCE. | | | | | | 561-233-5025 FOR MORE INFORMATION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-04-10 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-04-10 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-03-13 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-03-13 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2017-03-13 14:29:07 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010884 | | | 3/13/17 | | | | | | 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE | | | NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC | | | TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS | | | SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ. | | | INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE | | | CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG | | | SIZE BOILER. | | | | | | 2) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR | | | SYSTEMS OF THE NEW RTU'S- SECTION 606.2.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-02-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-02-01 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-02-01 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2017-02-01 12:51:39 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010884 | | | 2/1/2017 | | | | | | 1 ) M2.1 & M6.1: THE O/A CALCULATION SCHEDULE IS | | | INCORRECT. RTU-1 IS CONDITIONING THE BAR AREA, NOT | | | RTU-3. | | | | | | 2 ) M6.1: REFER TO TABLE 403.3 AND REVISE THE | | | CALCULATION FOR THE BAR AREA TO 100 PERSONS PER 1000 | | | SF/ 7.5 CFRMS PERSON/ AND 0.18 CFMS PER SF. THE | | | CALCULATION SHOULD ADJUST TO 2186 CFMS OF O/A REQUIRED. | | | PLEASE NOTE THE INCREASED LOAD MAY REQUIRE INCREASED | | | COOLING AND HEATING CAPACITIES FOR RTU-1. | | | | | | 3) THE AC HEATING CALCULATIONS SHOW THE HEAT CAPACITIES | | | OF RTU-1 & 2 ARE UNDERSIZED. | | | | | | 4) THE AC CALCULATIONS DO NOT SHOW ANY APPLIANCE OR | | | EQUIPMENT LOADS. PLEASE CLARIFY IF THE ADDED HEAT AND | | | HUMNIDITY LOAD FROM THE STEAM TANKS AND KETTLES HAVE | | | BEEN CALCULATED INTO THE TOTAL LOAD. | | | | | | 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE BOILER, BOILER | | | VENT PIPE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | EACH. PROVIDE A DIMENSIONED ELEVATION VIEW THAT | | | INDICATES THE TOTAL VENT RUN FROM THE OUTLET OF THE | | | BOILER TO THE TERMINATION CAP ABOVE THE ROOF. INDICATE | | | HOW THE VENT WILL BE SUPPORTED AND ANCHORED TO THE ROOF | | | STRUCTURE. | | | | | | 6) PROVIDE STEAM PIPING DRAWINGS THAT SHOW THE PIPING | | | RUNS, TYPES AND SIZES OF PIPE AND PIPE INSULATION. | | | | | | 7) M2.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE | | | BOILER PER SECTION 304 FBC-14 FUEL GAS. IT APPEARS BY | | | THE DRAWING THAT THE ONE-PERMANENT-OPENING METHOD IS | | | BEING PROVIDED. PLEASE SEE SECTION 304.6.2 AND RELOCATE | | | THE OPENING OF THE AIR INTAKE TO A LOCATION WITHIN 12 | | | INCHES OF THE TOP OF THE ENCLOSURE. | | | | | | 8) PROVIDE AN EQUIPMENT PLAN AND SCHEDULES FOR THE | | | BREWERY TANKS AND KETTLES. LABEL EACH PIECE OF | | | EQUIPMENT AND SHOW THE REQUIRED WORKING CLEARANCES. | | | PLEASE NOTE COMPLIANCE WITH SECTION 1003.1 MAY BE | | | REQUIRED FOR THE EQUIPMENT. | | | | | | 9) PROVIDE AN EQUIPMENT SCHEDULE FOR THE CHILLED WATER, | | | AND PIPING PLANS THAT SHOW PIPING RUNS, TYPES AND SIZES | | | OF PIPES AND PIPE INSULATIONS. | | | | | | 10) PROVIDE STRUCTURAL ENGINEERING FOR INSTALLATION OF | | | THE RTU'S INCLUDING THE ROOF OPENING AND | | | REINFORCEMENTS, ATTACHMENT OF THE CURB TO THE ROOF | | | STRUCTURE, AND MOUNTING THE RTU'S TO THE CURBS- SECTION | | | 301.15. | | | | | | 11) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE | | | THE WALK-IN COOLER AND REFRIGERATION SYSTEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2017-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-17 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-17 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2017-03-17 15:26:04 | THIS IS A SUBSTANTIAL IMPROVEMENT - $1,000,000 > 50% OF | | | PAPA VALUE FOR STRUCTURE $392,458 | | | ELEVATION CERTIFICATE SHOWS FFE AT 17.6, SO BUILDING | | | COMPLIES WITH BFE OF 13.0 + 1' FREEBOARD | | | AFTER CONSTRUCTION IS COMPLETE, A FINISHED CONSTRUCTION | | | ELEVATION CERTIFICATE WHICH INCLUDES EQUIPMENT | | | SERVICING THE BUILDING WILL BE REQUIRED. | | | | | | FLOOD MAP 1202290020B | | | A9, 13' NGVD29 | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2017-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-02-16 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-02-16 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2017-02-16 07:23:03 | THIS IS A SUBSTANTIAL IMPROVEMENT - $1,000,000 > 50% OF | | | PAPA VALUE FOR STRUCTURE $392,458 | | | SEE BUILDING COMMENTS (NEED ELEVATION OF EQUIPMENT | | | SERVICING THE BUILDING) | | | ELEVATION CERTIFICATE SHOWS FFE AT 17.6, SO BUILDING | | | COMPLIES WITH BFE OF 13.0 + 1' FREEBOARD | | | | | | FLOOD MAP 1202290020B | | | A9, 13' NGVD29 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2017-04-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-04-20 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-04-20 |
Time |
06:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-04-10 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-04-10 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2017-04-10 13:43:41 | 1) THE LETTER THAT WAS SUBMITTED FROM GLIDDEN SPINA | | | PARTNERS FOR THE OCCUPANT LOAD FOR THE REQUIRED | | | SANITARY FACILITIES IS UNACCEPTABLE. THE NON-ASSEMBLY | | | ROOM NUMBERS ARE LACKING THE CORRESPONDING SQUARE | | | FOOTAGE OF EACH ROOM IN ORDER TO CONFIRM THE NEW | | | OCCUPANT LOAD. WITHOUT THIS INFORMATION I CANNOT | | | DETERMINE THE MINIMUM REQUIRED SANITARY FACILITIES AND | | | THIS FACILITY SHALL COMPLY WITH THE POTTY PARITY | | | REQUIREMENTS AS MANDATED IN THE 2014 FBC-PLUMBING | | | SEC.403.1.3. I DISCUSSED THIS ITEM IN LENGTH WITH THE | | | REPRESENTATIVE FROM GLIDDEN SPINA IN A MEETING AND I | | | PROVIDED CLEAR DIRECTION AS TO WHAT WOULD BE REQUIRED | | | TO MEET THE EXCEPTION LISTED IN SEC. 603.1.3. THE | | | DIRECTION THAT I PROVIDED WAS NOT FOLLOWED AND | | | THEREFORE THE EXCEPTION HAS NOT BEEN MET. 2ND REQUEST. | | | 2) SHT. P5.1 - THE VENT FOR THE TRENCH DRAIN LOCATED IN | | | ROOM #111 DOES NOT COMPLY WITH 2014 FBC-PLUMBING | | | SEC.905.3. THE VENT SHALL CONNECT TO THE HORIZONTAL | | | DRAIN ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN | | | PIPE. | | | 3) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE | | | EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE | | | VENT COMPLYING WITH ASSA 1012 OR CSA B64.3 PER FBC | | | -PLUMBING SEC. 608.16.2. THE NOTE ON THE PLAN REFERS TO | | | MANUFACTURER REQUIREMENTS. THIS IS A PLUMBING CODE | | | REQUIREMENT AND THE PROPER BACKFLOW DEVICE SHALL BE | | | PROVIDED. 2ND REQUEST. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-27 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-25 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2017-03-25 08:09:27 | 1) 2014 FBC-PLUMBING SEC.403.1.3 - SEE REQUIREMENTS FOR | | | POTTY PARITY. | | | 403.1.3 POTTY PARITY. | | | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO | | | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS | | | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER | | | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE | | | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH | | | SECTION 553.86, FLORIDA STATUTES. | | | EXCEPTION: THIS SECTION DOES NOT APPLY TO | | | ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA | | | STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING | | | OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 | | | PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME | | | NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL | | | OF WATER CLOSETS AND URINALS FOR MEN. | | | 2) THE TOILET COMPARTMENT IN THE MEN'S RESTROOM THAT IS | | | SHOWN AS A NON-HANDICAPPED ACCESSIBLE COMPARTMENT SHALL | | | COMPLY WITH THE 2014 FBC-ACCESSIBILITY SEC.604.8.2 PER | | | FAC SEC. SEC.213.3.1. - AMBULATORY ACCESSIBLE | | | COMPARTMENTS - (213.3.1- TOILET COMPARTMENTS.) | | | WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE | | | TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN | | | ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH | | | 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH | | | 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE | | | PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER | | | CLOSETS TOTALS SIX OR MORE FIXTURES. ) | | | 3) SHT.A-8.0 THE SIDE WALL GRAB BAR FOR THE WATER | | | CLOSET IN THE HANDICAPPED ACCESSIBLE TOILET | | | COMPARTMENTS SHALL BE LOCATED AS SPECIFIED IN 2014 | | | FBC-ACCESS. SEC.604.5.1 AND THE REAR WALL GRAB BAR | | | SHALL BE LOCATED AS SPECIFIED IN SEC.604.5.2. | | | 4) SHT. A-1.3 - EQUIPMENT PLAN NOTE #6 REFERS TO AN 80 | | | GAL. AIR COMPRESSOR BUT IT IS NOT INDICATED ON THE | | | FLOOR PLAN. SHOW THE LOCATION ON THE FLOOR PLAN AND | | | SUBMIT A COMPRESSED AIR RISER DIAGRAM FOR ANY | | | COMPRESSED AIR PIPING TO BE INSTALLED.SHOW TYPE OF | | | MATERIAL AND PIPE SIZES, VALVES, ETC. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 5) SHT. A-9.2 - DETAIL #11 - THE NOTED DIMENSIONS ON | | | THE LAVATORY DETAIL ARE VERY SMALL AND ALMOST | | | ILLEGIBLE. DETAILS SHALL BE OF SUFFICIENT CLARITY TO | | | INDICATE THE NATURE AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SHT.P5.1 - SIZE ALL SECTIONS OF THE VENT SYSTEM ON | | | THE SANITARY RISER. COMPLY WITH 2014 FBC-PLUMBING SECS. | | | 906.1 & 906.2. | | | 7) THE BRANCH VENT CONNECTING THE STACK VENTS ON THE | | | SANITARY RISER SHALL BE INCREASED BY ONE NOMINAL PIPE | | | SIZE PER 2014 FBC-PLUMBING SEC. 906.2 - VENTS EXCEEDING | | | 40 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE | | | NOMINAL PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF | | | THE VENT PIPE. | | | 8) SHT. P5.1 - A VENT IS REQUIRED BETWEEN THE TWO WATER | | | CLOSETS IN THE WOMEN'S RESTROOM PER 2014 FBC-PLUMBING | | | SEC.909.1. | | | 9) THE TRENCH DRAIN LOCATED IN ROOM #111 SHALL COMPLY | | | WITH FBC-PLUMBING TABLE 909.1 FOR THE MAXIMUM DISTANCE | | | OF THE FIXTURE TRAP FROM A VENT. THIS WILL BE CHECKED | | | IN THE FIELD AND IS NOTED HERE AS A POSSIBLE CODE | | | VIOLATION. | | | 10) SHT. P5.1 - A URINAL IS DISCHARGING INTO THE WET | | | VENT AT THE FURTHEST UPSTREAM WATER CLOSETS IN TOILET | | | ROOMS #101 & 102. THE URINAL MUST DISCHARGE DOWNSTREAM | | | OF THE HORIZONTAL WET VENT PER FBC-PLUMBING SEC.912.1. | | | 11) THE SANITARY RISER SHOWS A 2 1/2 INCH VENT. WHERE | | | DOES THIS VENT CONNECT? CLARIFY. | | | 12) SIZE THE URINAL WASTE STACKS AND VENTS. | | | FBC-PLUMBING SEC.906.1. | | | 13) THE WATER SUPPLY LINE FOR THE ICE CHEST & BEER | | | FILLER SHOWN ON THE WATER RISER SHALL BE EQUIPPED WITH | | | A BACKFLOW PREVENTER COMPLYING WITH ASSE 1022 PER | | | FBC-PLUMBING SEC.608.3. | | | 14) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE | | | EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE | | | VENT COMPLYING WITH ASSE 1012 OR CSA B64.3. | | | FBC-PLUMBING SEC.608.16.2. | | | 15) ROOM #110 SHOWS THE BOILER BLOW-OFF DISCHARGING TO | | | A FLOOR DRAIN. WASTE WATER THAT IS DISCHARGED INTO THE | | | BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT | | | GREATER THAN 140 DEGREES FARENHEIT. WHERE HIGHER | | | TEMPERATURES EXIST, APPROVED COOLING METHODS SHALL BE | | | PROVIDED. 2014 FBC SEC.701.9. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-02-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-21 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-21 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2017-02-21 15:03:00 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW DIMENSION ON THE PLAN OF THE MIRROR IN | | | THE ACCESSIBLE BATHROOM STALL. PER FBC ACC 603.3 | | | MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES | | | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE | | | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM | | | ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 2.PLEASE INDICATE ON PLAN WHICH URINAL IS ACCESSIBLE. | | | PER FBC ACC 213.3.3 | | | | | | 3. SHT. P-5.1 THE FLOOR DRAINS AND TRENCH DRAINS ARE | | | NOT VENTED. PER FBC PL 901.2.1 | | | | | | 4. PLEASE COMPLY WITH MECHANICAL COMMENTS. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|