Plan Review Details - Permit 17010881
Plan Review Stops For Permit 17010881
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By jwitmer Date 2017-06-27 Time 17:26 Rev Time 0.00
Received By jwitmer Date 2017-06-27 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2017-01-28 Time 09:28 Sent To  
Notes
2017-01-28 09:30:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010881
 ADD: 4047 OKEECHOBEE BLVD. SUITE # 105& 106.
 CONT: MOSS DEVCO INC.
 TEL:561-876-4570
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 28/2017
 ACTION: DENIED
  
 1) PLEASE NOTE THERE IS A DISCREPANCY IN THE LOCATION
 OF THE PROPOSED WORK TO BE COMPLETED UNDER THIS PERMIT.
 THE PERMIT APPLICATION INDICATES WORK IS TO OCCUR IN
 UNITS 106 & 107, WHEREAS THE PLANS STATE WORK IS TO BE
 COMPLETED IN UNITS 105& 106? PLEASE CORRECT BEFORE THE
 NEXT SUBMISSION TO THE BUILDING DEPARTMENT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF PROPOSED WORK.
  
 2A) SHEET S-1 DISCREPANCY IN PLANS. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. 2014 FBC-B TABLE 603
 RATINGS ON THE ROOF FRAMING MEMBERS. THE SHEET S-1
 INDICATES THE TYPE OF CONSTRUCTION AS A BUILDING TYPE
 I-A REQUIRING 1 1/2 HOUR FIRE RATING, THE SHEET S-1
 INDICATES THE BUILDING IS FIRE SPRINKLERED, UNPROTECTED
 BOTH IA AND IB HAVE FIRE PROTECTED ROOF FRAMING
 MEMBERS. UNDER THE HEADING OF CONSTRUCTION LISTED: 1
 STORY CBS WITH METAL JOIST TYPE IIB NOT REQUIRING ANY
 FIRE PROTECTION ON THE ROOF FRAMING MEMBERS OR
 SECONDARY MEMBERS. PLEASE IDENTIFY THE TYPE OF
 CONSTRUCTION AND CORRECT THE PLANS ACCORDINGLY.
  
 2B) SHEET S2 ON THE LEFT SIDE OF THE SHEET IS A NOTE;
 NEW ONE HOUR PARTY WALLS (BY OTHERS). ARE THESE NEW
 WALLS FURTHER SEPARATING THE BUILDING INTO SMALLER BUT
 MORE BUILDINGS? PARTY WALLS ARE FIRE WALLS. 706.1.1
 PARTY WALLS. ANY WALL LOCATED ON A LOT LINE BETWEEN
 ADJACENT BUILDINGS, WHICH IS USED OR ADAPTED FOR JOINT
 SERVICE BETWEEN THE TWO BUILDINGS, SHALL BE CONSTRUCTED
 AS A FIRE WALL IN ACCORDANCE WITH SECTION 706. PARTY
 WALLS SHALL BE CONSTRUCTED WITHOUT OPENINGS AND SHALL
 CREATE SEPARATE BUILDINGS.
 THESE WALLS WILL NEED TO BE PERMITTED AND COMPLETED
 BEFORE THE TENANT PERMITS CAN BE PERMITTED AND
 CERTIFICATE OF COMPLETION CAN OCCUR.
  
 3) PLEASE NOTE THAT IN UNIT # 107 THE CONVERSION OF A
 KITCHEN FROM A RESTROOM DOES NOT SHOW ON ANY OF THE
 ISSUED PERMITS IN THE ELECTRONIC FILE SYSTEM FILE NET.
 ALL WORK AS SHOWN WILL BE CONSIDERED NEW WORK. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR
 AGENT AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489
 WHO INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE,
 DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR
 STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER,
 REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT RESISTANT
 COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR
 FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD
 RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS
 REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE
 DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT.
  
 4) SHEET S3 IS THE LIFE SAFETY PLAN, PLEASE PROVIDE THE
 LIFE SAFETY PLAN SHOULD HAVE ALL OF THE FURNITURE,
 KIOSK SHOWN ON THE PLANS. PLEASE PROVIDE WHAT THE USAGE
 OF THIS SPACE WILL BE USED FOR, WITH PASS THROUGH AND A
 KITCHEN? 2014 FBC-B 302.1. A ROOM OR SPACE THAT IS
 INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 WHERE A STRUCTURE IS PROPOSED FOR A PURPOSE THAT IS NOT
 SPECIFICALLY PROVIDED FOR IN THIS CODE, SUCH STRUCTURE
 SHALL BE CLASSIFIED IN THE GROUP THAT THE OCCUPANCY
 MOST NEARLY RESEMBLES, ACCORDING TO THE FIRE SAFETY AND
 RELATIVE HAZARD INVOLVED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 13:42 Rev Time 0.00
Received By jleahy Date 2017-07-06 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-21 Cont ID  
Sent By jpearson Date 2017-06-21 Time 07:30 Rev Time 0.00
Received By jpearson Date 2017-06-21 Time 07:30 Sent To  
Notes
2017-06-21 07:33:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2:
 AUTOMATIC RECEPTACLE CONTROL. THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED:
 A. AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP
 RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS,
 ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING
 FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL
 WORKSTATIONS.
 B. AT LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR
 MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION
 DOCUMENTS.
  
 THIS CONTROL SHALL FUNCTION ON:
 A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED
 CONTROL DEVICE THAT TURNS RECEPTACLES OFF A SPECIFIC
 PROGRAMMED TIMES ? AN INDEPENDENT PROGRAM SCHEDULE
 SHALL BE PROVIDED FOR CONTROLLED AREAS OF NO MORE THAN
 5000 SQ. FT. AND NOT MORE THAN ONE FLOOR (THE OCCUPANT
 SHALL BE ABLE TO MANUALLY OVERRIDE THE CONTROL DEVICE
 FOR UP TO TWO HOURS), OR
 B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN 20 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR
 C. AN AUTOMATED SIGNAL FROM ANOTHER CONTROL OR ALARM
 SYSTEM THAT SHALL TURN RECEPTACLES OFF WITHIN 20
 MINUTES AFTER DETERMINING THAT THE AREA IS UNOCCUPIED.
  
 ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED
 TO VISUALLY DIFFERENTIATE THEM FROM UNCONTROLLED
 RECEPTACLES AND ARE TO BE UNIFORMLY DISTRIBUTED
 THROUGHOUT THE SPACE.
  
 PLUG IN DEVICES SHALL NOT BE USED TO COMPLY WITH
 SECTION 8.4.2
  
 EXCEPTIONS: RECEPTACLES FOR THE FOLLOWING SHALL NOT
 REQUIRE AN AUTOMATIC CONTROL DEVICE:
  
 1. RECEPTACLES SPECIFICALLY DESIGNATED FOR EQUIPMENT
 REQUIRING CONTINUOUS OPERATION (24 HOURS/DAY, 365
 DAYS/YEAR).
 2. SPACES WHERE AN AUTOMATIC CONTROL WOULD ENDANGER THE
 SAFETY OR SECURITY OF THE ROOM OR BUILDING OCCUPANTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 15:56 Rev Time 0.00
Received By albarran Date 2017-02-06 Time 15:55 Sent To I
Notes
2017-02-06 15:56:20ACCORDING TO THE NOTES ON THE PLANS, THERE WILL BE NO
 ELECTRIC AS PART OF THIS PERMIT. A NOTE TO SAME WAS
 PLACED ON THE PLANS FOR THE INSPECTOR'S REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-26 Cont ID  
Sent By scaldero Date 2017-06-26 Time 14:11 Rev Time 0.00
Received By scaldero Date 2017-06-26 Time 14:00 Sent To  
Notes
2017-06-26 14:11:37PERMIT # 17010881
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) RESPONSE TO COMMENTS STATES THAT "UNIT 105 & UNIT
 107 ARE THE UNITS PER MANAGEMENT COMPANY". DRAWINGS
 SHOW UNITS 106 AND 107. PLEASE CONFIRM THAT DRAWINGS
 ARE CORRECT.
  
 2) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL OTHER PLAN REVIEWER
 COMMENTS HAVE BEEN SATISFIED.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By scaldero Date 2017-02-01 Time 09:44 Rev Time 0.00
Received By scaldero Date 2017-02-01 Time 09:44 Sent To  
Notes
2017-02-01 09:45:02PERMIT # 17010881
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SEE COMMENTS LISTED UNDER BUILDING REVIEW.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-16 Time 13:03 Sent To  
Notes
2017-06-19 13:03:13B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 15:58 Rev Time 0.00
Received By albarran Date 2017-01-24 Time 11:01 Sent To  
Notes
2017-02-06 15:58:17IN LIEU OF A MISSING EMAIL ADDRESS I CALLED AND SPOKE
 W/JOE OF MOSS DEVCO TO INFORM HIM THAT THE FILE REVIEWS
 HAD BEEN COMPLETED AND WAS READY FOR CORRECTIONS. SENT
 FILE TO SMALL DENIED DRAWER "NM". MA
2017-01-26 11:01:32B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2017-01-28 Time 09:28 Sent To  
Notes
2017-01-28 10:11:49OCCUPANCY UNDETERMINED AT THIS TIME IMPACT FEES MAYBE
 APPLICABLE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-21 Cont ID  
Sent By ccole Date 2017-06-21 Time 17:08 Rev Time 0.00
Received By ccole Date 2017-06-21 Time 16:55 Sent To  
Notes
2017-06-21 17:11:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010881
 6/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED IT BELOW. PLEASE NOTE THAT ADDITIONAL OUTSIDE
 AIR MAY BE REQUIRED WHICH COULD IMPACT THE AC SYSTEMS.
  
 THE PROJECT HAS BEEN IDENTIFIED AS A LEVEL 2 ALTERATION
 FBC-14 EXISTING BUILDING CODE. REFER TO SECTION 809.2
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING AC
 SYSTEMS THAT LIST THE MAKES AND MODELS, THE COOLING AND
 HEATING CAPACITIES, AND SUPPLY CFMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 16:54 Rev Time  
Received By ccole Date   Time   Sent To  
Notes
2017-02-01 16:58:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010881
 2/1/2017AIR.
  
 1) THE PROJECT HAS BEEN IDENTIFIED AS A LEVEL 2
 ALTERATION FBC-14 EXISTING BUILDING CODE. REFER TO
 SECTION 809.2 AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE MECHANICAL ALTERATION PLANS BASED ON THE NEW
 FLOOR PLAN LAYOUT.
  
 3) COMPLY WITH BUILDING PLAN REVIEW COMMENTS TO FURTHER
 CLARIFY THE SCOPE OF THE PROJECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-21 Cont ID  
Sent By gjohnson Date 2017-06-21 Time 13:12 Rev Time 0.00
Received By gjohnson Date 2017-06-21 Time 13:00 Sent To  
Notes
2017-06-21 13:44:081ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. FBC ACC
 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX. BY
 ELIMINATING ONE OF THE BATHROOMS THE OCCUPANCY NO
 LONGER COMPLY WITH THE CODE. THE OCCUPANT LOAD STATED
 IS 18 PEOPLE WHICH IS 3 PERSONS OVER THE 15 PEOPLE FOR
 USE OF A SINGLE UNISEX BATHROOM. YOU MAY PROVIDE A
 SIGNED AND SEALED LETTER TO JUSTIFY RELIEF FROM THE
 CODE.
  
 2. THE THE KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2
 AND 606.3
  
 3. THE PERMIT APPLICATION NEEDS TO BE REVISED TO
 REFLECT SCOPE OF WORK IT NOW STATES THERE IS NO
 PLUMBING OR ELECTRIC PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 4. THE VALUATION OF THE PROJECT APPEARS LOW PLEASE
 PROVIDE DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE
 SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. PER WPB AMEND TO FBC 109.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 10:06 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 09:06 Sent To  
Notes
***NONE***