Plan Review Details - Permit 17010880
Plan Review Stops For Permit 17010880
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-17 Cont ID  
Sent By jwitmer Date 2017-03-17 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2017-03-17 Time 16:18 Sent To  
Notes
2017-03-17 16:18:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010880
 ADD: 4047 OKEECHOBEE BLVD. SUITE # 302& 305
 CONT: MOSS DEVCO INC.
 TEL:561-876-4570
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MARCH 17/2017
 ACTION: BUILDING PROVISO
  
 1) 2014 FBC-ACCESSIBILITY CODE 803.4 BENCHES. A BENCH
 COMPLYING WITH 903 SHALL BE PROVIDED WITHIN THE ROOM.
 903.2 CLEAR FLOOR OR GROUND SPACE. CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 SHALL BE PROVIDED AND
 SHALL BE POSITIONED AT THE END OF THE BENCH SEAT AND
 PARALLEL TO THE SHORT AXIS OF THE BENCH.
  
 1A) 2014 ACCESS. CODE 903.3 SIZE. BENCHES SHALL HAVE
 SEATS THAT ARE 42 INCHES (1065 MM) LONG MINIMUM AND 20
 INCHES (510 MM) DEEP MINIMUM AND 24 INCHES (610 MM)
 DEEP MAXIMUM.
  
 1B) 2014 ACCESS. CODE 903.4 BACK SUPPORT. THE BENCH
 SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE AFFIXED TO A
 WALL. BACK SUPPORT SHALL BE 42 INCHES (1065 MM) LONG
 MINIMUM AND SHALL EXTEND FROM A POINT 2 INCHES (51 MM)
 MAXIMUM ABOVE THE SEAT SURFACE TO A POINT 18 INCHES
 (455 MM) MINIMUM ABOVE THE SEAT SURFACE. BACK SUPPORT
 SHALL BE 21/2 INCHES (64 MM) MAXIMUM FROM THE REAR EDGE
 OF THE SEAT MEASURED HORIZONTALLY.
  
 2) ACCESS. CODE 803.5 COAT HOOKS AND SHELVES. COAT
 HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED WITHIN
 ONE OF THE REACH RANGES SPECIFIED IN 308. SHELVES SHALL
 BE 40 INCHES (1015 MM) MINIMUM AND 48 INCHES (1220 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE
 PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH
 902.3. 2014 ACCESSIBILITY CODE 902.3 HEIGHT. THE TOPS
 OF WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) ACCESS. CODE 904.3.2 COUNTERS. THE COUNTER SURFACE
 HEIGHT SHALL BE 38 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 09:30 Rev Time  
Received By jwitmer Date 2017-01-28 Time 08:15 Sent To  
Notes
2017-01-28 09:22:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010880
 ADD: 4047 OKEECHOBEE BLVD. SUITE # 302& 305
 CONT: MOSS DEVCO INC.
 TEL:561-876-4570
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 28/2017
 ACTION: DENIED
  
 1A) SHEET S-1 DISCREPANCY IN PLANS. 107.2.1.3 ADDIONAL
 INFORMATION REQUIRED. 2014 FBC-B TABLE 603 RATINGS ON
 THE ROOF FRAMING MEMBERS. THE SHEET S-1 INDICATES THE
 TYPE OF CONSTRUCTION AS A BUILDING TYPE I-A REQUIRING 1
 1/2 HOUR FIRE RATING, THE SHEET S-1 INDICATES THE
 BUILDING IS FIRE SPRINKLERED, UNPROTECTED BOTH IA AND
 IB HAVE FIRE PROTECTED ROOF FRAMINF MEMBERS. UNDER THE
 HEADING OF CONSTRUCTION LISTED: 1 STORY CBS WITH METAL
 JOIST TYPE IIB NOT REQUIRING ANY FIRE PROTECTION ON THE
 ROOF FRAMING MEMBERS OR SECONDARY MEMBERS. PLEASE
 IDENTIFY THE TYPE OF CONSTRUCTION AND CORRECT THE PLANS
 ACCORDINGLY.
  
 1B) SHEET S2 ON THE LEFT SIDE OF THE SHEET IS A NOTE;
 NEW ONE HOUR PARTY WALLS (BY OTHERS). ARE THESE NEW
 WALLS FURTHER SEPARATING THE BUILDING INTO SMALLER BUT
 MORE BUILDINGS? PARTY WALLS ARE FIRE WALLS. 706.1.1
 PARTY WALLS. ANY WALL LOCATED ON A LOT LINE BETWEEN
 ADJACENT BUILDINGS, WHICH IS USED OR ADAPTED FOR JOINT
 SERVICE BETWEEN THE TWO BUILDINGS, SHALL BE CONSTRUCTED
 AS A FIRE WALL IN ACCORDANCE WITH SECTION 706. PARTY
 WALLS SHALL BE CONSTRUCTED WITHOUT OPENINGS AND SHALL
 CREATE SEPARATE BUILDINGS.
 THESE WALLS WILL NEED TO BE PERMITEDAND COMPLETED
 BEFORE THE TENANT PERMITS CAN BE PERMITED AND
 CERTIFICATE OF COMPLETION CAN OCCUR.
  
 2) DISCREPANCY IN THE PERMIT APPLICATION UNDER THE
 HEADING OF UNITS. THE PERMIT APPLICATION INDICATES WORK
 TO BE ACCOMPLISHED IN UNITS 302-305. WHEREAS IN THE
 PLANS THERE ARE (2) UNITS BEING REMODELED, UNIT 302 &
 UNIT 305. THE REAL ISSUE IS SHEET S1 INDICATES THE
 OCCUPANCY TYPE AS BUSINESS. SHEET S2 IN UNIT 305
 INDICATES THE UNIT TO BE MERCANTILE( SALES FLOOR
 INDICATED ON PLANS). PLEASE CLARIFY THE TYPE OF USAGE
 AND OCCUPANCY FOR EACH TENANT SPACE.
 2014 FBC-B 302.1 CLASSIFICATION. A ROOM OR SPACE THAT
 IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL
 COMPLY WITH SECTION 508.
  
 3) SHEET S-3 IS INDICATED THE LIFE SAFETY PLAN. THE
 LIFE SAFETY PLAN SHOULD HAVE ALL OF THE FURNITURE,
 KIOSK SHOWN ON THE PLANS. THE TRAVEL DISTANCES WILL
 CHANGE WHEN THERE IS A FURNITURE / KIOSK / RACKS/
 DISPLAYS AND SALE OF MERCHANDISE, STORAGE OF GOODS
 (STORAGE ROOMS SEPARATED OR NON SEPARATED).
 3A) MERCANTILE THE OCCUPANCY LOADS WILL BE DIFFERENT.
 2014 FBC-B TABLE 1004.1.2.
 3B) COMMON PATH OF TRAVEL FOR BUSINESS VS. MERCANTILE
 WILL BE DIFFERENT TABLE 1014.3.
 3C) RESTROOM FIXTURE COUNT WILL DIFFER FOR MERCANTILE
 VS. BUSINESS OCCUPANCY. 2014 FBC-P TABLE403.1.
  
 4) SHEET S-4 INDICATES (2) NEW DRESSING ROOMS,PLEASE
 SHOW COMPLIANCE WITH;
 4A) THE PLANS FOR THE NEW DRESSING ROOMS PROVIDE NO
 DIMENSIONS FOR THE NEW WALL LAYOUT. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 4B) PLEASE PROVIDE WHAT THE DOOR SIZE IS FOR THE NEW
 USE OF THESE ROOMS AS DRESSING ROOMS:
 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF
 EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32
 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 2014 FBC-ACCESS. CODE. ACCESS. CODE404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 4C) 803.1 DRESSING, FITTING, AND LOCKER ROOMS SHALL
 COMPLY WITH 803.
 ADVISORY 803.1 GENERAL.
 PARTITIONS AND DOORS SHOULD BE DESIGNED TO ENSURE
 PEOPLE USING ACCESSIBLE DRESSING AND FITTING ROOMS
 PRIVACY EQUIVALENT TO THAT AFFORDED OTHER USERS OF THE
 FACILITY. SECTION 903.5 REQUIRES DRESSING ROOM BENCH
 SEATS TO BE INSTALLED SO THAT THEY ARE AT THE SAME
 HEIGHT AS A TYPICAL WHEELCHAIR SEAT, 17 INCHES (430 MM)
 TO 19 INCHES (485 MM). HOWEVER, WHEELCHAIR SEATS CAN BE
 LOWER THAN DRESSING ROOM BENCHES FOR PEOPLE OF SHORT
 STATURE OR CHILDREN USING WHEELCHAIRS.
  
 4D) ACCESS. CODE 803.2 TURNING SPACE. TURNING SPACE
 COMPLYING WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 4E) ACCESS. CODE. 803.3 DOOR SWING. DOORS SHALL NOT
 SWING INTO THE ROOM UNLESS A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305.3 IS PROVIDED BEYOND THE ARC
 OF THE DOOR SWING.
  
 4F) ACCESS. CPODE 803.4 BENCHES. A BENCH COMPLYING WITH
 903 SHALL BE PROVIDED WITHIN THE ROOM.
  
 4G) ACCESS. CODE 803.5 COAT HOOKS AND SHELVES. COAT
 HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED WITHIN
 ONE OF THE REACH RANGES SPECIFIED IN 308. SHELVES SHALL
 BE 40 INCHES (1015 MM) MINIMUM AND 48 INCHES (1220 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-17 Cont ID  
Sent By vperez Date 2017-03-17 Time 07:57 Rev Time 0.00
Received By vperez Date 2017-03-17 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 15:40 Rev Time 0.00
Received By albarran Date 2017-02-06 Time 15:34 Sent To I
Notes
2017-02-06 15:40:31ACCORDING TO THE NOTES ON THE PLANS, THERE WILL BE NO
 ELECTRIC AS PART OF THIS PERMIT. A NOTE TO SAME WAS
 PLACED ON THE PLANS FOR THE INSPECTOR'S REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-20 Cont ID  
Sent By scaldero Date 2017-03-20 Time 12:19 Rev Time 0.00
Received By scaldero Date 2017-03-20 Time 12:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By scaldero Date 2017-02-01 Time 09:35 Rev Time 0.00
Received By scaldero Date 2017-02-01 Time 09:34 Sent To  
Notes
2017-02-01 09:35:41PERMIT #17010880
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SEE ALL COMMENTS UNDER BUILDING REVIEW.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-20 Cont ID  
Sent By skennedy Date 2017-03-20 Time 14:42 Rev Time 0.00
Received By skennedy Date 2017-03-16 Time 17:08 Sent To  
Notes
2017-03-16 17:08:33B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 15:42 Rev Time 0.00
Received By albarran Date 2017-01-24 Time 11:01 Sent To  
Notes
2017-02-06 15:42:10IN LIEU OF A MISSING EMAIL ADDRESS I CALLED AND SPOKE
 W/JOE OF MOSS DEVCO TO INFORM HIM THAT THE FILE REVIEWS
 HAD BEEN COMPLETED AND WAS READY FOR CORRECTIONS. SENT
 FILE TO SMALL DENIED DRAWER "NM". MA
2017-01-26 11:02:03B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 09:30 Rev Time  
Received By jwitmer Date 2017-01-28 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 12:32 Rev Time 0.00
Received By ccole Date 2017-03-17 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By ccole Date 2017-02-02 Time 10:10 Rev Time 0.00
Received By ccole Date 2017-02-02 Time 09:55 Sent To  
Notes
2017-02-02 10:14:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010880
 2/217
  
 1) THE PROPOSED PROJECT HAS BEEN CLASSIFIED AS A LEVEL
 2 ALTERATION ON SHEET S-1. REFER TO SECTION 809.1
 FBC-14 EXISTING BUILDING CODE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) THE NEW DRESSING ROOMS REQUIRE EXHAUST VENTILATION
 AT A MINIMUM RATE OF 0.25 CFMS PER SF.- TABLE 403.3.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-17 Cont ID  
Sent By gjohnson Date 2017-03-17 Time 09:41 Rev Time 0.00
Received By gjohnson Date 2017-03-17 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 08:21 Rev Time 0.00
Received By gjohnson Date 2017-02-01 Time 16:47 Sent To  
Notes
2017-02-02 08:25:581ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE SCOPE OF WORK STATES NO PLUMBING WORK BUT PLAN
 INDICATE TWO BATHROOMS BEING CAPPED OF PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 2. A WATER FOUNTAIN IS REQUIRED . PER FBC PL TABLE
 403.1
  
 3. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  