Plan Review Details - Permit 17010872
Plan Review Stops For Permit 17010872
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-07 Cont ID  
Sent By jwitmer Date 2017-08-07 Time 07:43 Rev Time 0.00
Received By jwitmer Date 2017-08-07 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-06-29 Cont ID  
Sent By jwitmer Date 2017-06-29 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2017-06-29 Time 13:21 Sent To  
Notes
2017-06-29 15:07:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010872
 ADD: 120 S. OLIVE AVE. SUITE 102
 CONT: VILLA FRANCA DESIGN & DEVELOPMENT
 TEL: 561-575-2288
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JUNE 29/ 2017
 ACTION: DENIED
  
 1) SHEET A8 & M1.1. THE NEW DESIGN OF THE TENANT SPACE
 WILL REQUIRE REVISIONS TO THE PLANS FOR THE AIR
 HANDLIER LOCATION THAT SERVES THE CORRIDOR. THE
 MECHANICAL PLANS SHOW A HORIZONTAL UNIT WHERE THE OLD
 SET OF PLANS SHOWED A VERTICAL AIR HANDLER WITHIN A A/
 C CLOSET WITHIN THE CORRIDOR. THE NEW LOCATION SHOWS
 THE AIR HANDLIER OVER THE RESTROOM WITH A HARD CEILING
 WITH A 24X36 ACCESS PANEL OUTSIDE OF THE RESTROOM.
 PLEASESHOW A CUT SECTION ABOVE THE CEILING WHERE THE
 ACCESS PANEL IS TO WHERE THE CORRIDOR AIR HANDLER IS
 INSTALLED, PLEASE SHOW ALL DUCTS IN THE VACINITY,
 PLEASE ALSO NOT THEIR IS AN ELECTRICLA PANEL IN THE
 RESTROOM WALL THAT MAY HAVE CONDUITS IN CONFLICT WITH
 ACCES TO THIS UNIT.
 2014 FBC-B- 2801.1 MECHANICAL APPLIANCES, EQUIPMENT AND
 SYSTEMS SHALL BE CONSTRUCTED, INSTALLED AND MAINTAINED
 IN ACCORDANCE WITH THE FLORIDA BUILDING CODE &
 MECHANICAL CODE.
  
 2) SHEET M1.1 SHOWS NEW A/C CONDENSING UNITS INSTALLED
 ON A NEW ROOF TOP A/C STAND. PLEASE PROVIDE THE PRODUCT
 APPROVAL FOR THE STAND AND ANCHORING OF THE STAND AND
 OF THE A/C UNITS TO THE STAND. FOR ALL ROOF TOP
 EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO
 THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2A) 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 2B) THE ROOF TOP PRODUCT APPROVAL FOR A/C STANDS WILL
 BE REQUIRED TO BE REVIEWED BY THE DESIGNER OF RECORD
 BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT.
 EITHER THE CONTRACTOR OR THE DESIGNER OF RECORD WILL
 NEED TO IDENTIFY/ CIRCLE THE FOLLOWING CRITERIA,
 CALCULATING THE AREA OF THE ROOF TOP COMPRESSORS, THE
 MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES , ANCHORS
 AND UPLIFT VERSES MOMENT.
  
 2C) SHEET M1.1 INDICATES THE NEW A/ C COMPRESSORS AND
 STAND WILL BE ON A 3RD FLOOR ROOF. PLEASE PROVIDE
 COMPLIANCE WITH;
 1013.6 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 3) PLEASE PROVIDE HOW THE A/ C COMPRESSOR PIPES ARE
 GOING TO BE ROUTED FROM THE 3RD FLOOR ROOF TO THE 1ST
 FLOOR. PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B
 714.4.1 714.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 714.4.1.1 THROUGH 714.4.1.3.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 11:39 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 11:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-31 Cont ID  
Sent By jwitmer Date 2017-01-31 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2017-01-31 Time 06:28 Sent To  
Notes
2017-01-31 08:57:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010872
 ADD: 120 S. OLIVE AVE. SUITE 102
 CONT: VILLA FRANCA DESIGN & DEVELOPMENT
 TEL: 561-575-2288
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 31/ 2017
 ACTION: DENIED
  
 1) SHEET A1:
 1A) SHEET A1 THE CORRIDORS THAT SURROUND THE TENANT
 SPACE ARE LABELED AS WALL TYPES WT1. SHEET A7 PROVIDES
 THE DETAIL OF WALL TYPE WT1 AND INDICATES THE ASSEMBLY
 FOR THE WALL IS TAKEN FROM THE 2014 FBC-B TABLE
 721.1.(1)(7). PLEASE NOTE THE HEADING FOR THIS WALL
 ASSEMBLY, STRUCTURE PARTS TO BE PROTECTED. APPLIES TO
 STEEL COLUMNS AND ALL PRIMARY TRUSSES.
 PLEASE LOOK AT THE TABLE 721.1(2) (13.1-13.3) THESE ARE
 WALL ASSEMBLIES FOR PARTITION WALLS NONCOMBUSTIBLE
 STUDS.
  
 2) SHEET A7 THERE ARE 2 DETAILS ST1 & WT3 WHICH
 REFERENCE THE 2014 FBC-B TABLE 722.2.1.4(2) TIME
 ASSIGNED TO FINISH MATERIALS ON THE EXPOSED SIDE OF THE
 WALL. PLEASE REVIEW SECTION 722.2.1.4 WALLS WITH GYPSUM
 WALLBOARD OR PLASTER FINISHES, CAST IN PLACE OR PRECAST
 CONCRETE WALLS WITH FINISHES OF GYPSUM WALLBOARD OR
 PLASTER APPLIED TO ONE OR BOTH SIDES SHALL BE PERMITTED
 TO BE CALCULATED IN ACCORDANCE WITH THE PROVISIONS OF
 THIS SECTION.
 FBC-B 713.2 CONSTRUCTION. SHAFT ENCLOSURES SHALL BE
 CONSTRUCTED AS FIRE BARRIERS IN ACCORDANCE WITH 707.
 FBC-B 707.3.1 SHAFT ENCLOSURES. THE FIRE RESISTANCE
 RATING OF THE FIRE BARRIER SEPARATING THE BUILDING AREA
 FROM THE SHAFT SHALL COMPLY WITH SECTION 713.4.
 FBC-B 713.4. FIRE RESISTANCE RATING. SHAFT ENCLOSURES
 SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS THAN THE
 FLOOR ASSEMBLY PENETRATED, BUT NOT NEED EXCEED 2 HOURS.
 SHAFT ENCLOSURES SHALL MEET THE REQUIREMENTS OF
 703.2.1.
 FBC-B 703.2.1. NONSYMMETRICAL WALL CONSTRUCTION.
 INTERIOR WALLS AND PARTITIONS OF NONSYMMETRIC
 CONSTRUCTION SHALL BE TESTED WITH BOTH FACES EXPOSED TO
 THE FURNACE, AND THE SHORTEST DURATION OBTAINED FROM
 THE TWO TESTS CONDUCTED IN ACCORDANCE WITH ASTM E 119
 OR UL 263.
  
 3) SHEET A7 DETAIL WT3 SHOWS SHAFT CONSTRUCTION BUT
 DOES NOT PROVIDE THE PROTECTION FOR THE THROUGH FLOOR
 PENETRATION PER FBC-B 714.4 HORIZONTAL ASSEMBLIES.
 PENETRATIONS OF A FLOOR ASSEMBLY NOT REQUIRED TO BE
 ENCLOSED BY A SHAFT BY SECTION 712.1 SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714.4.1 THROUGH 714.4.2.2.
  
 4) SHEET A1 SHOWS A LUNCH COUNTER DOES SHOW 1
 ACCESSIBLE DINING AREA FACING THE KITCHEN MEETING THE
 0.05% ACCESSIBLE DINING SPACES. THE PLANS ALSO SHOW A
 COUNTER AT 42 INCHES AND 8 UNDER COUNTER BAR STOOLS.
 DISPERSION MAYBE AN ISSUE. A PATRON MAY FEEL THAT
 EQUIVALENCY(SECTION 103) HAS NOT BEEN REACHED SINCE THE
 ONLY ACCESSIBLE SEAT FACES THE KITCHEN. IF THERE WILL
 BE ADDITIONAL OUTSIDE SEASONAL SEATING THEN THE TOTAL
 NUMBER OF SEATS HAS TO BE RECALCULATED MEETING THE
 0.05% ACCESSIBLE DINING AND DISPERSION AS PER SECTION
 226.2 OF THE 2014 ACCESSIBILITY CODE.
  
 5) SHEET A1 SHOWS THE ENTRANCE INTO THE TENANT SPACE IS
 A UNKNOWN, THIS IS A ISSUE THAT NEEDS TO BE DETERMINED
 BEFORE PERMIT ISSUANCE. PLEASE SEE SECTION 202.4.1
 DISPROPORTIONATE COST 2014 ACCESS. CODE. A TENANT CAN
 BE MADE TO SPEND UP TO 20%($18,600.00) OF THE PERMIT
 VALUE $93,000.00 STATED IN THE VALUE OF THE PROJECT.
 THE 1ST ITEM ON THE LIST WHERE FUNDS HAVE TO BE SPENT
 IS AN ACCESSIBLE ENTRANCE.
  
 6) DISPROPORTIONATE COST 202.4.1 EITHER THE CONTRACTOR
 OR DESIGNER OF RECORD ON THEIR LETTER HEAD WILL NEED TO
 SHOW AN ITEMIZED LIST WHERE UP TO THE 20 % OF THE FUNDS
 $18,600.00 IN THE ORDER STATED IN THE CODE SECTION.
  
 7A) THE COVEERSHEET NEEDS TO LIST THE MINIMUM BUILDING
 TYPE FOR A 8 STORY BUILDING. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS: BUILDING (3) TABLE
 503.
  
 7B) THE COVERSHEET INDICATES THIS IS A MERCANTILE
 OCCUPANCY, PLEASE NOTE THAT SMALL ASSEMBLY SPACES
 303.1.2(1) ROOMS USED FOR ASSEMBLY PURPOSES AND THE
 OCCUPANT LOAD IS LESS THAN 50 PERSONS THE OCCUPANCY
 WILL BE CLASSIFIED AS A B OCCUPANCY.
  
 7C) THIS IS A CHANGE OF OCCUPANCY AND NEED TO MEET ALL
 OF THE REQUIREMENTS OF 2014 EXISTING BUILDING CODE
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISITNG BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 (EXISTING
 BUILDING CODE) SHALL APPLY.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-08-03 Cont ID  
Sent By jpearson Date 2017-08-03 Time 14:34 Rev Time 0.00
Received By jpearson Date 2017-08-03 Time 14:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-07-11 Cont ID  
Sent By jpearson Date 2017-07-11 Time 14:50 Rev Time 0.00
Received By jpearson Date 2017-07-11 Time 14:50 Sent To  
Notes
2017-07-11 14:56:23CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHEET E3.1 SHOWS THE CONDUCTOR SIZE FOR THE FEED
 FROM THE EXISTING WIREWAY TO THE METER, FROM THE METER
 TO THE DISCONNECT, AND FROM THE DISCONNECT TO THE PANEL
 AS SIZE 3/0 COPPER. 3/0 IS NOT RATED FOR THE LOAD
 SPECIFIED IN THE LOAD CALCULATION. PROVIDE CORRECT WIRE
 AND CONDUIT SIZE TO HANDLE THE LOAD. NEC 310.15(B)(16),
 NEC CHAPTER 9 TABLES.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-03 Cont ID  
Sent By vperez Date 2017-03-21 Time 08:59 Rev Time 0.00
Received By jpearson Date 2017-03-21 Time 08:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-13 Cont ID  
Sent By vperez Date 2017-02-13 Time 07:49 Rev Time 0.00
Received By vperez Date 2017-02-13 Time 07:48 Sent To  
Notes
2017-02-13 08:05:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN
 HOODS ETC. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 4. PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC EC
 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES
 PER CODE SECTION.
 5. PROVIDE SIZE OF THE J-BOX SHOWN TO EXTEND FEEDERS TO
 NEW PANEL LOCATION. FBC 107.3.5
 6. PLEASE PROVIDE RECEPTACLES OUTLET FOR THE REQUIRED
 SHOW WINDOW RECEPTACLES PER NEC 210.62 AND CALCULATIONS
 PER NEC 220.43A
 7. PLEASE ADDRESS BUILDING AND MECHANICAL COMMENTS
 RELATED TO ELECTRICAL.
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-08-07 Cont ID  
Sent By scaldero Date 2017-08-07 Time 14:36 Rev Time 0.00
Received By scaldero Date 2017-08-07 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2017-07-17 Cont ID  
Sent By scaldero Date 2017-07-17 Time 09:57 Rev Time 0.00
Received By scaldero Date 2017-07-17 Time 09:54 Sent To  
Notes
2017-07-17 09:57:07PERMIT #17010872
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) REVIEW AND RESPOND TO ALL OTHER PLAN REVIEWER
 COMMMENTS.
  
 2) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-15 Cont ID  
Sent By scaldero Date 2017-03-15 Time 14:47 Rev Time 0.00
Received By scaldero Date 2017-03-15 Time 14:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-01 Cont ID  
Sent By scaldero Date 2017-02-01 Time 09:38 Rev Time 0.00
Received By scaldero Date 2017-02-01 Time 09:36 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By fmittner Date 2017-08-29 Time 13:56 Rev Time 0.00
Received By fmittner Date 2017-08-29 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-09-01 Cont ID  
Sent By gjohnson Date 2017-09-01 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 14:34 Sent To  
Notes
2017-08-24 14:34:59B24

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-24 Cont ID  
Sent By lmarchan Date 2017-08-24 Time 14:34 Rev Time 0.00
Received By lmarchan Date 2017-07-28 Time 11:04 Sent To  
Notes
2017-07-31 11:04:14B24

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-31 Cont ID  
Sent By lmarchan Date 2017-07-31 Time 11:02 Rev Time 0.00
Received By lmarchan Date 2017-06-23 Time 13:24 Sent To  
Notes
2017-06-26 13:25:01B24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2017-03-08 Time 11:14 Sent To  
Notes
2017-03-09 11:15:09B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-13 Cont ID  
Sent By vperez Date 2017-02-13 Time 08:05 Rev Time 0.00
Received By vperez Date 2017-02-13 Time 08:05 Sent To  
Notes
2017-01-26 11:34:09B26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-31 Cont ID  
Sent By jwitmer Date 2017-01-31 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2017-01-31 Time 06:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 15:56 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-07-05 Cont ID  
Sent By ccole Date 2017-07-05 Time 14:52 Rev Time 0.00
Received By ccole Date 2017-07-05 Time 14:52 Sent To  
Notes
2017-07-05 15:27:433RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17010872
 7/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CLARIFY HOW ACCESS FOR SERVICE AND REPLACEMENT OF
 THE ABOVE CEILING AIR HANDLERS WILL BE PROVIDED-
 SECTION 306.1. SHOW PANEL LOCATIONS AND PROVIDE
 DIMENSIONS.
  
 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION
 OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING
 PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING
 SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO
 THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR
 REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES DEEP
 AND 30 INCHES WIDE (762 MM BY 762 MM) SHALL BE PROVIDED
 IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE.
  
 2) SHEET D1: PROVIDE HVAC DEMOLITION NOTES. IT APPEARS
 THAT THE EXISTING AIR HANDLER IN THE CORRIDOR CLOSET IS
 BEING REMOVED AND THE CLOSET OPENING WALLED OFF. REFER
 TO COMMENT #1 ABOVE AND CLARIFY HOW THE OWNER OF THE
 UNIT WILL GAIN ACCESS TO IT.
  
 3) M0.1: REVISE SCOPE OF WORK #3 TO INDICATE THAT
 SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST
 SYSTEM AND WALK-IN COOLER. PLEASE NOTE THAT THE
 LOCATION OF THE GREASE HOOD EXHAUST TERMINATION AT THE
 SOUTH WALL MAY NOT BE IN COMPLIANCE WITH SECTION
 506.3.13.2
  
 4) M1.1: PLEASE LABEL THE O/A INTAKE OPENING IN THE
 SIDEWALK AS EITHER NEW OR EXISTING.
  
 5) M1.1: REVISE MECHANICAL PLAN KEY NOTE #1: SECTION
 401.4 FBC-14 MECHANICAL REQUIRES A MINIMUM 10'
 CLEARANCE FROM THE O/A OPENING TO THE STREET, WHICH IS
 ALSO NOTED ON THE PLAN.
  
 6) M1.1: INDICATE HOW ACCESS TO THE FIRE DAMPER IN THE
 FLOOR WILL BE PROVIDED- SECTION 607.4.
  
 7) M1.1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE NEW ROOFTOP CONDENSERS- SECTION 301.15. SEE ALSO
 BUILDING REVIEW COMMENTS.
  
 8) M1.1: IT APPEARS FROM THE DRAWINGS THAT GUARDS WILL
 BE REQUIRED ALONG THE ROOF EDGES IN THE AREA OF THE NEW
 ROOFTOP CONDENSERS. PLEASE SEE SECTION 304.11 AND
 PROVIDE DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-14 Cont ID  
Sent By ccole Date 2017-03-14 Time 17:13 Rev Time 0.00
Received By ccole Date 2017-03-14 Time 17:13 Sent To  
Notes
2017-03-14 17:40:502ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010872
 3/14/17
  
 1) REFER TO SECTION 401.5 AND SHOW THE ACTUAL LOCATION
 OF THE O/A INTAKE ON THE PLAN WITH CLEARANCE DISTANCE
 MEASUREMENTS. PLEASE NOTE THE OPENING MUST BE A MINIMUM
 10' FROM THE STREET.
  
 2) THE SUBMITTED ENERGY FORM C402-2014 CANNOT BE USED
 TO SHOW COMPLIANCE FOR A CHANGE OF OCCUPANCY. PLEASE
 SEE THE HEADING AT THE TOP OF THE FORM AND SECTION
 C101.5.1.1 FBC-14 ENERGY CONSERVATION.
  
 3) THE NARRATIVE RESPONSE TO THE 1ST REVIEW COMMENT #4
 STATES "ALL ELECTRIC APPLIANCES, NO HOOD OR EXHAUST
 REQUIRED" PLEASE NOTE THE EXHAUST RATE OF 0.7 CFMS PER
 SQ. FT. IS REQUIRED REGARDLESS OF THE TYPE OF COOKING
 APPLIANCES- GAS OR ELECTRIC. IN ADDITION PLEASE REFER
 TO SECTION 507.2.1 FBC-14 MECHANICAL WHICH STATES A
 TYPE 1 HOOD IS REQUIRED WHERE COOKING APPLIANCES
 PRODUCE GREASE OR SMOKE.
  
 4) THERE ARE MANUFACTURER'S SPECIFICATIONS SUBMITTED
 FOR A VENTLESS HOOD. PLEASE PROVIDE THE MAKE AND MODEL
 IN THE EQUIPMENT SCHEDULE ON SHEET A2 . ON THE
 MECHANICAL PLANS PROVIDE THE EXHAUST RATE OF THE HOOD,
 INDICATE HOW MAKEUP AIR WILL BE SUPPLIED, AND PROVIDE
 AN AIR BALANCE CALCULATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By ccole Date 2017-02-02 Time 07:41 Rev Time 0.00
Received By ccole Date 2017-02-02 Time 07:31 Sent To  
Notes
2017-02-02 08:04:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010872
 2/2/17
  
 1) THE PROJECT IS CLASSIFIED AS A CHANGE OF OCCUPANCY
 PER SECTION 506.1 FBC-14 EXISTING BUILDING CODE. SPACES
 UNDERGOING A CHANGE OF OCCUPANCY THAT WOULD RESULT IN
 AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL OR
 ELECTRICAL ENERGY SHALL COMPLY WITH FBC-14 ENERGY
 CONSERVATION- SEE SECTIONS C101.4.5 AND C401.2 AND
 PROVIDE DOCUMENTATION OF COMPLIANCE.
  
 2) THE A1 PLAN INDICATES A GAS-FIRED COOKING APPLIANCES
 REQUIRING COMBUSTION AIR. REFER TO SECTION 304.1 FBC-14
 FUEL GAS AND INDICATE HOW THE COMBUSTION AIR WILL BE
 SUPPLIED AND PROVIDE A CALCULATION.
  
 3) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 KITCHEN EXHAUST SYSTEMS, FIRE SUPPRESSION, AND WALK-IN
 COOLERS AND FREEZERS- PLEASE PLACE A NOTE ON THE PLANS
 ACCORDINGLY.
  
 4) AN EXHAUST RATE OF 0.7 CFMS PER SF IS REQUIRED FOR
 THE KITCHEN PER TABLE 403.3. PLEASE INDICATE HOW
 COMPLIANCE WILL BE MET AND PROVIDE AN AIR BALANCE
 CALCULATION THAT INCLUDES ALL EXHAUST RATES IN THE
 SPACE.
  
 5) THE 8X8 O/A DUCT IN THE CRAWLSPACE MUST HAVE AN
 INSULATION VALUE OF MINIMUM R-4.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-09-01 Cont ID  
Sent By gjohnson Date 2017-09-01 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-09-01 Time 12:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-08-17 Cont ID  
Sent By gjohnson Date 2017-08-17 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2017-08-17 Time 09:34 Sent To  
Notes
2017-08-17 11:11:572ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 2ND REQUEST1. PLEASE PROVIDE GREASE INTERCEPTOR SIZING
 CALCULATIONS. PER WPB AMEND TO FBC 107.2.1 I SUGGEST
 HAVING THE MANUFACTURE DO YOUR CALCULATIONS YOU MIGHT
 FIND YOU CAN USE A SMALLER TANK.
  
 2. THE OUTLET OF GREASE INTERCEPTOR IS SHOWN AT 4" THE
 INLET OF THE SUMP PUMP SHOWS 3" THE SANITARY PIPING CAN
 NOT BE REDUCED IN THE DIRECTION OF FLOW. PER FBC PL
 704.2
  
 3. PLEASE PROVIDE MANUFACTURE SPEC FOR SUMP PUMP
 SHOWING THE FLOW RATE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-07-11 Cont ID  
Sent By gjohnson Date 2017-07-11 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2017-07-11 Time 09:43 Sent To  
Notes
2017-07-11 10:10:021ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE OTHER FIXTURES IN KITCHEN AREA SHALL BE
 CONNECTED TO THE GREASE INTERCEPTOR, THE FLOOR DRAIN
 AND FLOOR SINKS AND THE PREP SINK. PER FBC PL 1003.3.1
  
 2. PLEASE PROVIDE GREASE INTERCEPTOR CALCULATIONS. PER
 WPB AMEND TO FBC 107.2.1
  
 3. WITH A OCCUPANT LOAD OF 20 PEOPLE IT IS REQUIRED TO
 PROVIDE SEPARATE FACILITIES FOR EACH SEX. FBC PL 403.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 16:14 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By aaponte Date 2017-08-25 Time 09:57 Rev Time 0.00
Received By aaponte Date 2017-08-25 Time 09:57 Sent To  
Notes
2017-08-25 10:12:56PROVISO: EXTERIOR VENTS SHALL NOT MAKE EXTERIOR NOISE
 OR PROJECT SMELLS OUT INTO THE STREET.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-04-06 Cont ID  
Sent By aaponte Date 2017-04-06 Time 08:58 Rev Time 0.00
Received By aaponte Date 2017-04-06 Time 08:58 Sent To  
Notes
2017-04-06 09:02:231. PROPOSED WALL AT THE NORTH WEST SIDE OF THE SPACE IS
 BLOCKING AN EXISTING WINDOW. PLEASE MOVE THE WALL BACK
 TO MAINTAIN THE WINDOW AND THE VISUAL CONNECTION
 BETWEEN INSIDE AND OUT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  