Plan Review Details - Permit 17010826
Plan Review Stops For Permit 17010826
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-30 Cont ID  
Sent By rmcdouga Date 2017-01-30 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2017-01-30 Time 06:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-23 Cont ID  
Sent By rmcdouga Date 2017-01-23 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2017-01-23 Time 18:10 Sent To  
Notes
2017-01-23 18:24:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT AND ROOF SLOPE. FBC
 107.2.1
  
 2) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTING OF THE BASE SHEET ON THE FLAT ROOF
 AREAS. THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM THAT
 WAS SELECTED (W-11) IS -52.5 PSF WHICH IS NOT ADEQUATE
 FOR ROOF ZONES 2 AND 3. SEE NOTE 7 ON PAGE 2 OF THE
 PRODUCT APPROVAL.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-30 Cont ID  
Sent By rmcdouga Date 2017-01-30 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2017-01-26 Time 15:43 Sent To  
Notes
2017-01-27 15:44:08RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-23 Cont ID  
Sent By rmcdouga Date 2017-01-23 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2017-01-23 Time 16:22 Sent To  
Notes
2017-01-23 16:22:17RMCDOUGAL