Plan Review Details - Permit 17010820
Plan Review Stops For Permit 17010820
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-19 Cont ID  
Sent By shill Date 2018-07-19 Time 13:14 Rev Time 0.00
Received By shill Date 2018-07-19 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-06-07 Cont ID  
Sent By shill Date 2017-06-07 Time 11:48 Rev Time 0.00
Received By shill Date 2017-06-06 Time 17:47 Sent To  
Notes
2017-06-07 12:15:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISION 17020076, WHICH HAS NOT YET BEEN ISSUED,
 HAS A (NEW) NOTE ON SHEET S102 WHICH STATES THAT DESIGN
 PRESSURES MAY BE REDUCED FOR COMPONENTS AND CLADDING.
  
 THE APPROVED PLAN SPECIFIES +-81PSF FOR ZONE 4,
 +81/-148 FOR ZONE 5 (VULT).
  
 PRODUCTS PROPOSED DO NOT MEET DESIGN PRESSURE
 REQUIREMENTS. EITHER SUBMIT PRODUCTS WHICH COMPLY WITH
 THE DPS ON THE APPROVED PLAN, OR HAVE THE REVISION
 ISSUED SO THE NOTE WILL BE APPLICABLE.
  
 2. SCHAEFFER'S (PE) ENGINEERING STATES THAT DESIGN
 PRESSURES ARE BY OTHERS. SEOR'S LETTER STATES THAT THE
 DESIGN PRESSURES ARE ACCEPTABLE. DOCUMENTS SHOULD BE
 CLEAR AS TO WHO IS SPECIFYING DESIGN PRESSURES.
  
 3. A COMPLETE REVIEW OF THE PRODUCT APPROVALS HAVE NOT
 BEEN DONE AT THIS TIME AS DESIGN PRESSURES ARE NOT
 CLEAR. HOWEVER, NOTE THE FOLLOWING:
  
 SCHAEFFER'S LETTER DATED 1/30/17 IS A PHOTOCOPY;
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 VERIFY ALL ENGINEERING IS ORIGINAL; DO NOT SUBMIT COLOR
 COPIES.
  
 4. PROVIDE THREE COLLATED SETS OF DOCUMENTS FOR REVIEW.
 THERE ARE FIVE BOUND SETS OF PAPERWORK. NONE ARE MARKED
 VOID. IT IS NOT CLEAR WHAT NEEDS TO BE REVIEWED.
  
 DEFERRED SUBMITTALS SHOULD INCLUDE ENOUGH INFORMATION
 TO DETERMINE CODE COMPLIANCE AND ALL INFORMATION
 REQUIRED FOR INSPECTIONS.
  
 5. REVISION AND PERMIT STATUS:
  
 REVISION 17020076 - NEEDS IMPACT FEES; ALL OTHER
 REVIEWS HAVE PASSED
 16010520 (SITE LIGHTING) WAS NOT ISSUED; I PRINTED THIS
 TODAY - PLEASE PICK UP PERMIT CARD AND DOWNLOAD PLANS;
 REQUIRED TO BE ON SITE
 17041247 LOW VOLTAGE NOT ISSUED - MUST BE ISSUED PRIOR
 TO COMMENCEMENT OF LOW VOLTAGE WORK - ALL REVIEWS HAVE
 PASSED
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-29 Cont ID  
Sent By shill Date 2017-03-29 Time 15:36 Rev Time 0.00
Received By shill Date 2017-03-29 Time 15:36 Sent To  
Notes
2017-03-29 15:36:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PER BUILDING OFFICIAL, A DESIGN PROFESSIONAL
 LICENSED BY FS471 OR FS481 IS TO SPECIFY DESIGN
 PRESSURES. THE SEOR HAS A DISCLAIMER ON THE REVIEW
 STAMP AND IS NOT TAKING RESPONSIBILITY FOR THE DESIGN
 PRESSURES. SHEET 01 OF 11 PELLA SHOP DRAWINGS INCLUDES
 A STATEMENT THAT IT REQUIRES REVIEW BY A LOCAL
 ENGINEER. SHEET S-102 STATES THAT DESIGN PRESSURES CAN
 BE IN ACCORDANCE WITH FBC. FBC CHAPTER 16 INCLUDES A
 TABLE UP TO 60 FEET. THIS BUILDING IS OVER 60 FEET.
  
 2. PELLA SHOP DRAWINGS - MULLIONS ARE SHOWN. MULLIONS
 ARE REQUIRED TO HAVE ENGINEERING OR PRODUCT APPROVAL,
 FBC 1609. WERE DETAILS FOR THE MULLION INCLUDED IN THE
 MASTER PERMIT? ADVISE WHERE THIS INFORMATION CAN BE
 FOUND, OR SUBMIT AT THIS TIME.
  
 3. THE PRODUCT APPROVAL FOR THE FRENCH DOOR IS EXPIRED;
 GOVERNING CODE FOR THIS PROJECT IS FBC 2014, FS553.
  
 4. DESIGN PRESSURES REVIEWED ARE SUBJECT TO ENGINEERING
 NOT YET RECEIVED WHICH SPECIFY DESIGN PRESSURES FOR
 THIS COMMERCIAL THRESHOLD BUILDING.
  
 5. THIS REVISION WILL BE ISSUED WITH PROVISO;
 INSTALLATION IS TO BE IN CONFORMANCE WITH THE ISSUED
 PERMIT. ALL DOORS IN THE MEANS OF EGRESS FOR ASSEMBLY
 OCCUPANCY TO INCLUDE PANIC BARS OR FIRE EXIT HARDWARE
 FBC B 1008.
  
 6. PLANS ARE DIFFICULT TO READ AND WILL NOT BE LEGIBLE
 AFTER SCANNING DUE TO SIZE OF TEXT, FBC 107; PROVIDE
 FULL SIZE LEGIBLE PLANS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By shill Date 2017-01-26 Time 15:07 Rev Time 0.00
Received By shill Date 2017-01-26 Time 15:07 Sent To  
Notes
2017-01-26 15:24:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REFER TO BULLETIN #5, REVISED PAGE S102. DESIGN
 PRESSURES FOR ZONE 4 IS +-48PSF, ZONE 5 +48.6 / -88.8
 REGARDLESS OF SIZE OF OPENING. REVISE SHEET 1 OF 11
 ACCORDINGLY.
  
 2. FS 553, FLORIDA STATE OR LOCAL PRODUCT APPROVAL IS
 REQUIRED. CUT SHEETS OF COPIED ENGINEERING WHICH MAY BE
 FROM A PRODUCT APPROVAL WERE SUBMITTED. THE CUT SHEETS
 LACK A PRODUCT APPROVAL NUMBER.
  
 IF A LOCAL PRODUCT APPROVAL IS REQUIRED, SEE
 REQUIREMENTS IN FLORIDA STATUTE, PROVIDE ORIGINAL
 ENGINEERING, EVALUATION REPORT, ETC. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS. (PRODUCT APPROVALS
 FOR WHICH THE ORIGINAL IS ON FILE WITH THE STATE ARE
 EXEMPTED FROM THIS STATUTE.)
  
 3. A NOTE ON THE PLANS STATE THAT OPERABLE DOORS ARE TO
 BE INSTALLED IN ZONE 4 ONLY. PLEASE ADVISE AS TO WHICH
 FIXED DOORS ARE PROPOSED IN ZONE 5.
  
 THE FIXED PANEL HAS A DESIGN PRESSURE LIMITATION OF +70
 / -85 PSF, WHICH DOES NOT MEET THE ENGINEER OF RECORD'S
 DESIGN PRESSURE REQUIREMENT FOR ZONE 5. DESIGN
 PRESSURES FOR PRODUCTS INSTALLED IN BOTH ZONES
 (PARTIALLY IN ZONE 4, PARTIALLY IN ZONE 5) MAY, TO THE
 BEST OF MY KNOWLEDGE, BE INTERPOLATED (PLEASE CONSULT
 WITH EOR).
  
 4. THE INSWING DOOR SHOWN ON SHEET 1 (1ST FLOOR H
 INSWING) APPEARS TO HAVE A DESIGN PRESSURE LIMITATION
 OF +40 / -50. IT IS POSSIBLE THAT OTHER DOORS DO NOT
 COMPLY WITH THE ENGINEER OF RECORD'S SPECIFIED DESIGN
 PRESSURES. A COMPLETE REVIEW WAS NOT DONE. IT IS
 SUGGESTED THAT A SCHEDULE SHOWING THE DP LIMIT FOR EACH
 PRODUCT BE CREATED SO COMPLIANCE CAN QUICKLY BE
 VERIFIED.
  
 5. DESIGN PROFESSIONAL IS TO VERIFY THAT ALL PRODUCTS
 APPROVED FOR USE COMPLY WITH THE DESIGN PRESSURES FOR
 THE PROJECT PRIOR TO SUBMITTAL, FBC 107.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-07 Cont ID  
Sent By shill Date 2017-06-07 Time 12:15 Rev Time 0.00
Received By shill Date 2017-05-26 Time 10:21 Sent To  
Notes
2017-05-30 10:22:07RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-29 Cont ID  
Sent By shill Date 2017-03-29 Time 15:36 Rev Time 0.00
Received By shill Date 2017-03-20 Time 06:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-26 Cont ID  
Sent By shill Date 2017-01-26 Time 15:24 Rev Time 0.00
Received By shill Date 2017-01-23 Time 13:20 Sent To  
Notes
2017-01-24 13:20:36SHILL'S DESK