| 2017-06-07 12:15:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. REVISION 17020076, WHICH HAS NOT YET BEEN ISSUED, |
| | HAS A (NEW) NOTE ON SHEET S102 WHICH STATES THAT DESIGN |
| | PRESSURES MAY BE REDUCED FOR COMPONENTS AND CLADDING. |
| | |
| | THE APPROVED PLAN SPECIFIES +-81PSF FOR ZONE 4, |
| | +81/-148 FOR ZONE 5 (VULT). |
| | |
| | PRODUCTS PROPOSED DO NOT MEET DESIGN PRESSURE |
| | REQUIREMENTS. EITHER SUBMIT PRODUCTS WHICH COMPLY WITH |
| | THE DPS ON THE APPROVED PLAN, OR HAVE THE REVISION |
| | ISSUED SO THE NOTE WILL BE APPLICABLE. |
| | |
| | 2. SCHAEFFER'S (PE) ENGINEERING STATES THAT DESIGN |
| | PRESSURES ARE BY OTHERS. SEOR'S LETTER STATES THAT THE |
| | DESIGN PRESSURES ARE ACCEPTABLE. DOCUMENTS SHOULD BE |
| | CLEAR AS TO WHO IS SPECIFYING DESIGN PRESSURES. |
| | |
| | 3. A COMPLETE REVIEW OF THE PRODUCT APPROVALS HAVE NOT |
| | BEEN DONE AT THIS TIME AS DESIGN PRESSURES ARE NOT |
| | CLEAR. HOWEVER, NOTE THE FOLLOWING: |
| | |
| | SCHAEFFER'S LETTER DATED 1/30/17 IS A PHOTOCOPY; |
| | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. |
| | |
| | VERIFY ALL ENGINEERING IS ORIGINAL; DO NOT SUBMIT COLOR |
| | COPIES. |
| | |
| | 4. PROVIDE THREE COLLATED SETS OF DOCUMENTS FOR REVIEW. |
| | THERE ARE FIVE BOUND SETS OF PAPERWORK. NONE ARE MARKED |
| | VOID. IT IS NOT CLEAR WHAT NEEDS TO BE REVIEWED. |
| | |
| | DEFERRED SUBMITTALS SHOULD INCLUDE ENOUGH INFORMATION |
| | TO DETERMINE CODE COMPLIANCE AND ALL INFORMATION |
| | REQUIRED FOR INSPECTIONS. |
| | |
| | 5. REVISION AND PERMIT STATUS: |
| | |
| | REVISION 17020076 - NEEDS IMPACT FEES; ALL OTHER |
| | REVIEWS HAVE PASSED |
| | 16010520 (SITE LIGHTING) WAS NOT ISSUED; I PRINTED THIS |
| | TODAY - PLEASE PICK UP PERMIT CARD AND DOWNLOAD PLANS; |
| | REQUIRED TO BE ON SITE |
| | 17041247 LOW VOLTAGE NOT ISSUED - MUST BE ISSUED PRIOR |
| | TO COMMENCEMENT OF LOW VOLTAGE WORK - ALL REVIEWS HAVE |
| | PASSED |
| | |
| | |
| | |