Plan Review Details - Permit 17010803
Plan Review Stops For Permit 17010803
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-26 Cont ID  
Sent By skennedy Date 2017-01-26 Time 15:22 Rev Time 0.00
Received By skennedy Date 2017-01-26 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By jwitmer Date 2017-01-25 Time 17:25 Rev Time 0.00
Received By jwitmer Date 2017-01-25 Time 12:14 Sent To  
Notes
2017-01-25 17:25:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010803
 ADD: 1450 S. OLIVE AVE.
 CONT: ARENA AMERICAS
 TEL: 407-867-2334
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. JAN. 25/ 2017
 ACTION: DENIED
  
 1) FLOOR PLAN INDICATES AN OCCUPANT LOAD OF 450
 OCCUPANTS. THE STRUCTURE IS 223.75 FT. X 49.5 FT.=
 11075 SQ. FT/ 15 SQ. FT. /OCCUPANT = 739 OCCUPANTS. SEE
 2014 FBC-B TABLE 1004.1.2. THE SEATING PLAN INDICATES A
 TOTAL OF 380 SEATS. PLEASE CONFIRM THE PEOPLE THAT
 WOULD BE SEATED AT THE TABLES WOULD BE THE SAME PEOPLE
 ON THE DANCE FLOOR, THAT THE EVENT HAS LIMITED SEATING
 AND THE REMAINDER OF THE OCCUPANT LOAD OF 450 WOULD BE
 STAFF FOR THE EVENT. THE LIMITING FACTOR IS NOT TO HAVE
 AN OCCUPANT CONTENT NOT GREATER THAN
 500 PERSONS.
 THE FIRST LIMITING FACTOR IS WHEN THE OCCUPANT LOAD IS
 OVER 500 OCCUPANTS IN AN ASSEMBLY OCCUPANCY AND THE
 STRUCTURES SQUARE FOOTAGE EXCEEDS 5,000 SQUARE FEET
 THEN IT IS CONSIDERED A THRESHOLD BUILDING
 NEEDING TO MEET THE REQUIREMENTS OF F. S. 553.71(7).
  
 2) THE SECOND LIMITING FACTOR HAS TO DO WITH THE
 IMPORTANCE FACTOR OF THE BUILDING AS PART OF THE WIND
 DESIGN CRITERIA. PAGE 5 OF 8 WIND SPEED RATING
 INDICATES THE RATING IS TAKEN AT 90 MPH VASD CATEGORY B
 AND BUILDING RISK CATEGORY II.
  
 THE RISK CATEGORY IS FIGURED LOW. SEE THE 2014 FBC-B
 TABLE 1604.5 RISK CATEGORY III STRUCTURES INCLUDES
 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF 300 OR
 MORE. THE IMPORTANCE FACTOR FOR A RISK CATEGORY II
 STRUCTURE IS 1.0 WHEREAS THE IMPORTANCE FACTOR FOR A
 RISK CATEGORY III STRUCTURE IS A 1.15. THE LIMITING
 FACTOR APPEARS TO BE THE PURLINS IN A EXPOSURE C @ 59
 MPH (VASD). WITH THE IMPORTANCE FACTOR OF 1.15 IN AN
 EXPOSURE C THE PURLIN LIMITATION WOULD BE APPROXIMATELY
 51.30 MPH VASD.
  
 THE EVENT MAY NOT PROCEED IF THE WIND SPEED IS FORECAST
 TO EXCEED 50 MPH (VASD) AND THE FABRIC SHALL BE REMOVED
 FROM THE STRUCTURE BEFORE 50 MPH (VASD) WIND SPEED IS
 EXPERIENCED. STATE ON PLANS.
  
 3) THE FLOOD PLAN SHOWS A STAGE BUT DOES NOT PROVIDE
 THE HEIGHT OF THE STAGE, WHAT CRITERIA THE STAGE LIVE
 LOAD WILL BE BUILT TOO? SEE FBC-B 1607.1.
  
 4) THE PLANS ARE DEFICIENT IN PROVIDING STAIRS TO THE
 STAGE AND A RAMP FOR VERTICAL ACCESSIBILITY. 201.1.1
 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY. SEE THE ACCESSIBILITY
 REQUIREMENTS OF 405 FOR RAMPS, AND HANDRAILS AND
 POSSIBLY GUARDRAILS.
  
 5) THE FLOOR PLAN INDICATES THE USE OF AN ADA TRAILER?
 THE FLOOR PLAN INDICATES (2) RESTROOM TRAILERS BUT NO
 ACCESSIBLE RESTROOMS. PLEASE COMMENT IS THE ADA TRAILER
 THE ACCESSIBLE RESTROOMS, HOW DOES A PERSON IN A
 WHEELCHAIR GAIN ENTRY?
 213.2 TOILET ROOMS AND BATHING ROOMS. EXCEPTION # 3. .
 WHERE MULTIPLE SINGLE USER PORTABLE TOILET OR BATHING
 UNITS ARE CLUSTERED AT A SINGLE LOCATION, NO MORE THAN
 5 PERCENT OF THE TOILET UNITS AND BATHING UNITS AT EACH
 CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603. PORTABLE
 TOILET UNITS AND BATHING UNITS COMPLYING WITH 603 SHALL
 BE IDENTIFIED BY THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY COMPLYING WITH 703.7.2.1.
  
 6) PLEASE PROVIDE A FLOOR PLAN SHOWING COMPLIANCE WITH
 2014 FBC-ACCESS. CODE 226. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 7) 2014 ACCESS. CODE 226.2 DISPERSION. DINING SURFACES
 AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 8) 2014 ACCESS. CODE 902.1 DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 902.2 CLEAR FLOOR OR GROUND SPACE.
 8A) A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED
 FOR A FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 8B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-01-26 Cont ID  
Sent By skennedy Date 2017-01-26 Time 15:10 Rev Time 0.00
Received By skennedy Date 2017-01-26 Time 15:10 Sent To  
Notes
2017-01-26 15:22:17A SEPARATE ELECTRICAL PERMIT SUBMITTAL IS FORTHCOMING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2017-01-26 06:48:19INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE A ONE-LINE DIAGRAM REFLECTING ALL
 PANELBOARDS, CORD CONDUCTOR SIZE ARRANGEMENT. FBC
 107.3.5 MINIMUM PLAN REVIEW CRITERIA.
 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL ELECTRICAL
 LOADS; EXAMPLE LIGHTING, RECEPTACLES AND MECHANICAL
 EQUIPMENT. LOAD CALCULATIONS REQUIRED TO BE WITHIN
 GENERATOR CAPACITY. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
 3. SHOW BONDING AND GROUNDING SCHEME FOR THE GENERATOR
 AND ANY CONDUCTIVE METAL PARTS OF THE TENT. FOLLOW NEC
 250 REQUIREMENTS.
 4. PROVIDE A FIXTURE SCHEDULE AND PRODUCT DATA SHEETS
 REFLECTING ALL LIGHTING FIXTURES BEING USED. LISTINGS
 WILL BE VERIFIED. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
 5. PROVIDE GENERAL NOTES TO COMPLY WITH ALL APPLICABLE
 TEMPORARY REQUIREMENTS PER NEC 590, REGARDING GFCI
 PROTECTION, PROTECTION AGAINST ACCIDENTAL DAMAGE
 (CORDS), LAMP PROTECTION, SUPPORTS ETC.
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-25 Cont ID  
Sent By pleduc Date 2017-01-25 Time   Rev Time 0.00
Received By pleduc Date 2017-01-25 Time 13:05 Sent To B
Notes
2017-01-25 15:23:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FINAL REVIEW AND APPROVAL IS PENDING A SITE
 INDPECTION AND VERIFICATION OF APPLICABLE LIFE SAFETY
 FEATURES AND FIRE PREVENTION CONCERNS BY A FIRE
 INSPECTOR.
  
  
 2) ENSURE THAT FIRE FINAL IS CALLED IN AND SCHEDULED
 WHEN ALL EQUIPMENT AND MATERIALS ARE IN PLACE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
2017-01-25 13:05:47REQUESTED ADDITIONAL INFORMATION FROM APPLICANT VIA
 EMAIL CONTACT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-26 Cont ID  
Sent By skennedy Date 2017-01-26 Time 15:22 Rev Time 0.00
Received By skennedy Date 2017-01-26 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-26 Cont ID  
Sent By vperez Date 2017-01-26 Time 06:54 Rev Time 0.00
Received By vperez Date 2017-01-26 Time 06:54 Sent To  
Notes
2017-01-24 11:46:26ROUTED TO TEMP TENT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-01-26 Cont ID  
Sent By vperez Date 2017-01-26 Time 06:54 Rev Time 0.00
Received By vperez Date 2017-01-26 Time 06:54 Sent To  
Notes
2017-01-26 06:54:32PER CHIEF MOSER

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-26 Cont ID  
Sent By skennedy Date 2017-01-26 Time 14:57 Rev Time 0.00
Received By skennedy Date 2017-01-26 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By tklarge Date 2017-01-26 Time 06:35 Rev Time 0.00
Received By tklarge Date 2017-01-26 Time 06:34 Sent To  
Notes
2017-01-26 06:33:261) WHAT IS THE USE OF THE ADA TRAILER? IS THIS A
 HANDDICAPPED ACCESSIBLE RESTROOM TRAILER? CLARIFY. IF
 SO, CLEARLY IDENTIFY IT AS SUCH. COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC.213.2 (3).