Plan Review Details - Permit 17010773
Plan Review Stops For Permit 17010773
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-08 Cont ID  
Sent By cthroop Date 2017-08-08 Time 09:56 Rev Time 0.00
Received By cthroop Date 2017-08-08 Time 08:25 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-07 Cont ID  
Sent By cthroop Date 2017-04-07 Time 13:37 Rev Time 0.00
Received By cthroop Date 2017-04-07 Time 13:34 Sent To FIRE
Notes
2017-04-07 13:41:09BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1. PROVIDE DETAIL FOR NEW FENCE POST TO DECK
 CONNECTION.
 2. PROVIDE REINFORCING DETAIL FOR ALL NEW FENCE/WALL
 LOCATIONS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-10 Cont ID  
Sent By cthroop Date 2017-02-10 Time 10:01 Rev Time 0.00
Received By cthroop Date 2017-02-10 Time 10:01 Sent To  
Notes
2017-02-10 10:02:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED WORK MAY BE ALTERED DUE TO FIRE AND ZONING
 COMMENTS.
 2. COMPLY WITH FIRE AND ZONING COMMENTS AND RE-SUBMIT.
 3. NO BUILDING REVIEW PERFORMED AT THIS TIME.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-08-11 Cont ID  
Sent By pleduc Date 2017-08-11 Time   Rev Time 0.00
Received By pleduc Date 2017-08-10 Time 17:03 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-10 Cont ID  
Sent By pleduc Date 2017-04-10 Time   Rev Time 0.00
Received By pleduc Date 2017-04-10 Time 13:20 Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-07 Cont ID  
Sent By pleduc Date 2017-02-07 Time   Rev Time 0.00
Received By pleduc Date 2017-02-03 Time 16:00 Sent To B
Notes
2017-02-03 17:33:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A1.1 - A WOOD FENCE IS INDICATED AT THE EXIT
 PATH LEADING FROM THE EXIT STAIR DOOR AND HALLWAY EXIT
 DOOR.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 7.2.2.5.2* EXPOSURES.
 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED OPENING
 ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER THAN AN
 EXISTING STAIRWAY, AND THE WALLS OR OPENINGS ARE
 EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF
 LESS THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS
 WITHIN 10 FT (3050 MM) HORIZONTALLY OF THE NONRATED
 WALL OR UNPROTECTED OPENING SHALL BE CONSTRUCTED AS
 REQUIRED FOR STAIRWAY ENCLOSURES, INCLUDING OPENING
 PROTECTIVES.
  
  
 THE NON RATED FENCE IS NOT IN COMPLIANCE WITH THE
 ABOVE, PLEASE CORRECT.
  
  
  
 2) SHEET A1.1 - A CONCRETE WALL IS INDICATED NEXT TO
 THE EXISTING BACKFLOW PREVENTOR. THERE IS NO SEPARATION
 DIMENSION INDICATED AND OR ANY INDICATION THAT THIS
 WALL WILL NOT INTERFERE WITH ANY REPAIR/TESTING AND/OR
 MAINTENANCE WORK.
  
 PER NFPA 24, UNDERGROUND FIRE LINE
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES
 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW
 PREVENTION ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE
 WITH THEIR INSTALLATION INSTRUCTIONS.
  
 NFPA 13
  
 8.17.4.6* BACKFLOW DEVICES.
  
 A.8.17.4.6 WHERE BACKFLOW PREVENTION DEVICES ARE
 INSTALLED, THEY SHOULD BE IN AN ACCESSIBLE LOCATION TO
 PROVIDE FOR SERVICE AND MAINTENANCE.
  
 PLEASE PROVIDE A SPECIFIC SEPARATION DIMENSION AND A
 REVIEW/NARRATIVE FROM THE FIRE SPRINKLER
 INSTALLER/MAINTENANCE CONTRACTOR THAT IT COMPLIES WITH
 THEIR REQUIRMENTS AND/OR THE CODE.
  
  
  
 3) SHEET A1.1 - THERE IA A CONCRETE WALL/STRUCTUREL BY
 THE BACKFLOW PREVENTOR THAT MAY CROSS OVER THE
 UNDERGROUND FIRE LINE.
  
 PER NFPA 24, UNDERGROUND FIRE LINE
  
 10.6 PROTECTION AGAINST DAMAGE.
 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS.
  
 10.6.5* PIPE JOINTS SHALL NOT BE LOCATED UNDER
 FOUNDATION FOOTINGS.
  
  
 PLEASE PROVIDE A DETAILED REVIEW FROM A CERTIFIED
 ENGINEER OR OTHER QUALIFIED ENTITY REGARDING THE ABOVE
 NOTE AND THAT THE WALL WILL NOT INTERFERE WITH ANY
 POSSIBLE CONDITION OR MAINTENANCE/REPAIR CONCERNS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-31 Cont ID  
Sent By eschneid Date 2017-08-31 Time 16:25 Rev Time 0.00
Received By eschneid Date 2017-08-18 Time 09:17 Sent To  
Notes
2017-08-23 09:18:06RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-23 Cont ID  
Sent By lmarchan Date 2017-08-23 Time 09:17 Rev Time 0.00
Received By lmarchan Date 2017-07-19 Time 14:49 Sent To  
Notes
2017-07-20 14:49:48RESUB ROUTED TO FIRE ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-25 Cont ID  
Sent By eschneid Date 2017-04-25 Time 14:05 Rev Time 0.00
Received By eschneid Date 2017-03-30 Time 15:48 Sent To  
Notes
2017-03-31 15:50:02RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-10 Cont ID  
Sent By cthroop Date 2017-02-10 Time 10:00 Rev Time 0.00
Received By cthroop Date 2017-01-23 Time 09:20 Sent To  
Notes
2017-01-25 09:20:29ROUTED TO ZONING

Review Stop Z ZONING
Rev No 4 Status F Date 2017-08-31 Cont ID  
Sent By eschneid Date 2017-08-31 Time 16:24 Rev Time 0.25
Received By eschneid Date 2017-08-31 Time 16:24 Sent To  
Notes
2017-08-31 16:25:47FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE PROPOSED INSTALLATION OF THE
 WALL AND FENCES CHANGES THE APPROVED SITE PLAN AND THUS
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT PRIOR TO THE APPROVAL OF THIS PERMIT
 APPLICATION BY ZONING. PLEASE SUBMIT AN APPLICATION TO
 THE CITY'S PLANNING DIVISION.
  
 2) ONCE THE MINOR AMENDMENT IS SUBMITTED ZONING WILL
 APPROVE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
2017-08-24 14:50:41ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 3 Status F Date 2017-08-04 Cont ID  
Sent By eschneid Date 2017-08-04 Time 11:46 Rev Time 0.25
Received By eschneid Date 2017-08-04 Time 11:46 Sent To B
Notes
2017-08-04 11:48:01FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE PROPOSED INSTALLATION OF THE
 WALL AND FENCES CHANGES THE APPROVED SITE PLAN AND THUS
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT PRIOR TO THE APPROVAL OF THIS PERMIT
 APPLICATION BY ZONING. PLEASE SUBMIT AN APPLICATION TO
 THE CITY'S PLANNING DIVISION.
  
 2) THE LANDSCAPE PLANS IS INCONSISTENT WITH THE CHANGES
 TO SHEET A1.1 (USE OF EXISTING RAIL INSTEAD OF THE NEW
 SCREEN WALL AND THE CONCRETE WALL INSTEAD OF THE
 ALUMINUM WALL). ALL PLANS NEED TO SHOW THE SAME
 CONDITIONS.
  
 3) ONCE THE MINOR AMENDMENT IS SUBMITTED AND THE PLANS
 ALL MATCH, ZONING WILL APPROVE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
2017-07-20 16:59:55ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 2 Status F Date 2017-04-25 Cont ID  
Sent By eschneid Date 2017-04-25 Time 14:04 Rev Time 0.50
Received By eschneid Date 2017-04-25 Time 14:04 Sent To  
Notes
2017-04-25 14:05:15FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE PROPOSED INSTALLATION OF THE
 WALL AND FENCES CHANGES THE APPROVED SITE PLAN AND THUS
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT PRIOR TO THE APPROVAL OF THIS PERMIT
 APPLICATION BY ZONING. PLEASE SUBMIT AN APPLICATION TO
 THE CITY'S PLANNING DIVISION.
  
 2) THE PLANS ARE INCONSISTENT. SHEET A1.1 - NOTE 1
 CALLS OUT AN ALUMINUM SCREEN WALL AND DETAIL A1/A1.2
 SHOWS THIS AS ALUMINUM, WHILE DETAIL A3/A1.2 DESCRIBES
 THIS AS A NEW DECORATIVE WOOD FENCE.
  
 3) REPEAT COMMENT: THE NEW SCREEN WALL WILL CREATE AN
 UNSAFE SITUATION BETWEEN VEHICLES ENTERING THE SITE AND
 THOSE EXITING THE LOADING BAYS BY BLOCKING THE
 VISIBILITY AT THE INTERSECTION. THE VIEW IN THIS AREA
 MAY NOT BE OBSTRUCTED. THIS WALL SEEMS TO HAVE LIMITED
 SCREENING POTENTIAL.
  
 4) REPEAT QUESTION: DRAWING L5 ON SHEET A1.2 SHOWS
 VALET ENTRANCES ON EITHER SIDE OF THE WALL THAT IS
 BEING TREATED WITH THE VENEER PANELS. PLEASE EXPLAIN
 THIS NOTE (VALET ENTRANCE). THIS AREA IS NOT PERMITTED
 FOR VALET OPERATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  
2017-04-11 16:08:37ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By eschneid Date 2017-02-02 Time 14:09 Rev Time 0.75
Received By eschneid Date 2017-02-02 Time 14:09 Sent To FIRE
Notes
2017-02-02 14:12:41FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) THE PROPOSED INSTALLATION OF THE WALL AND FENCES
 CHANGES THE APPROVED SITE PLAN AND THUS REQUIRES THE
 APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR
 TO THE APPROVAL OF THIS PERMIT APPLICATION BY ZONING.
 PLEASE SUBMIT AN APPLICATION TO THE CITY'S PLANNING
 DIVISION.
  
 2) THERE IS A PLANTING BED TO THE SOUTH OF THE BACKFLOW
 PREVENTER, WHICH APPEARS TO BE IN DIRECT CONFLICT WITH
 THE PROPOSED WALL LOCATION. YOU MAY NOT REDUCE THE
 AMOUNT OF LANDSCAPE ON THE SITE. PROVIDE HOW THE
 LANDSCAPE SQUARE FOOTAGE AND MATERIAL WILL BE
 PRESERVED.
  
 3) FLOOR PLAN KEY NOTE 5 ON SHEET A1.1 CALLS OUT AN 8
 FOOT CMU WALL; HOWEVER, THE WALL IS SHOWN AT 6 FEET IN
 HEIGHT ON SHEET A1.2.
  
 4) THE PROPOSED CMU WALL (AT EITHER SIX OR EIGHT FEET)
 WILL BLOCK THE REQUIRED PEDESTRIAN AHEAD SIGN. PROVIDE
 HOW THIS WARNING NOTICE WILL BE RETAINED IN A LOCATION
 WHICH NOTIFIES DRIVERS OF THE UPCOMING PEDESTRIAN
 WALKWAY AND CROSSING?
  
 5) THE PROPOSED CMU WALL WILL OBSTRUCT DRIVERS FROM
 SEEING PEOPLE EXITING THE STAIRWELL IN THE CASE OF A
 EMERGENCY.
  
 6) THE NEW CYPRESS WOOD SCREEN WALL WILL CREATE AN
 UNSAFE SITUATION BETWEEN VEHICLES ENTERING THE SITE AND
 THOSE EXITING THE LOADING BAYS BY BLOCKING THE
 VISIBILITY AT THE INTERSECTION.
  
 7) DRAWING L5 ON SHEET A1.2 SHOWS VALET ENTRANCES ON
 EITHER SIDE OF THE WALL THAT IS BEING TREATED WITH THE
 VENEER PANELS. PLEASE EXPLAIN THIS NOTE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
2017-01-26 14:15:07ROUTED TO ERIC SCHNEIDER