Plan Review Details - Permit 17010714
Plan Review Stops For Permit 17010714
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-07 Cont ID  
Sent By cthroop Date 2017-03-07 Time 08:47 Rev Time 0.00
Received By cthroop Date 2017-03-06 Time 15:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-13 Cont ID  
Sent By cthroop Date 2017-02-13 Time 08:57 Rev Time 0.00
Received By cthroop Date 2017-02-13 Time 08:57 Sent To  
Notes
2017-02-13 08:59:54BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
 2. COMPLY WITH ELECTRICAL COMMENTS AND RE-SUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-27 Cont ID  
Sent By cthroop Date 2017-01-27 Time 15:30 Rev Time 0.00
Received By cthroop Date 2017-01-27 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-03-06 Cont ID  
Sent By njwira Date 2017-03-01 Time 17:54 Rev Time 0.00
Received By vperez Date 2017-03-06 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-10 Cont ID  
Sent By albarran Date 2017-02-10 Time 10:29 Rev Time 0.00
Received By albarran Date 2017-02-10 Time 09:40 Sent To B
Notes
2017-02-10 10:33:18ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) & CITY
 AMENDMENTS TO THE 2015 FBC
  
 ELECTRICAL PLAN REVIEW COMMENTS
  
  
 PROJECT NAME: SOLAR PV ELECTRIC INSTALL
 JOB ADDRESS: 310 35TH ST.
 DESCRIPTION: INSTALLATION OF ROOFTOP SOLAR ELECTRIC
 SYSTEM, INCLUDING PANELS, INVERTER, MOUNTING RAILS AND
 WEATHERPROOFING
 MASTER PERMIT: 17010714
  
  
 PLANS FOR THE ABOVE MENTIONED PERMIT WERE REVIEWED FOR
 COMPLIANCE WITH THE CODES HEREIN DESCRIBED FOR THE
 SECOND TIME. FOLLOWING YOU WILL SEE NOTES ADDRESSING
 THE REQUIRED CORRECTIONS. ADDITIONAL CORRECTIONS MAY BE
 REQUIRED AFTER REVIEW OF YOUR RESUBMITTAL.
  
 1. THE SUBMITTED NARRATIVE FOR THE CORRECTIONS REFERS
 TO SHEET NUMBERS NOT FOUND ON PLAN SET.
 2. SECTION 107.2.1.4 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT BUILDING PLANS BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE. YOU HAVE SUBMITTED HALF SIZE
 PLANS WHICH ARE UNACCEPTABLE. SUBMIT FULL SIZE SHEETS
 AS MENTIONED HEREIN SO THAT REVIEWS CAN BE COMPLETED
 PROPERLY.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 MIKE ALBARRAN, CONTRACT ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH, PH. (561) 805-6746
 EMAIL: [email protected] OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By mvaldes Date 2017-01-26 Time 14:44 Rev Time 0.00
Received By mvaldes Date 2017-01-26 Time 10:54 Sent To  
Notes
2017-01-26 15:27:131ST REVIEW 2014 5TH FBC ED. NEC 2014
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PV SOLAR LINE SIDE TAP EQUIPMENT GROUNDING
 CONDUCTORS SHALL BE GROUPED TOGETHER PER NEC 690.47(F)
  
 2] USING THE PV MAXIMUM SHORT CIRCUIT PLUS THE UTILITY
 AVAILABLE FAULT CURRENT SHOW AIC CALCULATIONS TO VERIFY
 SHORT CIRCUIT RATING OF EQUIPMENT. NEC 110.24, 110.10,
 110.9
  
 3] CLARIFY WHY FROM THE AC DISCONNECT TO THE AC
 COMBINER AN 8 AWG IS BEING USED WHEN A 6 AWG IS BEING
 USED FROM THE DISCONNECT TO THE MAIN SERVICE PANEL. (8
 AWG = 40 AMPS ON 60 DEGREE TERMINALS) ( AC INVERTER
 OUTPUT CURRENT IS 21 AMPS X 125% X 2 INVERTERS = 52.5
 AMPS)
  
 4] IN ACCORDANCE WITH NEC 705.50 INTERCONNECTED
 ELECTRIC POWER PRODUCTION SOURCES SHALL BE GROUNDED IN
 ACCORDANCE WITH ARTICLE 250. THEREFORE THE PV AC
 DISCONNECT SHALL BE BONDED TO THE CASE & SERVICE RATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-07 Cont ID  
Sent By cthroop Date 2017-03-07 Time 08:47 Rev Time 0.00
Received By cthroop Date 2017-02-21 Time 14:41 Sent To  
Notes
2017-02-22 14:41:23RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-13 Cont ID  
Sent By cthroop Date 2017-02-13 Time 08:56 Rev Time 0.00
Received By cthroop Date 2017-02-07 Time 12:52 Sent To  
Notes
2017-02-08 12:53:01RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-27 Cont ID  
Sent By cthroop Date 2017-01-27 Time 15:20 Rev Time 0.00
Received By cthroop Date 2017-01-19 Time 13:35 Sent To  
Notes
2017-01-23 13:36:00ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2017-03-01 Cont ID  
Sent By njwira Date 2017-03-01 Time 17:54 Rev Time 0.00
Received By njwira Date 2017-02-24 Time 11:32 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By njwira Date 2017-02-09 Time 16:05 Rev Time 0.00
Received By njwira Date 2017-02-08 Time 16:44 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-24 Cont ID  
Sent By njwira Date 2017-01-24 Time 16:12 Rev Time 0.00
Received By njwira Date 2017-01-23 Time 14:48 Sent To E
Notes
***NONE***