Plan Review Details - Permit 17010676
Plan Review Stops For Permit 17010676
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2017-03-02 Cont ID  
Sent By Mgonzale Date 2017-03-02 Time   Rev Time 1.00
Received By mgonzale Date 2017-03-02 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-07 Cont ID  
Sent By wjolin Date 2017-03-07 Time 14:38 Rev Time 0.00
Received By wjolin Date 2017-03-07 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By wjolin Date 2017-02-15 Time 08:04 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 07:46 Sent To  
Notes
2017-02-15 08:04:30SHEET C5.02: RELOCATE FIRE HYDRANT 75 FEET TO THE
 SOUTHEAST. THIS WILL PUT IT CLOSER TO THE FIRE LANE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-13 Cont ID  
Sent By ccole Date 2017-03-13 Time 14:43 Rev Time 0.00
Received By ccole Date 2017-03-06 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By lmarchan Date 2017-03-06 Time 09:45 Rev Time 0.00
Received By lmarchan Date 2017-02-02 Time 12:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By ccole Date 2017-03-13 Time 14:41 Rev Time 0.00
Received By ccole Date 2017-03-13 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By ccole Date 2017-02-14 Time 12:48 Rev Time 0.00
Received By ccole Date 2017-02-14 Time 12:48 Sent To  
Notes
2017-02-14 13:43:131ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010676
 2/14/17
  
 1) THE LICENSING SCOPE FOR BOTH A GENERAL CONTRACTOR
 AND A UNDERGROUND UTILITIES CONTRACTOR DOES NOT INCLUDE
 INSTALLATION OF PIPING THAT IS AN INTEGRAL PART OF A
 FIRE PROTECTION SYSTEM BEGINNING AT A POINT WHERE THE
 PIPING IS USED EXCLUSIVELY FOR SUCH SYSTEM- PLEASE SEE
 FL. STATUTES 489.113(2)(D), 489.105(3)(N), AND 633.102.
  
 2) SHEET C5.02: THE PLAN APPEARS INCOMPLETE FOR THE
 SCOPE OF WORK. PLEASE SHOW THE UNDERGROUND FIRE LINE
 RUN BEGINNING AT THE POINT OF CONNECTION TO THE MAIN
 WATER LINE TO THE BUILDING. PLEASE SHOW THE LOCATION OF
 THE REQUIRED BACK FLOW PREVENTER, AND PROVIDE PIPING
 DETAILS AND SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-13 Cont ID  
Sent By cpuell Date 2017-03-13 Time 14:51 Rev Time 0.00
Received By cpuell Date 2017-03-13 Time 14:43 Sent To  
Notes
2017-03-13 14:44:19DIG-SIGS ON ALL PLAN SHEETS VERIFED/CCOLE