Plan Review Details - Permit 17010600
Plan Review Stops For Permit 17010600
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-01-26 Cont ID  
Sent By shill Date 2019-01-26 Time 11:39 Rev Time 0.00
Received By shill Date 2019-01-26 Time 11:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 11:32 Rev Time 0.00
Received By shill Date 2018-10-29 Time 11:32 Sent To  
Notes
2018-10-29 11:32:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. THIS MAY BE SENT VIA EMAIL OR MAY BE PROVIDED WHEN
 RESUBMITTING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 08:02 Rev Time 0.00
Received By shill Date 2018-05-22 Time 08:01 Sent To  
Notes
2018-05-22 08:03:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. THIS MAY BE SENT VIA EMAIL OR MAY BE PROVIDED WHEN
 RESUBMITTING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By jgomez Date 2017-02-23 Time 13:51 Rev Time 0.00
Received By jgomez Date 2017-02-22 Time 16:59 Sent To  
Notes
2017-02-22 17:46:49RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE ARE TWO SEPARATE STRUCTURES. MAIN HOUSE AND
 GUEST HOUSE. NEED A PERMIT APPLICATION FOR EACH
 STRUCTURE. THIS WILL AVOID CONFUSION AND WILL
 FACILITATE PLAN REVIEW, INSPECTIONS AND RECORDS
 RETENTION. SEC. 105.1 AND SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 2-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- PROPOSED GUEST HOUSE:
 A) NEW BEDROOM #2: IT APPEARS THAT 3043SH WINDOW
 DOESN'T COMPLY WITH EGRESS SEC. R310.1 FBC-RESIDENTIAL,
 5TH EDITION (2014). IT DOESN'T SEEM TO PROVIDE THE
 REQUIRED 24" CLEAR HEIGHT. PROVIDE MANUFACTURER'S CUT
 SHEETS SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS.
  
 B) PROVIDE COMPLETE WALL SECTION FOR WALL LOCATED BY
 THE GARAGE DOORS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SPECIFY FINISHES ON BOTH SIDES. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS AS SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AND CLEARLY SPECIFY MULLION SIZE TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
  
 C) ALL THE SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/DETAILS AND SPECIFICATIONS. PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO LIST
 THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
 NOTE: FLORIDA PRODUCT APPROVAL LISTED ON THE CONNECTOR
 SCHEDULE ON SHEET S-1.0 IS FOR THE 2010 CODE VERSION.
 NEED TO PROVIDE FLORIDA PRODUCT APPROVAL FOR THE 2014
 CODE VERSION.
  
 D) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL THE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 NOTE: COORDINATE WITH PRODUCT APPROVALS REQUIRED FOR
 THE MAIN HOUSE TO AVOID HAVING MORE THAN 2 COPIES FOR
 EACH PRODUCT APPROVAL.
  
 4- MAIN HOUSE: REMODELED BEDROOMS:
 A) IT APPEARS THAT 3043SH BEDROOM WINDOWS DON'T COMPLY
 WITH EGRESS SEC. R310.1 FBC-RESIDENTIAL. IT DOESN'T
 SEEM TO PROVIDE THE REQUIRED 24" CLEAR HEIGHT. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING COMPLIANCE WITH THE
 EGRESS REQUIREMENTS.
  
 B) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS AND CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES.
  
 B) ALL THE SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/DETAILS AND SPECIFICATIONS. PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO LIST
 TH FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
 NOTE: FLORIDA PRODUCT APPROVAL LISTED ON THE CONNECTOR
 SCHEDULE ON SHEET S-1.0 IS FOR THE 2010 CODE VERSION.
 NEED TO PROVIDE FLORIDA PRODUCT APPROVAL FOR THE 2014
 CODE VERSION.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL THE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 5- SECTION A/A-2 ON SHEET A-2.0:
 A) REVISE THE ROOF SLOPE TO COMPLY WITH SEC. R905.11.1
 FBC-RESIDENTIAL.
  
 B) ROOF SHEATHING SPECIFICATIONS DON'T MATCH ROOF
 SHEATHING SPECIFICATIONS SPECIFIED ON SHEET S-1.0.
 REVISE AS REQUIRED TO MATCH. CLARIFY ROOF SHEATHING
 THICKNESS AND NUMBER OF LAYERS. NOTE: SEC. R803.2.3.1
 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS MIN.
  
 C) ROOF INSULATION: THERE ARE TWO DIFFERENT TYPES OF
 INSULATION SPECIFIED. TAPERED INSULATION WITH THE ROOF
 ASSEMBLY AND R-30 BATT INSULATION BETWEEN ROOF JOISTS.
 CLARIFY IF BOTH INSULATIONS ARE GOING TO BE INSTALLED.
 COORDINATE WITH ROOFING PRODUCT APPROVAL SUBMITTED.
 SEC. R806 FBC-RESIDENTIAL.
  
 6- FOUNDATION PLAN ON SHEET S-1.0:
 A) IS MISSING THE CONCRETE BLOCK WALL VERTICAL
 REINFORCEMENT AS REQUIRED BY SEC. R609.3.3
 FBC-RESIDENTIAL. NOTE: SEE FOUNDATION NOTES ON SAME
 SHEET FOR REINFORCEMENT SPACING.
  
 B) PLAN SHOWS SEC. I/S-2. WHERE IS SECTION I/S-2?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- ROOF FRAMING PLANS ON SHEET S-1.0:
 A) REVISE ROOF SLOPE TO COMPLY WITH SEC. R905.11.1
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE CROSS VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL. SPECIFY HOW GETTING THE CROSS
 VENTILATION ON 2X12 SOLID ROOF JOISTS. NOTE: ALSO TAKE
 INTO ACCOUNT THAT THE 2X12 BLOCKING DOESN'T ALLOW AIR
 MOVEMENT.
  
 C) PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE OVERFLOW DRAINS AND SCUPPERS AS REQUIRED BY SEC.
 R903.4.1 FBC-RESIDENTIAL.
  
 D) PLAN SHOWS SEC. I/S-2. WHERE IS SECTION I/S-2?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 8- CURRENT CODE IS THE FBC 5TH EDITION (2014). NOTES ON
 DRAWINGS A-1.0, A-3.0 AND S-1.0 REFERENCE THE 2010 FBC.
 REVISE AS REQUIRED. CHAPTER 553 F.S.
  
 9- FLAT ROOF NOA'S SUBMITTED (NOA 15-0203.05 AND
 14-1030.02):
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 COORDINATE WITH ITEM #5(C) ABOVE. IS IT GOING TO BE AN
 INSULATED FLAT ROOF ASSEMBLY OR ROOF IS GOING TO BE
 INSULATED BETWEEN ROOF JOISTS?
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA'S. NOTE: CALCULATIONS ARE REQUIRED IF THE SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES.
  
 10- PLANS NEED TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS. TILE BLOCK STATES THAT PLANS
 WERE DRAWN BY H.V.
 NOTE: IF THE DESIGNER IS THE CONTRACTOR, THEN
 CONTRACTOR TO PROVIDE PROOF THAT HE/SHE IS QUALIFIED TO
 CERTIFY PLANS AS REQUIRED BY SEC. 489.115 (4)(B)2. THE
 FOLLOWING IS A COPY OF THAT SECTION: ?"IN ADDITION, THE
 BOARD MAY APPROVE SPECIALIZED CONTINUING EDUCATION
 COURSES ON COMPLIANCE WITH THE WIND RESISTANCE
 PROVISIONS FOR ONE AND TWO FAMILY DWELLINGS CONTAINED
 IN THE FLORIDA BUILDING CODE AND ANY ALTERNATE
 METHODOLOGIES FOR PROVIDING SUCH WIND RESISTANCE WHICH
 HAVE BEEN APPROVED FOR USE BY THE FLORIDA BUILDING
 COMMISSION. DIVISION I CERTIFICATE-HOLDERS OR
 REGISTRANTS WHO DEMONSTRATE PROFICIENCY UPON COMPLETION
 OF SUCH SPECIALIZED COURSES MAY CERTIFY PLANS AND
 SPECIFICATIONS FOR ONE AND TWO FAMILY DWELLINGS TO BE
 IN COMPLIANCE WITH THE CODE OR ALTERNATE METHODOLOGIES,
 AS APPROPRIATE, EXCEPT FOR DWELLINGS LOCATED IN
 FLOODWAYS OR COASTAL HAZARD AREAS AS DEFINED IN SS.
 60.3D AND E OF THE NATIONAL FLOOD INSURANCE PROGRAM."
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD SHEETS. SUBMITT OLD SHEETS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-04 Cont ID  
Sent By jpearson Date 2018-10-04 Time 09:15 Rev Time 0.00
Received By jpearson Date 2018-10-04 Time 08:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-17 Cont ID  
Sent By jpearson Date 2018-05-17 Time 07:50 Rev Time 0.00
Received By jpearson Date 2018-05-15 Time 13:51 Sent To  
Notes
2018-05-17 07:49:18APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
  
 PLAN REVIEW STATUS: DENIED. SEE COMMENTS BELOW:
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5 (AIC CALCULATION NOT PROVIDED. NEC
 110.10)
 2. CORRECTED.
 3. CORRECTED.
 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3 (NOT PROVIDED.)
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. ON MAIN SERVICE THE SERVICE CONDUCTORS CANNOT BE
 SHOWN WITH EQUIPMENT GROUNDING CONDUCTOR AS THE
 GROUNDED CONDUCTOR OR NEUTRAL WILL BE THE RETURN PATH
 BACK TO SOURCE. FBC RES E3607 (THE SERVICE CONDUCTORS
 TO THE FIRST MEANS OF DISCONNECT HAVE BEEN CORRECTED,
 HOWEVER, FROM THE FIRST MEANS OF DISCONNECT TO THE
 INTERIOR PANEL IS NOW SHOWN WITHOUT THE REQUIRED EGC.
 PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6,
 3607.3.1)
 10. GUEST HOUSE NOW ON SEPARATE PERMIT.
 11. GUEST KITCHEN NOW ON SEPARATE PERMIT.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
  
 NEW COMMENT:
  
 18. PANEL A SHOWS A 6-3 ROMEX WIRE ON A 60 AMP BREAKER
 FOR AHU 1. THE ALLOWABLE AMPACITY FOR ROMEX WIRE SHALL
 NOT EXCEED THAT OF A 60 DEGREE CELCIUS RATING.
 THEREFORE, THE AMPACITY FOR 6-3 ROMEX IS 55 AMPS AND IS
 NOT SUFFICIENT FOR A 60 AMP CIRCUIT. PROVIDE
 CORRECTION. NEC 334.80; FBC RE E3705.4.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-13 Cont ID  
Sent By vperez Date 2017-02-13 Time 09:08 Rev Time 0.00
Received By vperez Date 2017-02-13 Time 09:08 Sent To  
Notes
2017-02-13 09:43:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 200AMP
 SERVICE. 2/0 CONDUCTOR TO PROTECT 180AMP CALCULATED
 LOAD. FBC RES E3603
 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 5. SHOW EXTERIOR RECEPTACLE AT FRONT ENTRANCE TO MAIN
 HOUSE PROTECTED BY GFCI DEVICE. FBC RES E3902.3
 6. PLEASE ADDRESS WALL SPACE RECEPTACLE REQUIREMENTS
 PER FBC RES E3901.2.2, 1. ANY SPACE THAT IS 2FT OR MORE
 IN WIDTH. SEE NEW GUEST ROOM AND ROOM ADJACENT TO
 KITCHEN.
 7. SMOKE DETECTORS TO MAINTAIN A 3FT CLEARANCE FROM FAN
 BLADES, FBC RES 314
 8. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET/
 MAIN HOUSE
 9. ON MAIN SERVICE THE SERVICE CONDUCTORS CANNOT BE
 SHOWN WITH EQUIPMENT GROUNDING CONDUCTOR AS THE
 GROUNDED CONDUCTOR OR NEUTRAL WILL BE THE RETURN PATH
 BACK TO SOURCE. FBC RES E3607
 10. GUEST HOUSE: SHOW A RECEPTACLE W/P GFCI PROTECTED
 AT THE HVAC AC LOCATION FOR SERVICE PER FBC RES
 E3901.12 HVAC OUTLET/ MINI SPLITS
 11. GUEST KITCHEN RECEPTACLES TO LABELED GFCI
 PROTECTED. FBC RES E3902.6
 12. SHOW SMOKE DETECTORS FBC RES 314/315
 13. RECEPTACLE AT THE LAUNDRY ROOM 6FT OF SINK TO BE
 LABELED AS GFCI PROTECTED. FBC RES E3902.7
 14. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 15. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR
 DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC
 RES E3703.2 AND 4
 16. ELECTRICAL SHEET TO BE SIGNED AND SEALED BY
 DESIGNER OF RECORD OR ELECTRICAL QUALIFIER. FBC 107.3.5
 17. SHOW SMOKE DETECTORS ON DRAWINGS CLARIFY IF
 EXISTING OR NEW. FBC RES 314.
 18. COMMENTS MAT FOLLOW UPON RESUMITTAL. FEEL FREE TO
 CONTACT ME SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2017-01-23 Cont ID  
Sent By scaldero Date 2017-01-23 Time 10:21 Rev Time 0.00
Received By scaldero Date 2017-01-23 Time 10:20 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-05-03 Cont ID  
Sent By fmittner Date 2018-05-03 Time 12:02 Rev Time 0.00
Received By fmittner Date 2018-05-03 Time 12:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-02-08 Cont ID  
Sent By fmittner Date 2017-02-08 Time 08:38 Rev Time 0.00
Received By fmittner Date 2017-02-08 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-26 Cont ID  
Sent By shill Date 2019-01-26 Time 11:39 Rev Time 0.00
Received By shill Date 2019-01-23 Time 10:44 Sent To  
Notes
2019-01-25 10:44:53RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 11:32 Rev Time 0.00
Received By shill Date 2018-09-24 Time 13:48 Sent To  
Notes
2018-09-26 13:48:37R03

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 08:28 Rev Time 0.00
Received By shill Date 2018-04-19 Time 15:07 Sent To  
Notes
2018-04-20 15:07:55R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-24 Cont ID  
Sent By cpuell Date 2017-02-24 Time 13:10 Rev Time 0.00
Received By cpuell Date 2017-01-18 Time 14:08 Sent To  
Notes
2017-01-27 17:48:2601/27/17 CHANGED PERMIT TYPE FROM COMMERCIAL TO
 RESIDENTIAL. CHANGED BIN NUMBER TO R-12. JG.
2017-01-19 14:08:42C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-01-26 Cont ID  
Sent By shill Date 2019-01-26 Time 11:39 Rev Time 0.00
Received By shill Date 2019-01-26 Time 11:39 Sent To  
Notes
2019-01-26 11:39:51MU 18-41934, 225 SF, $0 DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 08:01 Rev Time 0.00
Received By shill Date 2018-05-22 Time 08:01 Sent To  
Notes
2018-05-22 08:02:022-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE. (GUEST HOUSE, PERMIT 18051003)
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By jgomez Date 2017-02-23 Time 07:22 Rev Time 0.00
Received By jgomez Date 2017-02-23 Time 07:22 Sent To  
Notes
2017-02-23 07:22:312-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By cmontell Date 2018-10-25 Time 14:38 Rev Time 0.00
Received By cmontell Date 2018-10-25 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-07 Cont ID  
Sent By cmontell Date 2018-05-07 Time 14:13 Rev Time 0.00
Received By cmontell Date 2018-05-07 Time 13:33 Sent To  
Notes
2018-05-07 14:13:09GUEST STUDIO
 PER 2014 FLORIDA RESIDENTIAL CODE SEC M1602.2
 PROHIBITED SOURCES. (4)
 4. A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, GARAGE,
 BOILER ROOM, FURNACE ROOM, UNCONDITIONED ATTIC OR OTHER
 DWELLING UNIT.
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By jvalido Date 2017-02-23 Time 18:36 Rev Time 0.00
Received By jvalido Date 2017-02-23 Time 17:28 Sent To  
Notes
2017-02-23 18:11:43CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE REFRIGERANT PIPING DETAIL ON PLANS FOR THE
 GUEST HOUSE.
 (2) PROVIDE CONDENSER TIE DOWN DETAIL.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) PROVIDE ON THE PLANS WHO DREW THE PLANS.
 AS PER:
 R103.1 GENERAL.
 CONSTRUCTION DOCUMENTS AND OTHER SUPPORTING DATA SHALL
 BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION
 FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY THE STATUTES OF THE JURISDICTION IN WHICH
 THE PROJECT IS TO BE CONSTRUCTED. WHERE SPECIAL
 CONDITIONS EXIST, THE CODE OFFICIAL IS AUTHORIZED TO
 REQUIRE NECESSARY CONSTRUCTION DOCUMENTS TO BE PREPARED
 BY A REGISTERED DESIGN PROFESSIONAL.
  
 (4) PROVIDE HEAT LOAD CALCULATIONS WITH EQUIPMENT
 SIZING.
 AS PER:
 R403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 (5) PROVIDE AHRI OF ALL EQUIPMENT.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By tklarge Date 2018-05-21 Time 12:28 Rev Time 0.00
Received By tklarge Date 2018-05-21 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By gjohnson Date 2017-02-09 Time 14:08 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 11:02 Sent To  
Notes
2017-02-09 14:30:581ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLANS ARE NOT SIGNED AND SEALED. THEY SHALL COMPLY
 WITH WPB AMEND TO FBC 107.2.1 ALL INFORMATION,
 DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2.SHOW LAUNDRY SINK ON RISER DIAGRAM FOR GUEST HOUSE.
 PER WPB AMEND TO FBC 107.2.1
  
 3. A CLEAN OUT IS REQUIRED NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL
 708.3.5
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 08:28 Rev Time 0.00
Received By shill Date 2018-05-22 Time 08:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By jgomez Date 2017-02-23 Time 14:32 Rev Time 0.00
Received By jgomez Date 2017-02-23 Time 12:48 Sent To  
Notes
2017-02-23 14:32:351- FLAT ROOF NOA'S SUBMITTED (NOA 15-0203.05 AND
 14-1030.02):
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 COORDINATE WITH ITEM #5(C) ABOVE. IS IT GOING TO BE AN
 INSULATED FLAT ROOF ASSEMBLY OR ROOF IS GOING TO BE
 INSULATED BETWEEN ROOF JOISTS?
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA'S. CALCULATIONS ARE REQUIRED IF THE SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-03 Cont ID  
Sent By fmittner Date 2018-05-03 Time 12:03 Rev Time 0.00
Received By fmittner Date 2018-05-03 Time 12:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-08 Cont ID  
Sent By fmittner Date 2017-02-08 Time 08:38 Rev Time 0.00
Received By fmittner Date 2017-02-08 Time 08:38 Sent To  
Notes
***NONE***