Plan Review Details - Permit 17010585
Plan Review Stops For Permit 17010585
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-16 Cont ID  
Sent By jwitmer Date 2017-03-16 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2017-03-16 Time 09:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 07:46 Rev Time  
Received By jwitmer Date 2017-01-28 Time 06:16 Sent To  
Notes
2017-01-28 07:46:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010585
 ADD: 319 CLEMATIS ST. SUITE # 508 & 510
 CONT: GERARD CONTRACTING
 TEL: 561-832-9785
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 28/2017
 ACTION: DENIED
  
 1) SHEET A-1.0 THE ENTRY DOOR JUST TO THE RIGHT OF THE
 ELEVATOR LOBBY SHOWS AS NEW WORK AS IN FILL AN EXISTING
 OPENING. THE PLANS DO NOT PROVIDE COMPLIANCE FOR
 MANEUVERING CLEARANCES AT MANUAL SWING DOORS PER
 SCETION 404.2.4 OF THE 2014 FBC-ACCESSIBILITY CODE AND
 FIGURE 404.2.4.1 (A). MANEUVERING CLEARANCE OF 18
 INCHES LATCH SIDE OF THE DOOR.
  
 2) SHEET A-1.0 DETAIL D NEW BREAK ROOM ELEVATION SHOWS
 A SHELF HOLDING A MICROWAVE AT AN ELEVATION OF 4 FOOT
 10 INCHES OR 58 INCHES ABOVE THE FINISH FLOOR.
 2A) THE MICROWAVE MUST MEET ONE OF THE TWO REACH
 RANGES:
 308.2.2 OBSTRUCTED HIGH REACH.
 308.3.2 OBSTRUCTED HIGH REACH.
  
 2B) 309.1. OPERABLE PARTS SHALL COMPLY WITH 309.
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 3) 202.4.1 DISPROPORTIONATE COST. THE CONTRACT VALUE AS
 STATED INDICATES A CONTRACT VALUE OF $31,500. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 202.4.1 CAN REQUIRE UP
 TO 20% ($6,300.00) OF THE CONTRACT VALUE IN ACCESSIBLE
 UPGRADES TO THE TENANT SPACE. THE SEQUENCE IN HOW THE
 FUNDS ARE TO BE SPENT WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE NOTE THE BATHROOM WITHIN THE TENANT SPACE DOES
 NOT MEET THE REQUIREMENTS FOUND IN THE 2014
 FBC-ACCESSIBILITY CODE:
 604.3.1 SIZE
 604.4 SEATS.
 604.5 GRAB BARS.
 604.7 DISPENSERS
 606.1 LAVATORIES AND SINKS SHALL COMPLY WITH 606.
 608.1 SHOWER COMPARTMENTS SHALL COMPLY WITH 608.
  
 EITHER THE CONTRACTOROR DESIGNER OF RECORD SHALL ON
 THEIR LETTERHEAD PROVIDE A ITEMIZED LIST WHERE THE 20%
 IN FUNDS WILL BE SPENT ON THIS PROJECT AND ALSO REFLECT
 ON THE PLANS.
  
 4) THE LIFE SAFETY SHEET IN ALL OF THE WHOLE FLOOR
 SHOWN AND IN THE WORK AREA INCLUSIVE OF THE ELEVATOR
 LOBBY THERE IS ONLY ONE EMERGENCY BATTERY BACK UP LIGHT
 INDICATED ON THE WHOLE FLOOR. 2014 FBC-B 1006.3.1
 ILLUMINATION LEVEL UNDER EMERGENCY POWER.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-31 Cont ID  
Sent By rlecky Date 2017-01-31 Time 14:37 Rev Time 0.00
Received By rlecky Date 2017-01-31 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-08 Cont ID  
Sent By scaldero Date 2017-03-08 Time 14:15 Rev Time 0.00
Received By scaldero Date 2017-03-08 Time 14:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-23 Cont ID  
Sent By scaldero Date 2017-01-23 Time 10:36 Rev Time 0.00
Received By scaldero Date 2017-01-23 Time 10:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-16 Cont ID  
Sent By   Date 2017-03-16 Time   Rev Time 0.00
Received By lmarchan Date 2017-02-28 Time 15:30 Sent To  
Notes
2017-03-01 15:30:50B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-01 Cont ID  
Sent By lmarchan Date 2017-03-01 Time 15:25 Rev Time 0.00
Received By lmarchan Date 2017-01-18 Time 14:45 Sent To  
Notes
2017-01-19 14:45:44B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 07:46 Rev Time  
Received By jwitmer Date 2017-01-28 Time 06:16 Sent To  
Notes
2017-01-28 07:45:27NO CHANGE OF OCCUPANCY/ NO FEES DUE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-03 Cont ID  
Sent By ccole Date 2017-03-03 Time 11:38 Rev Time 0.00
Received By ccole Date 2017-03-03 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By ccole Date 2017-01-30 Time 11:58 Rev Time 0.00
Received By ccole Date 2017-01-30 Time 11:58 Sent To  
Notes
2017-01-30 12:08:331ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010585
 1/30/17
  
 1) THE PLAN INDICATES A DUCT PENETRATING THE INTERIOR
 EXIT STAIRWELL ENCLOSURE- SEE SECTION 1022.5 FBC-14
 BUILDING AND RELOCATE THE DUCT.
  
 2) PROVIDE AC CALCULATIONS FOR THE NEW MINI-SPLIT
 SYSTEM PER SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 AHU-1.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE NEW CU-1
 ON THE EXISTING RACK- SECTION 301.15.
  
 5) SHOW THE REQUIRED RETURN AIR TRANSFERS FROM ROOMS
 WITH FULL HEIGHT PARTITIONS- SECTION 601.5
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-08 Cont ID  
Sent By gjohnson Date 2017-03-08 Time 16:46 Rev Time 0.00
Received By gjohnson Date 2017-03-08 Time 15:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 09:05 Sent To  
Notes
2017-02-02 10:42:391ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. DISPROPORTIONATE COST. THE CONTRACT VALUE AS STATED
 INDICATES A CONTRACT VALUE OF $31,500. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 202.4.1 CAN REQUIRE UP
 TO 20% ($6,300.00) OF THE CONTRACT VALUE IN ACCESSIBLE
 UPGRADES TO THE TENANT SPACE. THE SEQUENCE IN HOW THE
 FUNDS ARE TO BE SPENT WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE NOTE THE BATHROOM WITHIN THE TENANT SPACE DOES
 NOT MEET THE REQUIREMENTS FOUND IN THE 2014
 FBC-ACCESSIBILITY CODE:
 604.3.1 SIZE
 604.4 SEATS.
 604.5 GRAB BARS.
 604.7 DISPENSERS
 606.1 LAVATORIES AND SINKS SHALL COMPLY WITH 606.
 608.1 SHOWER COMPARTMENTS SHALL COMPLY WITH 608.
  
 EITHER THE CONTRACTOR OR DESIGNER OF RECORD SHALL ON
 THEIR LETTERHEAD PROVIDE A ITEMIZED LIST WHERE THE 20%
 IN FUNDS WILL BE SPENT ON THIS PROJECT AND ALSO REFLECT
 ON THE PLANS.
  
 2. SHOW EXISTING WATER FOUNTAIN AND SERVICE SINK
 REQUIRED BY FBC PL TABLE 403.1
  
  
  
  