| Plan Review Stops For Permit 17010584 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-01-23 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-23 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-23 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2017-01-23 13:44:36 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | PLEASE PROVIDE PER FBC, DRAWINGS SHOWING A FLOOR PLAN | | | AND EXTENT OF REWIRING TO BE PERFORMED. | | | CLARIFY IF THERE ARE EXISTING SMOKE DETECTORS ON | | | PROPERTY. FBC RES 314-315 | | | SHOW ON PLANS NOTES TO PROVIDE REQUIRED TAMPER | | | RESISTANT RECEPTACLE THROUGHOUT. FBC RES E4002.14 | | | SHOW ON PLANS NOTES TO PROVIDE REQUIRED AFCI | | | PROTECTION. | | | | | | A COMPLETE REVIEW WILL BE CONDUCTED UPON SUBMITTAL OF | | | DRAWINGS | | | | | | V. PEREZ | | | *6717 |
|
|