Plan Review Details - Permit 17010555
Plan Review Stops For Permit 17010555
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-16 Cont ID  
Sent By shill Date 2017-05-16 Time 12:49 Rev Time 0.00
Received By shill Date 2017-05-16 Time 08:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By shill Date 2017-03-23 Time 11:37 Rev Time 0.00
Received By shill Date 2017-03-23 Time 11:37 Sent To  
Notes
2017-03-23 11:37:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. IT IS SUGGESTED THAT REVISIONS A THROUGH D, PLAN
 CHANGES PRIOR TO PERMIT ISSUANCE, CLOUDS BE REMOVED
 FROM THE PLAN. BEFORE REMOVING CLOUDS, SEE OTHER
 COMMENTS AND ENSURE THAT ALL REVISIONS ARE CORRECTLY
 MARKED. SOME CLOUDS SHOW CHANGES MADE BEFORE PERMIT
 ISSUANCE, BUT THE CHANGES WERE NOT ON THE ISSUED SET
 AND THEREFORE REQUIRE REVIEW. IT IS NOT CLEAR WHETHER
 THE CLOUD IS NUMBERED IN CORRECTLY OR IF THE PAGES
 SUBMITTED FOR PERMIT WERE NOT CURRENT.
  
 2. LS0.1 AND OTHER SHEETS, A DIMENSION "22 MIN" WAS
 ADDED; NOT CLEAR WHAT THIS IS, CLARIFY OR REVISE. IT IS
 NOT CLEAR WHY THE DIMENSION OF 22 TO THE CENTER OF
 CORRIDORS WHICH ARE OVER 5' IS NECESSARY. IS APPLICANT
 PROPOSING TO REDUCE THE WIDTH OF THE CORRIDORS? IF THIS
 IS THE CASE, INCLUDE THE TOTAL WIDTH FOR EACH CORRIDOR,
 EACH FLOOR. A COMPLETE PLAN REVIEW CANNOT BE DONE AT
 THIS TIME DUE TO LACK OF INFORMATION. FBC CHAPTER 10.
  
 3. LS0.1 AND OTHER SHEETS, BOTTOM LEFT CORNER OF
 PARKING GARAGE, A RAMP IS SHOWN FOR ACCESS TO FIRST
 LEVEL, BUT LACKS A STAIR. SEE FBC A 405.2, ADVISORY,
 THE ADDITIONAL DISTANCE CRATED BY A RAMP CAUSES A
 HARDSHIP FOR SOME PEOPLE AND A STAIR IS RECOMMENDED.
  
 4. LS0.1, A3 OCCUPANT LOADS AT THE POOL AREA WERE
 REMOVED, RESTORE OCCUPANT LOADS, FBC CHAPTER 10.
  
 5. LS0.3, OTHER LEVELS AND UNITS, BALCONIES WERE ADDED
 TO C2, NOT CLOUDED. TO EXPEDITE PLAN REVIEW, CLOUD ALL
 CHANGES, FBC 107.
  
 6. LS0.4, AMENITY DECK 4TH FLOOR IS CLOUDED BUT IT IS
 NOT CLEAR WHAT CHANGED. THIS SHEET IS NAMED "LEVELS
 4-7" IN PROJECTDOX BUT THE GRAPHIC TITLE IS 4TH FLOOR,
 CORRELATE AND COORDINATE NAME CHANGE WITH LIBRARIANS.
  
 AS IT IS NOT CLEAR WHETHER THIS SHEET IS FOR FLOORS
 4-7, OR 4TH FLOOR ONLY. BUILDING REVISIONS WERE
 SUBMITTED FOR THE OTHER FLOORS, BUT LIFE SAFETY PLANS
 WERE SUBMITTED FOR 1-4 (1-7?) ONLY.
  
 7. A2.7 SHOWS A NEW REVISION D WHICH WAS NOT ON THE
 ISSUED PERMIT SET (BUT IS NOTED AS PLAN REVIEW
 COMMENTS). CLARIFY WHAT CHANGED OR REMOVE. THIS MAY
 AFFECT OTHER SHEETS; NOT EACH SHEET WAS VERIFIED FOR
 REVISIONS REVIEWED.
  
 8. AREA ABOVE STAIR #4, 121 ADDED AND 170 REMOVED, NOT
 CLEAR WHAT CHANGED.
  
 9. A4.2.A, A4.5.A, OTHER SHEETS, SOME BALCONIES ARE
 NARROWER THAN 5'. IT IS NOT CLEAR HOW THE REQUIREMENT
 FOR THIS TO BE ADAPTABLE IS MET, FBC A FAIR HOUSING
 REQUIREMENT 4.
  
 10. A5.1.6, THE CLOUD AT DETAIL C CLUB HOUSE ROOF DECK
 KITCHEN IS LABELED DELTA C, BUT DOES NOT APPEAR TO BE
 ON THE ISSUED SET. UNABLE TO LOCATE A DELTA 1.
  
 11. NOT CLEAR WHAT WAS MODIFIED AT THE CLUBHOUSE, SHEET
 A5.2.1 AND OTHER PAGES, FBC 107.
  
 12. A5.4 RES LOBBY 114, APPEARS THAT A DOOR WAS REMOVED
 FROM THE DOOR SCHEDULE AND NOW REFERS TO STOREFRONT,
 CLARIFY CHANGE AND HOW THIS AFFECTS EXITING.
  
 13. A5.4 AND ELEVATIONS, APPEARS THAT A DOOR WAS
 REMOVED FROM THE BRIDGE, CLARIFY CHANGE AND HOW THIS
 AFFECTS EXITING, FBC 107.
  
 14. A5.4, A5.4.1, CLARIFY DOOR CHANGES, FBC 107, IN
 PARTICULAR CODE RELATED CHANGES (PANIC DEVICES,
 CLOSERS, NON ACCESSIBLE HARDWARE, FIRE RATINGS, ETC.).
  
 15. A8.2, DETAILS 12 AND 16, POSSIBLY OTHER LOCATIONS,
 STUCCO OVER SHEATHING IS TO HAVE A BOND BREAK TO
 PROPERLY RESIST WATER AND PROTECT THE VERTICAL
 SHEATHING. EITHER REVISE OR EXPLAIN RATIONALE. DUE TO
 THE CONFIGURATION OF THE DETAIL IT IS NOT CLEAR TO WHAT
 EXTENT THIS IS EXPOSED TO WEATHER, FBC 107.
 THIS AFFECTS OTHER DETAILS, FOR INSTANCE 9-A8.3, CHECK
 ALL.
  
 16. DETAIL 9-S4.2 SHOWS WOOD TRUSSES, SEE FBC B 603.1
 AND REVISE TO SPEC FRT OR CLARIFY.
  
 17. SEE MECHANICAL COMMENTS REGARDING LOUVERS. PROVIDE
 SPEC SHEETS AND EVIDENCE OF COMPLIANCE WITH FBC B 1609,
 603. ADDITIONAL INFORMATION MAY BE REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-27 Cont ID  
Sent By jleahy Date 2017-06-27 Time 15:41 Rev Time 0.00
Received By jleahy Date 2017-06-27 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 12:09 Rev Time 0.00
Received By jleahy Date 2017-05-24 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-13 Cont ID  
Sent By vperez Date 2017-03-13 Time 14:39 Rev Time 0.00
Received By vperez Date 2017-03-13 Time 14:39 Sent To  
Notes
2017-03-13 14:41:26INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
  
 PLEASE PROVIDE A NARRATIVE FOR THE REVISED SUBMITTAL,
 NOT MINOR CHANGES....
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By scaldero Date 2017-05-08 Time 11:21 Rev Time 0.00
Received By scaldero Date 2017-05-08 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-16 Cont ID  
Sent By rlindow Date 2017-02-16 Time 11:55 Rev Time 0.00
Received By scaldero Date 2017-02-16 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-12 Cont ID  
Sent By cpuell Date 2017-07-12 Time 15:25 Rev Time 0.00
Received By cpuell Date 2017-06-26 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-01 Cont ID  
Sent By cpuell Date 2017-06-01 Time 14:07 Rev Time 0.00
Received By cpuell Date 2017-05-04 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By lmarchan Date 2017-04-21 Time 15:36 Rev Time 0.00
Received By lmarchan Date 2017-02-14 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-07 Cont ID  
Sent By ccole Date 2017-07-07 Time 16:44 Rev Time 0.00
Received By ccole Date 2017-07-07 Time 16:44 Sent To  
Notes
2017-07-07 16:46:41MECHANICAL PROVISOS- 7/7/17
 REVISION #17010555
  
 1) THE FIRST COMPANY DOE CERTIFICATIONS FOR THE
 APARTMENT AC SYSTEMS MUST BE ELECTRONICALLY UPLOADED
 INTO THE DOCUMENT FILE.
  
 2) PROVIDE A LETTER CONFIRMING THAT THE EOR WILL BE THE
 RESPONSIBLE PARTY TO CONDUCT INSPECTIONS, AND
 ULTIMATELY PROVIDE A LETTER APPROVING THE INTUMESCENT
 PAINTING OF THE AC CLOSET DOORS IN THE APARTMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-16 Cont ID  
Sent By ccole Date 2017-05-16 Time 11:26 Rev Time 0.00
Received By ccole Date 2017-05-16 Time 11:26 Sent To  
Notes
2017-05-16 11:44:432ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010555
 5/16/17
  
 RESULTS: DENIED.
  
 1) THE REVISED SHEET M-2.4B WHICH IS PART OF THIS
 REVISION PER THE ARCHITECT'S NARRATIVE, WAS NOT
 UPLOADED FOR REVIEW- PLEASE PROVIDE THE SHEET.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 POOL BATHROOMS AC SYSTEM, AND REVISE THE ENERGY
 CALCULATIONS AND AC EQUIPOMENT SCHEDULE TO INCLUDE THE
 SYSTEM.
  
 3) M-4.1, UNIT A1: IT APPEARS THAT EF-1 IS UTILIZING
 TWO EXHAUST DUCTS AND TWO EXHAUST TERMINATIONS- PLEASE
 CLARIFY.
  
 4) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS.
 MANUFACTURER'S SPECIFICATIONS FOR THE FIRST COMPANY
 UNIT INDICATE "HOT DISCHARGE AIR" COMING OUT OF THE
 CONDENSER. PLEASE RELOCATE ALL O/A INTAKES WITHIN 10'
 HORIZONTALLY OF THE CONDENSER- SECTION 401.4
  
 5) PROVIDE AHRI CERTIFICATES FOR THE FIRST COMPANY
 SYSTEMS TO VERIFY THEY ARE RATED AT 14 SEER.
  
 6) NOW THAT THE EMS IS ELIMINATED PLEASE INDICATE
 COMPLIANCE WITH HVAC SYSTEM CONTROLS AS REQUIRED BY
 SECTION C403.2.4- C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By ccole Date 2017-02-23 Time 17:01 Rev Time 0.00
Received By ccole Date 2017-02-23 Time 17:01 Sent To  
Notes
2017-02-24 07:13:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #1701055
 2/24/17
  
 1) PLEASE PROVIDE A NARRATIVE FORM THE DESIGN
 PROFESSIONAL THAT ITEMIZES SHEET-BY-SHEET WHAT CHANGES
 WERE MADE TO THE APPROVED PLANS. PLEASE NOTE THAT THE
 NEW UPLOADED SHEETS M-5.1 & M-5.2 DO NOT APPEAR TO HAVE
 BEEN REVISED.
  
 2) THE REVISED LOCATIONS OF THE O/A INLETS FOR THE
 APARTMENT AC SYSTEMS AND SOME OF THE EXISTING LOCATIONS
 APPEAR TO BE WITHIN 10' OF THE EXHAUST FROM THE
 CONDENSER- SEE SECTION 401.4.
  
 3) REFER TO SECTION 401.5 AND INDICATE WHAT TYPE OF
 CORROSION RESISTANT PROTECTION WILL BE INSTALLED OVER
 THE O/A INTAKES OPENINGS- SCREENS, LOUVERS, OR GRILLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-11 Cont ID  
Sent By gjohnson Date 2017-07-11 Time 12:32 Rev Time 0.00
Received By gjohnson Date 2017-07-11 Time 12:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-22 Cont ID  
Sent By gjohnson Date 2017-05-22 Time 11:53 Rev Time 0.00
Received By gjohnson Date 2017-05-22 Time 11:53 Sent To  
Notes
2017-05-22 11:57:481ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE REVISED STORM RISER DISGRAM FOR
 CHANGES MADE TO STORM DRAIN SYSTEM. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-13 Cont ID  
Sent By gjohnson Date 2017-03-13 Time 15:50 Rev Time 0.00
Received By gjohnson Date 2017-03-13 Time 15:50 Sent To  
Notes
2017-03-13 15:54:49 
 1ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A NARRATIVE SUBMITTAL LETTER
 INDICATING THE REVISION ON EACH SHEET AND EACH REVISION
 BEING DONE ON THAT SHEET. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-07-12 Cont ID  
Sent By cpuell Date 2017-07-12 Time 15:25 Rev Time 0.00
Received By cpuell Date 2017-07-11 Time 12:35 Sent To  
Notes
2017-07-11 12:34:527/11/17 DIG. SIGNATURE ON PLUMBING PAGES IS GOOD/GPJ
2017-07-07 16:51:31MECH PLANS AND DOCUMENTS DIG/SIGS VERIFIED- CCOLE
 7/7/17
2017-05-22 11:53:265/22/17 PLUMBING PAGES ARE NOT DIG SIGNED GPJ
2017-05-16 10:18:155/16/17 ARCH & STRUCT SHEETS DIGITAL SIGNATURE OK (SH)
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By shill Date 2017-03-23 Time 12:13 Rev Time 0.00
Received By shill Date 2017-03-23 Time 12:13 Sent To  
Notes
2017-03-23 11:41:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 VERIFIED A & S SHEETS - DIGITAL SIGNATURE/SEAL OK;
 RESUBMITTED SHEETS NEED TO BE VERIFIED.
 M, E, P SHEETS ARE NOT SIGNED AND SEALED. WHEN
 RESUBMITTING, RESUBMIT SIGNED AND SEALED DOCUMENTS
 FS471.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-01 Cont ID  
Sent By aaponte Date 2017-06-01 Time 12:12 Rev Time 0.00
Received By aaponte Date 2017-06-01 Time 12:12 Sent To  
Notes
2017-06-01 12:12:26PROVISO: GROUND FLOOR UNITS FACING OPEN SPACE AT THE
 NORTH WING SHALL HAVE DIRECT ACCESS FROM OPEN SPACE
 INTO PATIO AREAS ACCORDING TO DAC 15-08A APPROVAL.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-28 Cont ID  
Sent By aaponte Date 2017-03-28 Time 15:44 Rev Time 0.00
Received By aaponte Date 2017-03-28 Time 15:44 Sent To  
Notes
2017-03-28 15:45:01PROVISO: GROUND FLOOR UNITS FACING OPEN SPACE AT THE
 NORTH WING SHALL HAVE DIRECT ACCESS FROM OPEN SPACE
 INTO PATIO AREAS ACCORDING TO DAC 15-08A APPROVAL.