| 2017-01-30 06:12:43 | 1) INDICATE THE SIZE AND THE CORRESPONDING EHD OF THE |
| | CSST BEING INSTALLED. WPB AMENDMENTS TO FBC |
| | SEC.107.2.1. |
| | 2) SHOW THE LOCATION OF THE MEDIUM PRESSURE GAS |
| | REGULATOR. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS |
| | SEC.409.4. |
| | 3) INDICATE ON THE PLAN IF THE EXISTING TANK TYPE WATER |
| | HEATER WAS GAS OR ELECTRIC. IF IT WAS ELECTRIC, THEN A |
| | SEPARATE ELECTRIC PERMIT WILL BE REQUIRED. |
| | 4) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER 2014 FBC-RES. |
| | SEC.G2426. |
| | 5) A PLAN HAS BEEN SUBMITTED SHOWING AND EN ELECTRIC |
| | OUTLET AND SOME ADDITIONAL WRITING THAT IS ILLEGIBLE. |
| | IS THIS ELECTRIC OUTLET NEW OR EXISTING? CLARIFY THE |
| | ADDITIONAL WRITING ON THE PLAN THAT CANNOT BE READ. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 6) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A |
| | COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| | PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| | THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| | THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| | 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| | WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. IN ADDITION, SUBMIT TWO COPIES OF THE PAGE FROM |
| | THE MANUFACTURER'S INSTALLATION MANUAL THAT SHOWS THE |
| | REQUIRED CLEARANCES FROM OPERABLE WINDOWS AND DOORS. |
| | 8) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. |
| | 9) SOME OF THE INFORMATION ON THE PLAN IS CUT OFF THE |
| | PAGE. SUBMIT A PLAN WITH ALL NOTES.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |