Plan Review Details - Permit 17010407
Plan Review Stops For Permit 17010407
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-06-12 Cont ID  
Sent By cthroop Date 2017-06-12 Time 10:52 Rev Time 0.00
Received By cthroop Date 2017-06-12 Time 10:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-30 Cont ID  
Sent By cthroop Date 2017-05-30 Time 15:21 Rev Time 0.00
Received By cthroop Date 2017-05-30 Time 14:51 Sent To  
Notes
2017-05-30 15:27:51BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE WINDOW AND DOOR SCHEDULE WITH DESIGN WIND
 LOADS FOR EACH OPENING. 2ND REQUEST.
 2. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. 2ND
 REQUEST
 3. ORIGINAL VALUE FOR MASTER PERMIT 16040039 WAS $1000.
 REVISON IS FOR SUBSTANTIAL INCREASE IN SOW. ADJUST
 VALUE ACCORDINGLY TO REFLECT INCREASE SOW. 2ND REQUEST
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-04 Cont ID  
Sent By cthroop Date 2017-05-04 Time 08:43 Rev Time 0.00
Received By cthroop Date 2017-05-04 Time 08:34 Sent To  
Notes
2017-05-04 08:51:15BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLANS SUBMITTED FOR REVISION INDICATE NEW WINDOWS
 AND DOORS NOT ON ORIGINAL PLANS.
 2. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
 3. PROVIDE WINDOW AND DOOR SCHEDULE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-17 Cont ID  
Sent By cthroop Date 2017-01-17 Time 13:47 Rev Time 0.00
Received By cthroop Date 2017-01-17 Time 13:47 Sent To E
Notes
2017-01-17 13:49:08BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ALL SUBMITTALL DOCUMENTS SHALL BE IN DUPLICATE.
 2. ELECTRICAL PERMIT REQUIRED.
 3. PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
 4. DESCRIPTION OF INFORMATION BEING SUBMITTED ON PLAN
 REVIEW REQUEST FORM "REVISED PLANS 2 COPIES. TUB
 INSTEAD OF SHOWER" DOES NOT REFLECT THE INCREASED SCOPE
 OF WORK SHOWN ON SUBMITTED DRAWINGS. NEW PLANS INDICATE
 THE FOLLOWING CHANGES:
 A. RE-LOCATE 2 ELECTRICAL METERS.
 B. REMOVE AND REPLACE 14 WINDOWS.
 C. REMOVE AND BLOCK UP 6 WINDOWS.
 D. REMOVE AND REPLACE 4 DOORS.
 5. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
 6. FRAMING DETAIL FOR WINDOW OPENINGS TO BE BLOCKED UP
 DOES NOT INCLUDE DETAIL TO INTERLOCK WITH EXISTING WALL
 SYSTEM.
 7. VALUE OF NEW WORK CANNOT BE ASSESSED AT THIS TIME.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND
 DOOR SUBMITTALS.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By jleahy Date 2017-05-03 Time 08:26 Rev Time 0.00
Received By jleahy Date 2017-05-03 Time 08:26 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 18:07 Rev Time 0.00
Received By mvaldes Date 2017-01-25 Time 18:07 Sent To  
Notes
2017-01-25 18:18:48REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE ELECTRICAL PLANS TO INCLUDE RISER DIAGRAM
 WITH CONDUIT & WIRE SIZES, GROUNDING DETAIL, COMPLETE
 LOAD CALCULATIONS, & PANEL SCHEDULES. FBC-107.3.5.3
  
 2] PLANS MUST BE SIGN AND SEALED BY DESIGN PROFFESIONAL
 AND SUBMITTED IN 2 COPIES. FBC-107
  
 3] SHOW 2 20 AMP SMALL APPLIANCE CIRCUITS & SHOW GFCI
 RECEPTACLE OUTLET SPACING IN KITCHEN. FBC-R SECTIONS
 E3901.3 & E3902.6
  
 4] SHOW A 20 AMP CIRCUIT & SHOW GFCI RECEPTACLE OUTLET
 WITHIN 3' OF BATHROOM SINK. FBC-R SECTIONS E3901.6 &
 E3902.1
  
 5] SMOKE ALARMS REQUIRED PER FBC-R SECTIONS 314 & 315.
  
 6] TAMPER RESISITANT RECEPTACLES REQUIRED PER FBC-R
 SECTION E4002.14.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-06-12 Cont ID  
Sent By cthroop Date 2017-06-12 Time 10:51 Rev Time 0.00
Received By cthroop Date 2017-06-08 Time 13:06 Sent To  
Notes
2017-06-09 13:07:07RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-30 Cont ID  
Sent By cthroop Date 2017-05-30 Time 15:21 Rev Time 0.00
Received By cthroop Date 2017-05-25 Time 10:44 Sent To  
Notes
2017-05-26 10:44:31RESUB OF REVISION ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By cthroop Date 2017-05-04 Time 08:43 Rev Time 0.00
Received By cthroop Date 2017-05-01 Time 10:05 Sent To  
Notes
2017-05-02 10:09:00RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 18:20 Rev Time 0.00
Received By mvaldes Date 2017-01-12 Time 13:06 Sent To  
Notes
2017-01-13 13:06:19REVISION ROUTED TO TKLARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-04 Cont ID  
Sent By tklarge Date 2017-05-04 Time 06:08 Rev Time 0.00
Received By tklarge Date 2017-05-04 Time 05:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-17 Cont ID  
Sent By tklarge Date 2017-01-17 Time 12:42 Rev Time 0.00
Received By tklarge Date 2017-01-17 Time 12:27 Sent To  
Notes
2017-01-17 12:42:221) TWO SETS OF PLANS ARE REQUIRED TO BE SUBMITTED FOR
 REVIEW. ONLY ONE SET HAS BEEN SUBMITTED. WPB AMEND. TO
 FBC SEC.107.1.
 2) PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER THE FL. ADMIN. CODE
 RULE 61G15-23.001. SEE BELOW:
  
 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL:
 (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS,
 OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE
 AND BEING FILED FOR PUBLIC RECORD;
  
 (4) ADDITIONAL REQUIREMENTS FOR PLANS OR PRINTS,
 ENGINEERING SPECIFICATIONS AND CALCULATIONS, AND
 ENGINEERING REPORTS OR OTHER DOCUMENTS. WHEN AN
 ENGINEER SIGNS, DATES AND SEALS ANY OF THE FOLLOWING
 TYPES OF DOCUMENTS PLANS OR PRINTS UNDER THE PROVISIONS
 OF SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS
 RULE, THE FOLLOWING ADDITIONAL INFORMATION MUST BE
 INCLUDED:
 (A) PLANS AND PRINTS. EVERY SHEET WITHIN THE PLANS AND
 PRINTS MUST BE SIGNED, DATED AND SEALED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 1. A TITLE BLOCK SHALL BE USED ON EACH SHEET OF PLANS
 OR PRINTS AND SHALL CONTAIN THE PRINTED NAME, ADDRESS,
 AND LICENSE NUMBER OF THE ENGINEER WHO HAS SIGNED,
 DATED AND SEALED THE PLANS OR PRINTS.
 2. IF THE ENGINEER SIGNING, DATING AND SEALING
 ENGINEERING PLANS OR PRINTS IS PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS; THE TITLE BLOCK
 SHALL CONTAIN THE PRINTED NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  