Plan Review Details - Permit 17010393
Plan Review Stops For Permit 17010393
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-25 Cont ID  
Sent By cthroop Date 2017-01-25 Time 09:59 Rev Time 0.00
Received By cthroop Date 2017-01-25 Time 09:59 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 14:38 Rev Time 0.00
Received By mvaldes Date 2017-01-25 Time 12:59 Sent To HIST
Notes
2017-01-25 15:13:35REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO"S
  
 1] ELECTRICAL PANEL SHALL HAVE SUFFICIENT SPACE IN
 MECHANICAL ROOM AND THE AREA SHALL NOT BE A CLOTHES
 CLOSET. FBC-R SECTIONS E3501 & E3405.4
  
 2] INCLUDE INTERSYSTEM BONDING TERMINAL PER FBC-R
 SECTION E3609.3
  
 3] SUBMIT LOW VOLTAGE SPECS FOR DIMMING PANELS (AT THE
 TIME OF INSPECTION)
  
 4] CORRECT SMOKE ALARM IN ROOM 213 (VERIFY LOCATION)
 FBC-R 314 & NFPA 72
  
 5] GENERATOR & LOW VOLTAGE SHALL BE UNDER A SEPERATE
 PERMIT.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-01-26 Cont ID  
Sent By fmittner Date 2017-01-26 Time 13:19 Rev Time 0.00
Received By fmittner Date 2017-01-26 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-26 Cont ID  
Sent By cpuell Date 2017-01-26 Time 14:02 Rev Time 0.00
Received By cpuell Date 2017-01-12 Time 12:49 Sent To  
Notes