Plan Review Details - Permit 17010356
Plan Review Stops For Permit 17010356
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-03 Cont ID  
Sent By jgomez Date 2017-04-03 Time 18:56 Rev Time 0.00
Received By jgomez Date 2017-03-30 Time 16:48 Sent To  
Notes
2017-03-30 16:49:02JGOMEZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-29 Cont ID  
Sent By jgomez Date 2017-03-29 Time 13:04 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 10:29 Sent To  
Notes
2017-03-28 10:29:52RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-19 Cont ID  
Sent By jgomez Date 2017-01-19 Time 13:01 Rev Time 0.00
Received By jgomez Date 2017-01-11 Time 08:35 Sent To  
Notes
2017-01-12 08:35:34REVISION ROUTED TO JGOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-04-03 Cont ID  
Sent By jgomez Date 2017-04-03 Time 18:56 Rev Time 0.00
Received By jgomez Date 2017-04-03 Time 18:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-29 Cont ID  
Sent By jgomez Date 2017-03-29 Time 09:07 Rev Time 0.00
Received By jgomez Date 2017-03-29 Time 07:49 Sent To  
Notes
2017-03-29 09:28:31RESIDENTIAL (R3) SECOND MECHANICAL REVISION CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW
 EQUIPMENT IS 17.5 SEER. ORIGINAL PLANS AND ENERGY
 CALCULATIONS WERE APPROVED WITH 19.50 SEER. ENGINEER OF
 RECORD WHO PERFORMED THE ENERGY CALCULATIONS NEED TO
 REVISE THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS TO REFLECT NEW EQUIPMENT. SEC. R103.2 AND
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. MECHANICAL ENGINEER OF RECORD
 TO PROVIDE REVISED ENERGY CALCULATIONS AND COMPLETE
 EQUIPMENT SIZING CALCULATIONS.
 NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS ARE PROPERLY SIGNED AND
 SEALED TO AVOID CONFLICTS/DELAYS. ALSO, OWNER TO SIGN
 THE ENERGY CALCULATIONS AT THE BOTTOM OF THE FORM.
  
 2- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: SPECIFY THE SIZE OF THE TRANSFER DUCT TO
 VERIFY COMPLIANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-19 Cont ID  
Sent By jgomez Date 2017-01-19 Time 13:01 Rev Time 0.00
Received By jgomez Date 2017-01-19 Time 13:01 Sent To  
Notes
2017-01-19 13:01:13RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE IS AN ENGINEER OF RECORD WHO DESIGNED THE
 MECHANICAL PLANS. PLANS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD SHOWN ON THE BOTTOM RIGHT OF
 PLANS. CHAPTER 471 FLORIDA STATUTE.
  
 2- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW
 EQUIPMENT IS 16 SEER. ORIGINAL PLANS AND ENERGY
 CALCULATIONS WERE APPROVED WITH 19.50 SEER. NEED TO
 PROVIDE EQUIPMENT WITH 19.50 SEER EFFICIENCY OR
 ENGINEER OF RECORD WHO PERFORMED THE ENERGY
 CALCULATIONS NEED TO REVISE THE ENERGY CALCULATIONS
 ACCORDINGLY. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 3- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]