Plan Review Details - Permit 17010356
| Plan Review Stops For Permit 17010356 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-04-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-04-03 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-30 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2017-03-30 16:49:02 | JGOMEZ'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-29 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-27 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2017-03-28 10:29:52 | RESUB ROUTED TO JGOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-01-19 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-01-11 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2017-01-12 08:35:34 | REVISION ROUTED TO JGOMEZ |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-04-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-04-03 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-04-03 |
Time |
18:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-29 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-29 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2017-03-29 09:28:31 | RESIDENTIAL (R3) SECOND MECHANICAL REVISION CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW | | | EQUIPMENT IS 17.5 SEER. ORIGINAL PLANS AND ENERGY | | | CALCULATIONS WERE APPROVED WITH 19.50 SEER. ENGINEER OF | | | RECORD WHO PERFORMED THE ENERGY CALCULATIONS NEED TO | | | REVISE THE ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS TO REFLECT NEW EQUIPMENT. SEC. R103.2 AND | | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | RESPONSE: REPEAT COMMENT. MECHANICAL ENGINEER OF RECORD | | | TO PROVIDE REVISED ENERGY CALCULATIONS AND COMPLETE | | | EQUIPMENT SIZING CALCULATIONS. | | | NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS AND | | | EQUIPMENT SIZING CALCULATIONS ARE PROPERLY SIGNED AND | | | SEALED TO AVOID CONFLICTS/DELAYS. ALSO, OWNER TO SIGN | | | THE ENERGY CALCULATIONS AT THE BOTTOM OF THE FORM. | | | | | | 2- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN | | | AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | RESPONSE: SPECIFY THE SIZE OF THE TRANSFER DUCT TO | | | VERIFY COMPLIANCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-01-19 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-01-19 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2017-01-19 13:01:13 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- THERE IS AN ENGINEER OF RECORD WHO DESIGNED THE | | | MECHANICAL PLANS. PLANS NEED TO BE SIGNED AND SEALED BY | | | THE ENGINEER OF RECORD SHOWN ON THE BOTTOM RIGHT OF | | | PLANS. CHAPTER 471 FLORIDA STATUTE. | | | | | | 2- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW | | | EQUIPMENT IS 16 SEER. ORIGINAL PLANS AND ENERGY | | | CALCULATIONS WERE APPROVED WITH 19.50 SEER. NEED TO | | | PROVIDE EQUIPMENT WITH 19.50 SEER EFFICIENCY OR | | | ENGINEER OF RECORD WHO PERFORMED THE ENERGY | | | CALCULATIONS NEED TO REVISE THE ENERGY CALCULATIONS | | | ACCORDINGLY. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | 3- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN | | | AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
|