Plan Review Details - Permit 17010294
Plan Review Stops For Permit 17010294
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-12 Cont ID  
Sent By jwitmer Date 2017-01-12 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2017-01-12 Time 13:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-15 Cont ID  
Sent By   Date 2017-02-15 Time   Rev Time  
Received By   Date 2017-02-15 Time   Sent To  
Notes
2017-02-15 07:23:15SEE APPROVALS UNDER PERMIT 16040977.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-02-15 Cont ID  
Sent By   Date 2017-02-15 Time   Rev Time  
Received By   Date 2017-02-15 Time   Sent To  
Notes
2017-02-15 07:22:09SEE APPROVALS UNDER PERMIT 16040977.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-15 Cont ID  
Sent By   Date 2017-02-15 Time   Rev Time  
Received By   Date 2017-02-15 Time   Sent To  
Notes
2017-02-15 07:22:52SEE APPROVALS UNDER PERMIT 16040977.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-15 Cont ID  
Sent By   Date 2017-02-15 Time   Rev Time  
Received By   Date 2017-02-15 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-15 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2017-02-15 Time 07:15 Sent To  
Notes
2017-02-15 07:16:12PALM BEACH COUNTY IMPACT FEES
 TRACKING NUMBER: MU-2017-004031-0000
 RECEIPT NO: 2017-0215-246
 $6,214.32
 J. W.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By jwitmer Date 2017-01-12 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2017-01-12 Time 13:37 Sent To  
Notes
2017-01-12 13:38:15IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-02-15 Cont ID  
Sent By   Date 2017-02-15 Time   Rev Time  
Received By   Date 2017-02-15 Time   Sent To  
Notes
2017-02-15 07:21:42SEE APPROVALS UNDER PERMIT 16040977.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-04 Cont ID  
Sent By tklarge Date 2017-02-04 Time 05:43 Rev Time 0.00
Received By tklarge Date 2017-02-04 Time 05:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-19 Cont ID  
Sent By tklarge Date 2017-01-19 Time 05:33 Rev Time 0.00
Received By tklarge Date 2017-01-19 Time 05:14 Sent To  
Notes
2017-01-19 05:15:36 
 1.) SHT. 5 OF 7 - THE PLANS SHOW TWO OF THE WATER
 SEVICES AS ONE INCH AND ALSO AS AN INCH AND A HALF.
 WHICH ONE IS IT? CLARIFY.
 2) SHOW THE CLEAR INSIDE DIMENSIONS (LXW) OF BOTH
 ACCESSIBLE TOILET ROOMS ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1. 2ND REQUEST.
 3) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY
 IN EACH TOILET ROOM. COMPLY WITH 2014 FBC-ACCESS.
 SECS.305, & 606.2. 2ND REQUEST.
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAINS. COMPLY WITH 2014 FBC- ACCESS. SECS.211 &
 602.SUBMIT A DRINKING FOUNTAIN DETAIL FOR REVIEW.
 5) SHT. 5 OF 7 - THE PLANS SHOW THE SANITARY SEWER
 CROSSING THE WATER SERVICE. THIS IS A VIOLATION AND
 CANNOT REMAIN AS DESIGNED. COMPLY WITH 2014
 FBC-PLUMBING SECS. 603.2, 703.1.
 6) A BACKFLOW PREVENTION DEVICE IS REQUIRED FOR EACH
 BUILDING, NOT ONE FOR BOTH BUILDINGS. 2014 FBC -
 PLUMBING SECS. 608.1,
 7) DRINKING FOUNTAINS ARE NOT PERMITTED IN THE TOILET
 ROOMS PER 2014 FBC-PLUMBING SEC.410.4.
 8) SHT. 5 OF 7 SHOWS PVC PIPE SUPPLYING HOSE BIBBS.
 THIS BRANCH FOR THE HOSE BIBBS IS CONSIDERED PART OF
 THE WATER DISTRIBUTION SYSTEM AND PVC IS NOT PERMITTED
 FOR THIS USE PER 2014 FBC-PLUMBING SEC. 605.4 & TABLE
 605.4.
 9) SHTS. 3 & 4 OF 13 SHOW WHAT APPEARS TO BE A DRAIN
 LINE RUNNING THROUGH THE CENTER OF EACH BUILDING AND
 LABELED AS " 8 INCH PVC SCH. 40 FLOOR DRAIN" & "6 INCH
 PVC SCH. 40 FLOOR DRAIN" BUT NO FLOOR DRAINS ARE SHOWN.
 CLARIFY. SUBMIT A RISER DIAGRAM FOR THESE DRAINS AND
 SHOW THEM ON THE CIVIL DRAWINGS WHERE THEY EXIT THE
 BUILDING. FLOOR DRAINS SHALL BE EQUIPPED WITH TRAP
 PRIMERS. 2014 FBC-PLUMBING SEC.1002.4. WHAT WILL BE
 DISCHARGING INTO THESE LINES? CLARIFY.
 10) SHT. 13 OF 13 - ADA ELEVATIONS - THE GRAB BAR
 BEHIND THE WATER CLOSET SHALL COMPLY WITH FBC-ACCESS.
 SEC.604.5.2 AND FIGURE 604.5.2. 2ND REQUEST.
 11) NONE OF THE FIXTURES ARE VENTED ON THE SANITARY
 RISERS. COMPLY WITH 2014 FBC-PLUMBING SECS. 901.2,
 901.2.1.
 12) THERE IS A 2 INCH DRY VENT SHOWN ON THE SANITARY
 RISER. WHAT IS THIS VENT FOR? IT IS NOT TO CODE. COMPLY
 WITH 2014 FPC SEC. 905.3.
 13) SHT. 5 OF 7 - SOUTH BUILDING - THE LOCATION OF THE
 CLEANOUT IN THE BUILDING SEWER ON THE WEST SIDE IS
 INSTALLED IN THE OPPOSITE DIRECTION OF FLOW AND WASTE
 WILL COLLECT IN THIS AREA AS DESIGNED. 2014
 FBC-PLUMBING SEC. 708.5.
 14) SHOW WATER SERVICE AND HOSE BIBS ON FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
 15) SHT.13 OF 13 SHOWS THE HEIGHT OF THE TOILET PAPER
 DISPENSER AS 4'-9" ABOVE THE FINISH FLOOR. THE HEIGHT
 OF THE TOILET PAPER DISPENSER SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC. 604.7.
 16) SHT. 3 OF 13 & SHT. 4 OF 13 - DRINKING FOUNTAIN BY
 COLUMN LINE E-1 AND A-1 - SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE DRINKING FOUNTAIN AND CLEARLY SHOW THE
 DRINKING FOUNTAIN AND SUBMIT AN ELEVATION DETAIL OF THE
 DRINKING FOUNTAIN. ONE DRINKING FOUNTAIN SHALL CCOMPLY
 WITH 2014 FBC- ACCESS. SECS.602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7 OR A SINGLE
 DRINKING FOUNTAIN SHALL COMPLY WITH SECS.602.1 THROUGH
 602.6 AND 602.7. (HILO TYPE UNIT).
 17) THE PLANS SHOW A LAVATORY IN THE TOILET ROOMS WITH
 A 24 INCH BY 24 INCH VANITY. THE VANITY DOES NOT COMPLY
 WITH 2014 FBC-SEC.606.2. SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE LAVATORY. THE LAVATORY SHALL BE
 POSITIONED FOR A FORWARD APPROACH. 2014 FBC - ACCESS.
 SEC,606.2. THE CLEAR FLOOR SPACE SHALL BE CENTERED ON
 THE FFIXTURE.
 18) SHUTOFF VALVES ARE REQD. ON THE WATER RISER PER
 2014 FBC-PLUMBING SEC.606.2.
 19) HOSE BIBBS SHALL BE EQUIPPED WITH INDIVIDUAL
 SHUTOFF VALVES .2014 FBC-PLUMBING SEC..606.2 (2).
 20) FULL OPEN VALVES SHALL BE INSTALLED ON THE WATER
 DISTRIBUTION SYSTEM PER 2014 FBC-PLUMBING SEC.606.1.
 21) WHAT IS THE WALL AND FLOOR FINISH IN THE TOILET
 ROOMS? COMPLYWITH 2014 FBC-BUILDING SECS. 1210.2.1
 THROUGH 1210.2.4.
 22) SHTS. 3 & 4 OF 13 - THE WATER RISERS ONLY SHOW ONE
 DRINKING FOUNTAIN IN EACH BUILDING BUT THE FLOOR PLAN
 SHOWS TWO SEPARATE FOUNTAINS IN EACH BUILDING. CLARIFY.
 23) THE SANITARY RISERS DO NOT COMPLY WITH 2014
 FBC-PLUMBING SEC. 912.1 FOR FIXTURES PERMITTED ON A
 HORIZONTAL WET VENT.
 24) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS.
 2014 FBC-PLUMBING SEC.708.3.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2017-01-12 Time 13:37 Sent To  
Notes
2017-01-12 13:37:45ROOF SOUTH BUILDING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-09 Cont ID  
Sent By eschneid Date 2017-02-09 Time 11:58 Rev Time 0.50
Received By eschneid Date 2017-02-09 Time 11:58 Sent To  
Notes
2017-02-09 11:58:15PASSED W/PROVISO
  
 1) PROVISO - THE PROPOSED ELEVATIONS DO NOT MATCH THE
 ISPR APPROVED ELEVATIONS OR THE SITE PLAN - DOOR
 LOCATIONS AND ROOF PITCH/HEIGHT. A MINOR SITE PLAN
 AMENDMENT WILL BE REQUIRED TO SHOW THE AS-BUILT
 CONDITIONS PRIOR TO THE CERTIFICATE OF OCCUPANCY FOR
 THE FIRST BUILDING ON THE SITE.
  
 2) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. DUMPSTER ENCLOSURE
 D. PARKING LOT STRIPING
 E. BICYCLE RACK
 F. SIGNS
 G. SITE LIGHTING. PROVIDE DETAILS FOR THE POLE LIGHT TO
 INCLUDE HOW THIS LIGHT WILL BE SHIELDED PREVENT GLARE
 INTO THE GEORGIA AVENUE RIGHT-OF-WAY WITH THE SITE
 LIGHTING PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.